HERCULES UNIT

Copyright © 2016

All rights reserve. This manual is a controlled document which contains confidential and proprietary information. No part or contents of this book maybe 

reproduced or transmitted in any form or by any means without the written permission of Actron Engineering Pty. Ltd.

REVISION 5.0       220201

ADDRESSING THE FANS USING 

EC CONTROL SOFTWARE

This documents implements the following settings:

Indoor Fans

Fan Number

PKV1400 / PKV2000

1

2591-xxx-101*

2

2591-xxx-201*

3

2591-xxx-301*

4

2591-xxx-401*

Outdoor Fans

Fan Number

PKV1400 / PKV2000

1

2506-138-101

2

2506-138-201

3

2506-138-301

4

2506-138-401

* For Indoor Fans, 2590-011 / 2590-014 / 2590-019 may be used, check actual motor installed.

 

2590-011 fans uses 2591-011-XXX.

 

both 2590-014 and 2590-019 fans uses 2591-014-XXX .

Summary of Contents for 2506-138-101

Page 1: ... Pty Ltd REVISION 5 0 220201 ADDRESSING THE FANS USING EC CONTROL SOFTWARE This documents implements the following settings Indoor Fans Fan Number PKV1400 PKV2000 1 2591 xxx 101 2 2591 xxx 201 3 2591 xxx 301 4 2591 xxx 401 Outdoor Fans Fan Number PKV1400 PKV2000 1 2506 138 101 2 2506 138 201 3 2506 138 301 4 2506 138 401 For Indoor Fans 2590 011 2590 014 2590 019 may be used check actual motor ins...

Page 2: ...ject to change without notice Copyright 2016 Actron Engineering Pty Ltd Hercules Units w CM100 Addressing the Fans Using EC Control Software 9590 7005 Rev 5 0 220201 Page 2 of 24 TABLE OF CONTENTS 1 0 Safety Precautions 4 2 0 Background 4 3 0 Tools and Accessories 4 4 0 EBM EC Control Software 4 5 0 Indoor Fans Addresses 22 6 0 Outdoor Fans Addresses 22 ...

Page 3: ... appliance Installer must incorporate a means of electrical disconnection isolator in the sub mains fixed wiring in accordance with the latest edition of the AS NZS 3000 also known as Australian Wiring Rules Secure the power cords and control cables that goes in out the unit Use the cable ties provided in the control box This unit is designed for use with R 410A refrigerant only Qualifications req...

Page 4: ...sign address to your fans 3 0 TOOLS AND ACCESSORIES PC Laptop with EBM EC Control software and instructions EBM Bus Cable 4 0 EBM EC CONTROL SOFTWARE The EBM EC Control software will need to be downloaded first into your PC Laptop prior to proceeding with fan configuration Ensure that you have the latest version which can be downloaded from R and D drive R Software EBM EC_Control_2 10 zip The soft...

Page 5: ...g the Fans Using EC Control Software 9590 7005 Rev 5 0 220201 Page 5 of 24 4 03 Disconnect the unit s J9 FBus 1 Terminal from CM100 Controller 4 04 Connect the other ends of the EBM Bus Cable between the disconnected J9 FBus 1 Terminal and the CM100 J9 FBus 1 Receptacle Disconnect J9 FBus 1 Terminal CM100 J9 FBus 1 Receptacle CM100 EBM Bus Cable J9 FBus 1 Terminal Unit J9 FBus 1 Terminal CM100 J9 ...

Page 6: ...g Pty Ltd Hercules Units w CM100 Addressing the Fans Using EC Control Software 9590 7005 Rev 5 0 220201 Page 6 of 24 4 05 Open the EC Control Application on the desktop If not on desktop the application can be found at the location you specified during the software installation process The following screen will be displayed 4 06 Make sure the Fab Name is Customer User name is Administrator and Lan...

Page 7: ... specifications are subject to change without notice Copyright 2016 Actron Engineering Pty Ltd Hercules Units w CM100 Addressing the Fans Using EC Control Software 9590 7005 Rev 5 0 220201 Page 7 of 24 4 07 Enter the password as topsecret and click on Login NOTE The password is case sensitive The following screen will be displayed ...

Page 8: ...00 Addressing the Fans Using EC Control Software 9590 7005 Rev 5 0 220201 Page 8 of 24 4 08 Note Make sure the COM port is detected correctly without any error when in error the colour of the port setting goes red with an error message In case of failure of communication with the interface following screen will be displayed Try closing and starting the Application in this case If the Communication...

Page 9: ...ations are subject to change without notice Copyright 2016 Actron Engineering Pty Ltd Hercules Units w CM100 Addressing the Fans Using EC Control Software 9590 7005 Rev 5 0 220201 Page 9 of 24 4 11 Click on Configuration Assistant 4 09 Turn ON the circuit breaker for the fan you wish to program keeping all the others OFF 4 10 Click on File ...

Page 10: ...roducts therefore specifications are subject to change without notice Copyright 2016 Actron Engineering Pty Ltd Hercules Units w CM100 Addressing the Fans Using EC Control Software 9590 7005 Rev 5 0 220201 Page 10 of 24 4 12 Click on Small Size Fab 4 13 Click on I have connected single Fan and then click Continue ...

Page 11: ...to change without notice Copyright 2016 Actron Engineering Pty Ltd Hercules Units w CM100 Addressing the Fans Using EC Control Software 9590 7005 Rev 5 0 220201 Page 11 of 24 4 14 Click on Start Search 4 15 When the search is complete the fan you wish to program will be displayed Check whether the type is displayed as MODBUS ebm papst Then click on Continue ...

Page 12: ...refore specifications are subject to change without notice Copyright 2016 Actron Engineering Pty Ltd Hercules Units w CM100 Addressing the Fans Using EC Control Software 9590 7005 Rev 5 0 220201 Page 12 of 24 4 16 The following screen will be displayed Click on Save 4 17 The following screen will be displayed Click on Finish ...

Page 13: ...ice Copyright 2016 Actron Engineering Pty Ltd Hercules Units w CM100 Addressing the Fans Using EC Control Software 9590 7005 Rev 5 0 220201 Page 13 of 24 4 18 After the config data is loaded the following screen is displayed with My Fab in green Click on the dropdown sign beside the My Fab menu The following screen will be displayed and the configuration data will start loading ...

Page 14: ...ore specifications are subject to change without notice Copyright 2016 Actron Engineering Pty Ltd Hercules Units w CM100 Addressing the Fans Using EC Control Software 9590 7005 Rev 5 0 220201 Page 14 of 24 4 19 The following screen will be displayed Right click on the fan showing MODBUS1_1 The following screen will be displayed ...

Page 15: ... are subject to change without notice Copyright 2016 Actron Engineering Pty Ltd Hercules Units w CM100 Addressing the Fans Using EC Control Software 9590 7005 Rev 5 0 220201 Page 15 of 24 4 20 Click on Set up fan parameters 4 21 Following screen will be displayed Make sure the status shows Fan OK Change Source of set value from Ain1 to RS485 Bus ...

Page 16: ...its products therefore specifications are subject to change without notice Copyright 2016 Actron Engineering Pty Ltd Hercules Units w CM100 Addressing the Fans Using EC Control Software 9590 7005 Rev 5 0 220201 Page 16 of 24 4 22 Click on Parameter set 1 4 23 Select Source of Parameter set switch as RS485 Bus ...

Page 17: ...products therefore specifications are subject to change without notice Copyright 2016 Actron Engineering Pty Ltd Hercules Units w CM100 Addressing the Fans Using EC Control Software 9590 7005 Rev 5 0 220201 Page 17 of 24 4 24 Select Control Mode as Closed Loop Speed Control The following screen will be displayed ...

Page 18: ...e design of its products therefore specifications are subject to change without notice Copyright 2016 Actron Engineering Pty Ltd Hercules Units w CM100 Addressing the Fans Using EC Control Software 9590 7005 Rev 5 0 220201 Page 18 of 24 4 25 Then click on Set The following screen will be displayed ...

Page 19: ...its products therefore specifications are subject to change without notice Copyright 2016 Actron Engineering Pty Ltd Hercules Units w CM100 Addressing the Fans Using EC Control Software 9590 7005 Rev 5 0 220201 Page 19 of 24 4 26 Click on Communication Parameters 4 27 Click on the number of the Device Address ...

Page 20: ...s are subject to change without notice Copyright 2016 Actron Engineering Pty Ltd Hercules Units w CM100 Addressing the Fans Using EC Control Software 9590 7005 Rev 5 0 220201 Page 20 of 24 4 28 Change the address to 2 Refer to Fans addressing chart see page 22 and then click on Set to lock the fan address The following screen will be displayed ...

Page 21: ...ing the Fans Using EC Control Software 9590 7005 Rev 5 0 220201 Page 21 of 24 4 29 Close the window 4 30 Switch ON the next Fan 4 31 Follow procedures 4 10 to 4 29 4 32 When searched for the next fan is completed the next screen will be displayed Note that every new fan will have an initial address as 1 4 33 When the first two fans are configured the following screen will be displayed 4 34 Follow ...

Page 22: ...g the Fans Using EC Control Software 9590 7005 Rev 5 0 220201 Page 22 of 24 Fan Number 1 2 3 4 Address 10 11 12 13 Fan Number 1 2 3 4 Address 2 3 4 5 5 0 INDOOR FANS ADDRESSES 6 0 OUTDOOR FANS ADDRESSES Outdoor Fans Number and Address Top View Fan 2 MODBUS1_11 Fan 3 MODBUS1_12 Fan 1 MODBUS1_10 Fan 4 MODBUS1_13 Compressor Section End Indoor Fans Number and Address Front View Fan 2 MODBUS1_3 Fan 1 M...

Page 23: ...THIS PAGE IS INTENTIONALLY LEFT BLANK ...

Page 24: ...onair com au Refrigerant Trading Authorisation No AU06394 Actron Engineering Pty Ltd ABN 34 002 767 240 HEAD OFFICE SYDNEY AUSTRALIA Copyright 2016 Actron Engineering Pty Ltd Printed in Australia 9590 7005 Rev No 5 0 220201 ...

Reviews: