ACS TVA-080 Technical Manual Download Page 6

 

 

TVA – 080 / 100 / 120 / 180 / 200 / 220 

 

page 6 of 8 

 

 

  

Electrical connection

 

 

Connection of the output 

 

For the two-wire connection cable between the isolation amplifier and the connected devices  a standard 

installation cable or multi-wire cable for measuring intends with a maximum of 25 

 per wire can be used. 

 

The use of a shielded signal cable is recommended, if strong electromagnetic influences could happens, e.g. 

due to machines or radio equipment. In that case the shielding of the cable should be connected to earth only at 

the side of the connected device. When connecting a SPS input stage there must be paid attention that mostly 

the signal circuit must be connected to earth by connection the minus terminal with measuring earth. 

The signal cable should be installed separated from power leading wires. 

 

For inauguration it is suggested, to deactivate all connected control devices, to avoid unwanted control reactions. 

 

Connection of the power supply voltage 

 

Due to the integrated wide range power supply, for connection to supply voltages from 20...253V AC / DC, the 

isolation amplifier is suitable for using in all common energy supply networks. 

The connection is reverse polarity protected. 

 

A fuse is integrated internally at the power supply circuit. Due to this the installation of a fine protection is not 

necessary. 

 

 

 

Terminal occupation 

 

 

 

 

 

 

 

 

 

 

 

 

Connection scheme 

 

Summary of Contents for TVA-080

Page 1: ...ls Direct voltage 0 10V 2 10V simultaneous outputs Direct current 0 20mA 4 20mA simultaneous outputs Signal adjustment of zero value and amplification optional Single or double channel version optional Integrated measurand transducer supply optional Space saving safe isolation with 4kV Wide range power supply from 20 to 253V AC and DC L a u t e r b a c h s t r 5 7 8 4 3 0 7 E g g e n f e l d e n G...

Page 2: ...Output code no B 0 10V 1 0 10V 1 0 20mA 2 0 20mA 2 4 20mA 3 4 20mA 3 90 520Hz PFM P special range Y special range Y TVA 200 U0 Version double channel device adjustable with measurand transducer supply TVA 220 ABCD U0 Version double channel device fix adjusted with measurand transducer supply Input 1 order no A Input 2 order no B Output 1 order no C Output 2 order no D 0 10V 1 0 10V 1 0 10V 1 0 10V...

Page 3: ...rrent through the isolation Function Measuring principle Version TVA 080 U0 TVA 100 U0 TVA 200 U0 adjustable version The connected electrical standard signal 0 10V 0 1V 5 5V 0 5 0 5V 0 20mA 4 20mA 10 10mA is measured by the evaluation circuit adjusted according to the front sided trimmer and transmitted galvanically isolated to the simultaneous output signals 0 10V and 0 20mA or 2 10V and 4 20mA a...

Page 4: ...evice meets the legal requirements of all relevant EC directives Installation The device is conceived for vertical installation on a standard fastening rail acc to DIN EN 60715 TH 35 7 5 resp TH 35 15 DIN EN 60715 TH 35 7 5 DIN EN 60715 TH 35 15 The device must be installed protected against dust and humidity e g in control stations or in a suitable protection housing with a minimum protection cla...

Page 5: ... for measuring intends with a maximum of 25 per wire can be used The use of a shielded signal cable is recommended if strong electromagnetic influences could happens e g due to machines or radio equipment In that case the shielding of the cable should be connected to earth only at the side of signaling transmitter resp measuring transducer The signal cable should be installed separated from power ...

Page 6: ...nput stage there must be paid attention that mostly the signal circuit must be connected to earth by connection the minus terminal with measuring earth The signal cable should be installed separated from power leading wires For inauguration it is suggested to deactivate all connected control devices to avoid unwanted control reactions Connection of the power supply voltage Due to the integrated wi...

Page 7: ...ange channel 1 switcher block SB1 Switch 1 2 3 SB1 measuring range switching state S1 switching state S2 switching state S3 measuring range CH 1 OFF ON ON 0 5 0 5V 10 10mA ON OFF OFF 4 20mA OFF OFF ON 0 1V 0 20mA OFF ON OFF 5 5V 10 10mA OFF OFF OFF 0 10V 0 20mA Input signal range channel 2 switcher block SB3 Switch 1 2 3 SB3 measuring range switching state S1 switching state S2 switching state S3 ...

Page 8: ...put Iout with 20mA TVA 200 220 RL 3333 at 10V RL 6666 at 10V at simultaneous output Iout with 20mA Direct current 0 20mA 4 20mA max 28mA Permitted load direct current TVA 080 100 120 180 RL 880 at 20mA RL 680 at 20mA at simultaneous output Uout with 5mA TVA 200 220 RL 570 at 20mA RL 530 at 20mA at simultaneous output Uout with 1 5mA Adjustment range zero value 25 5 of respective nominal measuring ...

Reviews: