Precont S
page 14 of 28
Adjustment menu – password 3009
NAMUR
run mode
Indication of current measurement value
Entry to code-inquiry
Input password
3009
Passwort right
codE
0000
NESS EEEE
OK
OK
OK
OK
OK
OK
2Ero
Adjustment
lower pressure
reference
signal
NSig 4.00
OK
Password wrong
OK
oSig 0.000
OK
3 seconds
OK
OK
SPAn
Adjustment
upper pressure
reference
signal
NSig 20..00
OK
OK
oSig 1.000
OK
Adjustment of lower pressure reference value with applied signal
Current pressure signal is assigned as the lower pressure signal to the displayed and
by „+“ resp. „-“ adjustable output signal (output mA resp. V).
Set with „OK“, cancel by pressing „Change“
for 3 seconds. At the signal 0...10V the value of
4.00 equals a voltage of 0V and a value of 20.00 equals a voltage of 10V.
Adjustment lower pressure reference value without applied signal
adjust lower pressure reference signal,
referring to the nominal sensor pressure
, with „+“ resp. „-“ to the
value that should be assigned to the output signal of 4,00 mA or resp. 0V. Set with „OK“, cancel by pressing
„Change“
for 3 seconds.
3 seconds
3 seconds
3 seconds
Adjustment of upper pressure reference value with applied signal
Current pressure signal is assigned as the upper pressure signal to the displayed and
by „+“ resp. „-“ adjustable output signal (output mA resp. V).
Set with „OK“, cancel by pressing „Change“
for 3 seconds. At the signal 0...10V the value of
4.00 equals a voltage of 0V and a value of 20.00 equals a voltage of 10V.
Adjustment upper pressure reference value without applied signal
adjust upper pressure reference signal,
referring to the nominal sensor pressure
, with „+“ resp. „-“ to the
value that should be assigned to the output signal of 20,00 mA or resp. 10V. Set with „OK“, cancel by pressing
„Change“
for 3 seconds.
OK
OK
diSP
Display
dP-_ dP3
OK
Decimal positions
setting
dP0
display
8888.
/ setting
dP1
display
888.8
setting
dP2
display
88.88
/ setting
dP3
display
8.888
Display zero value scaling
Indication value at 4 mA / 0 V output signal. If the displayed value falls below
-999
,
-EEE
is displayed.
OK
2Ero 0.000
OK
OK
SPAn 1.000
OK
Display end value scaling
Indication value at 20 mA / 10 V output signal. If the displayed value rises above
9999
,
EEEE
is displayed.
OK
t_F
System
damping
1
OK
OK
OK
SP 1
Switch point 1
SP_1 0.250
OK
Limit value switch point 1
Display value, where the PNP switching output S1 will be activated.
Hysteresis switch point 1
Switch point hysteresis of switch point S1 referring to the display value
OK
HYS1 0.005
OK
OK
n.o.n.c.
n.o.
OK
Operation mode switch point 1
n.o.
= normally open
= open circuit principle
S1 switches on at exceeding of the limit value
n.c.
= normally closed = closed circuit principle
S1 switches on at underrun of the limit value
n.c.
OK
OK
Func
norF
OK
ErrF
OK
Function switch point 1
norF
= limit value function with hysteresis
ErrF
= error indication function
S1 switches, if the output signal become higher than 20mA/10V resp.
lower than 4mA/0V.
SP 2
Switch point 2
Switch point 2
This menu is identical to the menu switch point 1 with the exception that the submenu
Func
is not available.
OK
SAbG
Fast
adjustment
on
OK
Fast adjustment per key combinations
Unlock or lock of fast adjustment for the lower and upper pressure reference value with applied signal as well as
setting the damping per key combinations.
oFF
OK
OK
ErrS
Behaviour
output signal
FS3.8
OK
FS22
OK
oFF
OK
OK
FrES
Reset to
factory values
Factory-Reset
Reset of all parameters to factory values. Customer specific settings will be lost.
OK
SPEi
Store
Store
Loss protected storage of all parameters (duration approx. 7 s)
25.12
run mode
OK
-
+
Enter the respective submenu and
capturing the set values
Jump from menu to menu / changing the direction of the
„+/-„ key / changing between the different possibilities in
selection menu
Change the indicated values. The longer the key will be
pressed, the faster the value will increase or decrease.
Function direction (higher or lower) can be changed by
the key „Change“. Pressing this key in the run mode will
display the software version
OK
OK
Behaviour of the output signal at signal range exceeding
FS3.8
= The output signal operates linear in the range from 4,0...20,0 mA resp. 0...10 V.
At exceeding of this range a constant signal of 3,8 mA / 0 V is generated.
FS22
= The output signal operates linear in the range from 4,0...20,0 mA resp. 0...10 V.
At exceeding of this range a constant signal of 22 mA / 11,25 V is generated.
oFF
= The output signal operates linear in the range from 3,9...21,0 mA resp. 0...10,5 V.
A signal besides these limits is not possible. The end values are kept at exceeding.
A error current output at exceeding or underrun is not generated.
25.12
System damping
Setting the system damping for neutralization of short pressure blows or also for calming down cyclic fluctuating
pressure signals.
The adjustment range is 0...60 seconds, in 100 steps of each 0,6 seconds.
Summary of Contents for Precont S
Page 19: ...Precont S page 19 of 28 Dimension drawings Precont S10 NAMUR...
Page 21: ...Precont S page 21 of 28 Dimension drawings Precont S20 NAMUR...
Page 23: ...Precont S page 23 of 28 Dimension drawings Precont S30 NAMUR...
Page 25: ...Precont S page 25 of 28 Dimension drawings Precont S40 NAMUR...
Page 27: ...Precont S page 27 of 28 Dimension drawings Precont S70 NAMUR...