
Rev A
(
ACT-VCC-2000-AC)
10
Figure 5.2 Dimensions for cut-out in enclosure door
Installation steps:
1. Mark the cabinet with the cut-out dimensions as in Figure 5.2
2. Cut out the shaded area
3. Remove the product from the shipping crate with care
4. Install the Air Conditioner on the cabinet as shown in Figure 5.1
5. The mechanical portion of the installation is now finished. Adhere
to the “Install Checklist.”
Install Checklist
The ambient air must be under 55
℃
, and the humidity under 95%.
Make sure that the product is installed within 3° of plumb level,
relative to the vertical direction
Make sure that the cabinet is well-sealed (using the supplied
gasket)
Do not turn the unit on immediately after finishing the
installation; the unit must remain standing vertically for more
than 30 minutes before being turned on to allow the compressor
oil to drain back to the compressor.
Complete wiring 5.2 and pre-operational 6.1 checks before
turning -on the unit.
5.2 Electrical Connection
**Electrical wiring should be performed, only by skilled technicians, before powering
on the product**
The power supply must be in accordance with the technical specifications of the unit. Power supply cable sizes and
circuit breaker sizes are recommended below:
Current documentation, cut out templates, DXF and Step files can also be found on our website
at
https://www.1-act.com/enclosure-cooling/resources/enclosure-cooling-dxf-and-step-files/
17.71”/450mm
29
.52
”/
75
0
mm
30
.23
”/
76
8mm
96
mm
114
mm
10
6
mm
10
6
mm
114
mm
96
mm