Marvair Wall Mount Heat Pump I&O Manual
06/2023 Rev.7
Electric Reheat Lock-Out
While the system is still operating in “Dehumidification Mode”. Activate Mechanical Cooling.
Do Not change the Humidity Setpoint on the Humidistat. Simply adjust the cooling setpoint to
approximately four degrees below the current indoor temperature. After the short delay, the unit will
sequence on, start cooling. Notice: system did not turn off. The Only change that occurred is “Heater
turned off”.
Is the indoor blower motor (IBM) On? .............................................................................
❒
Yes
❒
No
Is the Compressor On? ......................................................................................................
❒
Yes
❒
No
Is the Condenser Fan (CFM) On? .....................................................................................
❒
Yes
❒
No
Is the Heater Off? (Clamp an AmpProbe on one leg of the heater contactor to verify) ...
❒
Yes
❒
No
Electric Reheat Re-Start
While the system is still operating in “Cooling Mode” from the previous test. Re-Start
Dehumidification.
Do Not change the Humidity Setpoint on the Humidistat. Simply adjust the cooling setpoint to
approximately four degrees above the current indoor temperature. After the short delay, the unit will
sequence on, start dehumidification. Notice: system did not turn off. The Only change
that occurred
is “Heater turned on”.
Is the indoor blower motor (IBM) On? .............................................................................
❒
Yes
❒
No
Is the Compressor On? ......................................................................................................
❒
Yes
❒
No
Is the Condenser Fan (CFM) On? .....................................................................................
❒
Yes
❒
No
Is the Heater On? (Clamp an AmpProbe on one leg of the heater contactor to verify) ....
❒
Yes
❒
No
Electric Reheat Stop
Adjust the Humidity setpoint to approximately five percent above the current indoor Humidity
(Humidistat display should indicate current RH%). After the short delay, the unit will sequence off.
Did the Compressor Stop? ................................................................................................
❒
Yes
❒
No
Did the Condenser Fan (CFM) Stop? ...............................................................................
❒
Yes
❒
No
Did the indoor blower motor (IBM) Stop? .......................................................................
❒
Yes
❒
No
Is the Heater Off? (Clamp an AmpProbe on one leg of the heater contactor to verify) ...
❒
Yes
❒
No
H.
Cooling Mode (Economizer Cooling)
NOTE: If the HVAC system you are testing is Not configured with Economizer Cooling Option, Skip
this section of the Start-up / Commissioning Checklist.
Has the Economizer Control Board been properly wired to the Control? ........................
❒
Yes
❒
No
Has the Economizer Control Board Ambient selections been properly setup? ................
❒
Yes
❒
No
Has the Economizer Control Board Minimum Opening selection been properly setup? .
❒
Yes
❒
No
Are ambient conditions suitable for Economizer Cooling? (If not, skip this section) ......
❒
Yes
❒
No
Economizer Cooling Start
If using a standard thermostat, Set the Control to ON, Mode to Cooling, Fan to Auto (other controls,
set appropriately for cooling mode).
Adjust the cooling setpoint to approximately two degrees below the current indoor temperature. After
the initial start-up delay (.3 to 5 minutes), the unit will sequence on, start cooling. The damper will
modulate to maintain 55ºF mixed air temperature, thru the supply.
Is the indoor blower motor (IBM) On? .............................................................................
❒
Yes
❒
No
Is the Compressor Off? (Compressor Should be Off!) .....................................................
❒
Yes
❒
No
Is the Condenser Fan (CFM) Off? (CFM Should be Off!) ...............................................
❒
Yes
❒
No
Is the Economizer Damper Open?
(Damper Should be modulating, to control supply air temp.) ..........................................
❒
Yes
❒
No