Installation and Commissioning Guide - MultiElite 2 Split System
Doc. No. 9590-5009
Ver. 1 211221
10
Installation and Commissioning Guide
Multi Split System
08. Specifications
Table 08.1
Indoor units that can be used in combination
Number of connected units
1 to 5
Compressor stop/start frequency
Stop time
3 min or more
Power source voltage
Voltage supply
230VAC
Voltage fluctuation
+10% to -6% of rated voltage
1 Outdoor
Table 08.2
3 Indoor
4 Indoor
5 Indoor
Minimum Field Pipe Length (m) - 1 indoor unit
9
12
12
Maximum length for all rooms (m)
60
80
80
Maximum length for one indoor unit (m)
30
35
35
Maximum height different between indoor and
outdoor units (m)
OU higher than IU
15
15
15
OU lower than IU
15
15
15
Maximum height difference between indoor units (m)
10
10
10
NOTE
The installation must be performed in accordance with the requirement of local and national standards. The installation may
be slightly different in different areas.
When installing multiple indoor units with a single outdoor unit, ensure that the length of the refrigerant pipe and the
height dereference between the indoor and outdoor and indoor to indoor units meet the following requirements:
Unit: m/ft.