1-5
English
Fig B
10.0mm (0.39")
10.0mm (0.39") Lower
Please ensure that the following steps are taken:
•
Check the gradient for drainage flow as recommended in Figure B.
•
Provide clearance for easy servicing and optimal air flow as shown in Figure C.
•
The indoor unit must be installed such that there is no short circuit of the cool discharge air with the warm return air.
•
Do not install the indoor unit where there is direct sunlight shining on the unit. The location should be suitable for piping
and drainage installation. The unit must be a large distance away from the door.
Fig C
Ceiling Type
Floor Standing Type
Min. 10.0mm (0.39")
Max. 250mm (9.84")
Min. 500mm (19.60")
Utensils, Furnitures Or Built-
In Architectural Features
Must Not Protrude More
Than 250.0mm
Min. 1.0m (39.37")
Min. 400.0mm (15.75")
Min. 300.0mm (11.81")
1 IM-CEE-1108(0)-EN AS
5/26/09, 3:14 PM
5