Actulux SVM EI 24V-5A Installation Instruction Download Page 1

Installation instruction

Control Panel for Fire Ventilation

SVM 

EI

 24V-5A / SVM 

EI

 24V-8A

Fire ventilation   

Comfort ventilation

24VDC max. 5A/8A 

1 fire ventilation group, 1 comfort group 

Connection for manual control points, wind- and rain sensor, comfort switches, smoke detectors and 

Fireman’s Priority Switch.

Possibility for bus connection of 35 control panels

#211534 

Summary of Contents for SVM EI 24V-5A

Page 1: ... 24V 8A Fire ventilation Comfort ventilation 24VDC max 5A 8A 1 fire ventilation group 1 comfort group Connection for manual control points wind and rain sensor comfort switches smoke detectors and Fireman s Priority Switch Possibility for bus connection of 35 control panels 211534 ...

Page 2: ..._______________________________________________________ Comfort control ___________________________________________________________________________________________________ Wind and rain sensor ___________________________________________________________________________________________________ 230V power supply from group ______________________________________________________________________________...

Page 3: ...fety rules must therefore always be observed Νever short circuit a back up battery Do not use external chargers on installed batteries If unauthorized chargers are used explosive gasses can be released from the battery Do not drop back up batteries as strong acids can be released if they are broken Installation The control panel can weigh up to 7 kg and must be installed on a stable wall The mount...

Page 4: ... 27 KΩ you wish to detect the same way as the motor line This setting demands 3 wire cable from motor output to motor Current limiter type LIP function and setting if mounted The current limiter type LIP mounted on the opening system is used as current limiter between the 24V 48VDC supply and 1 or 2 actuators When the adjusted current limit is reached the speed of the actuators is reduced When the...

Page 5: ...us up signal gives 3x6 sec 18 sec One press on down closes the actuator completely for a period which is 18 sec longer than the complete opening time In order to avoid actuator pumping max 3 successive closing attempts will be allowed Potentiometer in Const pos As long as up signal or down signal are given the actuators are running Potentiometer in Puls variable pos The time on the above mentioned...

Page 6: ...INE FAIL AC FAIL YEL YEL BAT BAT ON DIP NO 1 2 OFF START termination DOME OPEN BLUE PS PS Black 2 5mm2 24VDC Batteries 2x 12V 7 2 Ah 24V Red 2 5mm2 Connection SVM EI 24V 5A 8A BUZZER B3 J5 J6 J7 A3 B1 B2 Serial Out next unit Connection to A1 prev unit 21 20 Gnd 23 22 Weather Gnd 24V A2 Serial In Connection from Bus connection for serial connection up to 35 pcs control units J4 Set J11 for batteri ...

Page 7: ... ON function Dismounted OFF function DIP 1 Conf Fireswitch No Fire switch active from 500 3 KΩ A short circuit of the smoke detector input will generate a line error Fire switch active from 0 3 KΩ A short circuit of the smoke detector input will generate alarm DIP 2 Failsafe No Line error on fire switch or detector puts the control in alarm Normal mode DIP 3 Temp Detekt No Line error on motor line...

Page 8: ...s adjusted according to the instructions Actuators should be closed when the wind is above 6 m s LED 3 on the main board indicates active weather sensor lights as long as input is active As long as the weather sensor is active motor inputs cannot be opened with comfort switches The weather sensor closes on all controls which are connected through bus connection On the input to weather station a we...

Page 9: ...re on actuator LED 5 Line failure fire switch red Lit for line failure on fire switch LED 6 Line failure smokesensor red Lit for line fail on smokes LED 7 BUS failure red Lit when local unit is not recieving signal LOCKOUT TEMP DETECT SERVICE TIMER SNITCH FAIL RELAY M WEEK OPEN OPTION SPRINKLER BUS COMFORT BUS FIRE 12 3 4 6 7 5 8 11 9 10 BUS Master BUS Slave END termination Con Fire Sig FAIL SAFE ...

Page 10: ...ng the Slave unit in lock out mode is by using a Fireman s Priority Switch 27 02 2018 ALARM ON ONE OF THE SLAVES SLAVE EVENT MASTER ALL OTHER SLAVES SMOKE FIRE MODE FIRE mode Lock Out mode MCP BVT FIRE MODE FIRE mode Lock Out mode MASTER SLAVE SLAVE SLAVE MCP SMOKE MCP SMOKE MCP SMOKE MCP SMOKE LOCK OUT LOCK OUT MASTER SLAVE SLAVE SLAVE MCP SMOKE MCP SMOKE MCP SMOKE MCP SMOKE LOCK OUT LOCK OUT Man...

Page 11: ...sement pour vérins électriques Producenten Manufacture Actulux A S Haandvaerkervej 2 9560 Hadsund Denmark Hersteller Usine de fabrication System for attestering og kontrol af ydeevne System for attestation and verification of performance SYSTEM 1 System zur Bescheinigung und Prüfung der Performance Système s d évaluation et de vérification de la constance des performances du produit Det bemyndiged...

Page 12: ...for Fire and Comfort Ventilation Type SVM EI 24V 5A SVM EI 24V 8A Control for Fire and Comfort Ventilation Type SVM EI 24V 5A SVM EI 24V 8A Service Maintenance Record System ID Date Company Engineer Next Due Comments ...

Page 13: ...act max 48V 0 5A Yes potential free contact max 48V 0 5A Failure output Yes potential free contact max 48V 0 5A Yes potential free contact max 48V 0 5A 24V DC for external use 24V DC max 0 5A at 230V operation 24V DC max 0 5A at 230V operation Bus communication Yes connection of 2 35 pcs control panels line detection Visual LED indication in front panel OK AC fault Low battery Line fault Alarm Com...