CAUTION
ELECTRICAL AND WIRING
•
Refer to the wiring diagram provided on the unit when making electrical wiring.
•
Do not ground any electrical equipment to the water piping.
•
Install an external isolator switch (if it is not provided) to prevent electrical shock.
RECOMMENDED FUSE AND CABLE SIZES
IMPORTANT :
* The figures shown in the table are for information purpose only. They should be checked and
selected to comply with the local/national codes of regulations. This is also subjected to the type of
installation and conductors used.
** The appropriate voltage range should be checked with label data on the unit.
46
!
A5ACV 100 / 135 / 210CR
!
•
All field wiring must be installed in accordance with the national wiring regulation.
•
All the terminals and connections must be tightened. Improper connection and fastenings could
cause electric shock, short circuit and fire.
•
Ensure that the rated voltage of the unit corresponds to that of the name plate before
commencing wiring work according to the wiring diagram.
•
The unit mus be GROUNDED to prevent possible hazards due to insulation failure.
•
All electrical wiring must not touch the refrigerant piping, compressor, pump, fan motor or any
moving parts of the fan motors.
•
Do not operate the chiller with wet hands. It would result in electric shock.
•
Do not use fuse of different amperage than stated. Using wire etc. to replace a fuse could cause
equipment damage or fire.
CAUTION
•
Do not allow water to remain in the water pipes if the unit is not operating for a long period.
Water must be drained out if the unit is not running during winter. Failing to do so would cause the pipe
to crack.
•
Do not drink the chilled water in the unit.
PRESSURE GAUGE
GATE
VALVE
GATE
VALVE
BALANCING
VALVE
THERMOMETER
FLEXIBLE
GATE VALVE
(LOWER POSITION
FOR DRAINAGE)
AIRVENT (INSTALL
HIGHEST POSITION)
FAN COIL UNIT/AIR HANDLING UNIT
GATE
VALVE
Figure 2
THERMOMETER
GATE
VALVE
GATE
VALVE
BALANCING
VALVE
STRAINER
CHECK
VALVE
MAKE UP
VALVE
PRESSURE
DIFFERENTIAL
VALVE
FLEXIBLE
Model
A5ACV30CR
A5ACV55CR
A5ACV75CR
230/1/50
415/3/50
415/3/50
Recommended Fuse*
A
36
25
36
Power Supply Cable Size*
mm
2
10
10
10
Number of Conductor
3
5
5
Interconnection Cable Size*
mm
2
1.5
1.5
1.5
Model
A5ACV100CR
A5ACV135CR
A5ACV210CR
415/3/50
415/3/50
415/3/50
Recommended Fuse*
A
40
60
100
Power Supply Cable Size*
mm
2
10
10
10
Number of Conductor
5
5
5
Interconnection Cable Size*
mm
2
1.5
1.5
1.5
Voltage Range**
Voltage Range**
Summary of Contents for A5ACV 100 CR
Page 43: ...INSTALLATION A5ACV 30 55 75CR 41 ...
Page 44: ...A5ACV 30CR A5ACV 55CR 75CR 42 ...
Page 78: ...10 WIRING DIAGRAMS PA R T NO 50 13 9 026086 MODEL A5ACV 30CR 76 ...
Page 79: ...77 MODEL A5ACV 55CR ...
Page 80: ...MODEL A5ACV 75CR PA R T NO 50 13 4 083602 78 ...
Page 81: ...MODEL A5ACV 100 135CR 79 ...