Acson 5ACV210CR Installation Manual Download Page 11

1-4

English

!

!

!

!

!

 

CAUTION

All field wiring must be installed in accordance with the national wiring regulation.

All the terminals and connections must be tightened. Improper connection and fastenings could cause electric shock,
short circuit and fire.

Ensure that the rated voltage of the unit corresponds to that of the name plate before commencing wiring work
according to the wiring diagram.

The unit must be GROUNDED to prevent possible hazards due to insulation failure.

All electrical wiring must not touch the refrigerant piping, compressor, pump, fan motor or any moving parts of
the fan motors.

Do not operate the chiller with wet hands. It would result in electric shock.

Do not use fuse of different amperage than stated. Using wire etc. to replace a fuse could cause equipment damage
or fire.

Electrical Wiring Diagram (please refer to Appendix 3).

REFRIGERANT CIRCUIT

All mini chillers units are pre-charged with R410A refrigerant.

SPECIAL PRECAUTIONS WHEN DEALING WITH R410A UNIT

R410A is a near azeotrope refrigerant blend of hydro fluorocarbon (HFC) which is environmental friendly.  It has Zero
Ozone Depletion Potential (ODP=0) and this conforms to Montreal Protocol regulations. It has no flame propagation and
a low toxic refrigerant (rated as A1 by ARI). R410A is a mixture of R32 (50%) and R125 (50%).

POE oil is used as lubricant for R410A compressor, which is different from the mineral oil used for R22 compressor.
During installation or servicing, extra precaution must be taken not to expose the R410A system too long to moist air.
Residual POE oil in the piping and components can absorb moisture from the air.

Refrigerant R410A is more easily affected by dust of moisture compared with R22, make sure to temporarily cover the
ends of the tubing prior to installation.

No additional charge of compressor oil only is permitted.

No refrigerant other than R410A is permitted.

Tools designed specifically for R410A only.
i) Manifold gauge and charging hose
ii) Gas leak detector
iii) Refrigerant cylinder/charging cylinder
iv) Vacuum pump c/w adaptor
v) Flare tools
vi) Refrigerant recovery machine

!

!

!

!

!

 

CAUTION

R410A must be charged as liquid. Usually R410A cylinder is equipped with a dip-pipe for liquid withdrawal.
If there is no dip-pipe, the cylinder should be inverted so as to withdraw liquid R410A from the valve.

Do not top-up when servicing leak, as this will reduce the unit performance. Vacuum the unit thoroughly and then
charge the unit with fresh R410A according to the amount recommended in the specification.

Do not touch the compressor or refrigerant piping when the chiller is running. If necessary wear protective gloves.

Summary of Contents for 5ACV210CR

Page 1: ...AIR COOLED CHILLER R410A INVERTER MODEL Model IM 5ACV210CR 0706 ACSON MINI CHILLER INSTALLATION MANUAL...

Page 2: ......

Page 3: ...its Vorsicht Scharfe Kanten und W rmetauscherfl chen stellen eine Gefahrenquelle dar Jeglicher Kontakt mit diesen Stellen ist zu vermeiden Cautela Per preservarsi da eventuali ferite evitare di toccar...

Page 4: ...ii 5ACV 210CR UNIT INSTALLATION 500 0 500 0 700 0 700 0...

Page 5: ...des objets sur le dessus du mini refroidisseur CAUTION Improper handling of unit during installation could result in leaks electrical shock or unit malfunction Contact your dealer for reinstallation o...

Page 6: ...M FSC1 FSC2 TB3 FAN 2 1 FAN 2 2 N FAN 1 2 FAN 1 1 4WV1 N 4WV2 BP_H N CC_H3 CC_H2 N CC_H1 BOIL N AU_H AU_H 4WV2 4WV1 BP_H FM1 FM2 CF2 18uF CF1 18uF COMP LCD DISPLAY PANEL EV1 EV2 BR 3P T S R PFC 1 2 1...

Page 7: ...er please read this instruction manual carefully and keep it for future reference INSTALLATION MANUAL AIR COOLED INVERTER CHILLER MODEL Part No A08019028696 IM 5ACV210CR 0706 0 Acson WARNING Installat...

Page 8: ...ata page 3 TRANSPORTATION The unit should be lifted using a crane Ensure that the hanger belts are not touching panel and the coil top front panel use protective panel as shown in Figure 1 The bolt of...

Page 9: ...ure water quality is good Water pipe recommended are black steel pipe and copper pipe During installation the piping of the unit should be clamp before rotating the installation pipe to reduce the mom...

Page 10: ...94 Readings taken at rated compressor frequency The Power Input and Current differ depending on the combination of outdoor temperature and entering water temperature For further details please refer t...

Page 11: ...a low toxic refrigerant rated as A1 by ARI R410A is a mixture of R32 50 and R125 50 POE oil is used as lubricant for R410A compressor which is different from the mineral oil used for R22 compressor D...

Page 12: ...LIQUID RECEIVER EXV FILTER DRIER 5ACV 210CR Refrigerant Circuit Diagram CHECK VALVE EXV CHECK VALVE COMPRESSOR 4 WAY VALVE OIL SEPARATOR OIL SEPARATOR OIL RETURN TUBE TWIN TUBE JOINT FILTER DRIER WAT...

Page 13: ...sor controller board The microprocessor controller is provided to give temperature control for the system by accurately measuring and controlling the water entering and water leaving temperature The t...

Page 14: ...et or outlet of the unit Insufficient refrigerant in the system Improper water flow rate Water in the system is contaminated No water in the system Low water level in the system Check power supply Loo...

Page 15: ......

Page 16: ...reils pr sent s dans ce manuel Im Falle einer widerspr chlichenAuslegung der vorliegendenAnleitung bzw einer ihrer bersetzungen gilt dieAusf hrung in Englisch nderungen von Design und technischen Merk...

Reviews: