Installation and Commissioning Guide - Advance Split Ducted Outdoor Unit
Doc. No.0525-085 Ver. 2 22xxxx
Installation and Commissioning Guide
Advance Outdoor Units
24
PRELIMINARY DATA ONLY
Ver. 2.04 220704
THIS LABEL TO BE REMOVED ON SIGN-OFF
Specifications for Refrigeration
TABLE : REFRIGERATION PIPING - SINGLE PHASE
Reverse Cycle (Outdoor / Indoor)
CRV140S /
EVV140S
CRV160S /
EVV160S
CRV180S /
EVV180S
Max. Equivalent Pipe Length Range
metres
0 - 60
0 - 60
0 - 60
Max. Vertical Height Differential
(1)
metres
20
20
20
Field Pipe Size
Liquid Line
inch (mm)
3/8 (9.52)
3/8 (9.52)
3/8 (9.52)
Gas Line
inch (mm)
3/4 (19.05)
3/4 (19.05)
3/4 (19.05)
Outdoor Pipe Size
Liquid Line
inch (mm)
3/8 (9.52)
swaged
3/8 (9.52)
swaged
3/8 (9.52)
swaged
Gas Line
inch (mm)
3/4 (19.05)
swaged
3/4 (19.05)
swaged
3/4 (19.05)
swaged
Indoor Pipe Size
Liquid Line
inch (mm)
3/8 (9.52)
swaged
3/8 (9.52)
swaged
3/8 (9.52)
swaged
Gas Line
inch (mm)
3/4 (19.05)
swaged
3/4 (19.05)
swaged
7/8 (22.22)
(2)
swaged
NOTES
(1)
Included in maximum field pipe length.
(2)
Cut swaged end on the unit to fit field pipe.
TABLE : REFRIGERATION PIPING - THREE PHASE
Reverse Cycle (Outdoor / Indoor)
CRV160T /
EVV160S
CRV180T /
EVV180S
CRV210T /
EVV210S
CRV240T /
EVV240S
Max. Equivalent Pipe Length Range
metres
0 - 60
0 - 60
0 - 60
0 - 60
Max. Vertical Height Differential
(1)
metres
20
20
20
20
Field Pipe Size
Liquid Line
inch (mm)
3/8 (9.52)
3/8 (9.52)
3/8 (9.52) or 1/2
(12.7)
(2) (3)
1/2 (12.7)
Gas Line
inch (mm)
3/4 (19.05)
3/4 (19.05)
7/8 (22.2) or 1
(25.4)
(2) (3)
1 (25.4)
Outdoor Pipe Size
Liquid Line
inch (mm)
3/8 (9.52)
swaged
3/8 (9.52)
swaged
1/2 (12.7)
(2)
swaged
1/2 (12.7)
swaged
Gas Line
inch (mm)
3/4 (19.05)
swaged
3/4 (19.05)
swaged
7/8 (22.2)
swaged
7/8 (22.2)
swaged
Indoor Pipe Size
Liquid Line
inch (mm)
3/8 (9.52)
swaged
3/8 (9.52)
swaged
1/2 (12.7)
(2)
swaged
1/2 (12.7)
swaged
Gas Line
inch (mm)
3/4 (19.05)
swaged
7/8 (22.2)
(2)
swaged
1 (25.4) swaged 1 (25.4) swaged
NOTES
(1)
Included in maximum field pipe length.
(2)
Cut swaged end on the unit to for field pipe, if required.
(3)
For pipe runs 20-60m 1/2” and 1" pipe must be used.