Trouble shooting: 

 

Fault Possible 

problem 

Recommended 

action 

Control Mode does not fit damper 

Two sizes of Control mode exist. 

Check correct selection (page 3) 

Control Mode does not fit to damper 
drive shaft when Control Mode is 

correctly positioned 

Damper shaft not in ‘damper closed’ 
position 

Damper shaft has an ‘indication groove’ which 
is parallel to damper blades. Damper must be 

in closed position before fitting Control mode. 

Control Mode not in released position 

If not electrically connected, check manual 
reset mechanism is released. (Refer to Control 

Mode label). If electrically powered, with ETR 
fitted, press and hold test switch on ETR. 

Control Mode does not operate 
electrically (ETR LED not illuminated) 

ETR not correctly fitted 

Refer to Page 3. 

Mode wired incorrectly / No power 

Refer to above wiring diagram 

ETR activated 

Remove probe section of ETR. Check electrical 
continuity of ETR probe, replace if necessary. 

Control Mode operated, but limited 
or no movement of damper blades 

evident 
 

The Control Mode is fitted back to front 

Universal: 
Label must be outer most. Check and correct if 

necessary. 
Compact: 
Label “FAIL SAFE CLOSED” facing outermost. 

Check and correct if necessary. 

Over tightening of M5 x 80mm screw. (3 
position only) 

Loosen screw to 5Nm torque. 

Damper/Control Mode positions not 
synchronised 

Remove Control Mode. Check damper closed 
(see indication Groove on damper shaft), and 

Control Mode released. Refit Control Mode. 

Obstruction impeding damper blade 

Check visually, remove obstruction. If 
necessary, remove Control Mode and operate 

damper drive shaft with 14mm A/F spanner. 

  

 

 

 

 

 

 

17. Standard Application & Wiring 
 
Control Mode 5 - 24V A.C. or 
D.C.24V - AC (19.2 - 28.8V) - 

50/60Hz24V - DC (21.6 - 28.8V) 
 
Control Mode 120 - 120V A.C.120V 
A.C. (96 - 132V) - 50/60Hz 
 
Control Mode 6 - 230V A.C.230V 
A.C. (196 - 264V) - 50/60Hz 
 
Supply On - Damper motors open.  
Supply Off - Damper springs closed.  
ETR Operates - Damper springs 
closed. 
 
12W (Maximum Motoring)4W 
(Maximum Reset) 
 
End Switches2 x S.P.D.T. 6(3)A, AC 

250V 
 

To isolate from main power supply, the system 
must incorporate a device, which disconnects 

the phase conductors, with at least 3mm 
contact gap. 

2 x 1 metre of halogen free, low smoke and fume 
electric cables are included with each control 

mode. The ETR is prewired with 0.5-metre 
halogen free low smoke and fume cable. 

 