PHYSICAL DATA
Table A-1 : R410A - Heat Pump
Model
5ACV100CR
5ACV135CR
5ACV210CR
Nominal cooling capacity
kW
27.84
38.54
58.56
Nominal heating capacity
kW
29.31
41.47
61.49
Operating weight
kg
405.0
525.0
682.0
Refrigerant charge R410A
kg
4.7
×
2
6.0
×
2
9.5
/
8.5
Compressor
1 Scroll + 1 Inverter Compressor
2 Scoll + 1 Inverter Compressor
Control system
LCD Electronic Control
Refrigerant - water heat exchanger
Brazed Plate Heat Exchanger
Water connections (BSP)
inches
1 1/4
1 1/2
Maximum water pressure
kPa
1000
1000
Hydronic circuit
Pump
Horizontal Multistage End-Suction
Available pressure (Cooling/Heating)
kPa
127.7 / 157.3
167.4 / 157.6
258.5 / 244.0
Water inlet connection (BSPT)
inches
1 1/4
1 1/4
1 1/2
Water outlet connection (BSPT)
inches
1 1/4
1 1/4
1 1/2
Drain tap coupling (BSPT)
inches
1/2
1/2
1/2
Closed expansion tank water volume
litre
8
8
8
Refrigerant - air heat exchanger
Tube diameter
mm
9.52
9.52
9.52
No. of rows
2
2
2
Tubes/row
42
42
62
Fin spacing
mm
1.59
1.59
0.6299
Fan
Diameter/Number of O/D fan
mm
24 x 2
26 x 2
32 x 2
No. of blades
4
4
6
Air flow (high speed)
m
3
/hr
6480
14400
11890
Fan speed (high speed)
r/min
690
780
550
WATER PIPING AND FITTING
•
All water pipe must be insulated to prevent capacity losses and condensation.
•
Install a 40-60 mesh strainer to ensure water quality is good.
•
Water pipe recommended are black steel pipe and copper pipe.
•
During installation, the piping of the unit should be clamp before rotating the installation pipe to reduce the moment induce
on the unit piping.
•
Users are recommended to install the pipe and accessories as shown in Figure 2.
•
An air vent must be installed at the highest position, while a drainage plug at the lowest position of the water circuit. Open
the air vent to release any air trap in the water circuit.
•
Run the clean water through the water inlet and operate the pump to drain out the dirty water. Clean the strainer after
running the pump for 30 minutes.
•
Fill up the water circuit after connecting all the pipes and equipment. Check water leakages at all connections and joints.
Do not start the unit when the system is leaking. To optimize the capacity of the system, ensure that the system is free of air
bubbles. The air trapped in the system would make the system unbalanced.
Note: For cooling nominal values are based on 12°C / 7°C entering / leaving evaporator water temperature, 35°C air ambient
temperature.
Note: For heating nominal values are based on 40°C / 45°C entering / leaving evaporator water temperature, 7°C DB / 6°C
WB air ambient temperature.