GWA – 250

page 7 of 8

Operation and display elements

 

 

 
 
 
 
 
 
 

 

 
 

Function indicator 

 

 

ON  

 green LED  

 

 

 ready status, power supply voltage on 

 

A  

 

 red LED    

 

 

 output relay A switched on 

 

B  

 

 red LED    

 

 

 output relay B switched on 

 

Key coding switch 

 

For setting the limit value from  0...99% of the configured signal range in steps of 1%. 

 

At two-position-control 

s the limit value A represents the switching value and the limit value B the switching back value. 

 

Configuration switches 

 

The configuration of the input signal range as well as the relay functions is made per dip switches inside the housing.  

 

 Dangerous 

voltage 

 

Ensure a safe switching off the supply voltage when opening the housing 

 

For configuration release the upper housing part at top and bottom side behind the terminals by using a screwdriver and pull 
it out of the housing. Drop-in pin's avoid a complete pulling out. Following the respective dip switches can be set according to 
the desired functions to ON or OFF. 

 

Relay functions  switcher block SB1 

 

Switch 1, 2, 5, 6 (SB1) 

 Safety function 

 

switching state S1 

switching state S2 

safety function 

ON 

OFF 

channel B – minimum safety 

OFF 

ON 

channel B – maximum safety 

 

 

 

switching state S5 

switching state S6 

safety function 

ON 

OFF 

channel A – minimum safety 

OFF 

ON 

channel A – maximum safety 

 

Switch 3, 7 (SB1)  

 

 switching delay 

 

switch switching 

state 

ON 

switching state OFF 

channel B – 4 seconds 

channel B – 0,4 seconds 

channel A – 4 seconds 

channel A – 0,4 seconds 

 

Switch 4 (SB1)   

 

 operation function 

 

switch switching 

state 

ON 

switching state OFF 

two-position-control 

double limit value switch function 

 

Input signal range GWA – 250  

switcher block SB2 

 

Switch 1 (SB2)   

 

 measuring range – only at GWA – 250 

 

switch switching 

state 

ON 

switching state OFF 

input signal 4...20mA 

input signal 0...10V / 0...20mA 

 

Input signal range GWAP – 250   

switcher block SB2 / SB3

 

 

Switch 2, 3 (SB2)  

 

 measuring range signal zero value – only at GWAP – 250 

 

switching state S2 

switching state S3 

signal zero value 

ON 

ON 

zero value – 50°C 

OFF 

ON 

zero value      0°C 

OFF 

OFF 

zero value + 50°C 

 

Switch 1, 2, 3 (SB3) 

 measuring range signal range – only at GWAP – 250 

 

 

switching state S1 

switching state S2

 

switching state S3

 

signal range

 

ON ON ON 30 

Kelvin 

ON OFF ON  50 

Kelvin 

OFF OFF  ON  100 

Kelvin 

OFF OFF OFF 600 

Kelvin 

Limit value channel B

2-digit  
key coding switch 

Function indicator 

3 LED’s for indication 
of operating states 

Limit value channel A

2-digit  
key coding switch 

Configuration switch

inside the housing 

 
 
 
 
 
 
 
 
 
 
 
 
 

 
 
 
 
 
 
 
 

     

Summary of Contents for GWA-250

Page 1: ...n two separated limit values Two position control function a limit value with hysteresis Configurable switching delay Simple operation per key coding switch for adjusting the limit values from 0 99 of the signal range in steps of 1 Integrated measurand transducer supply Version with remote control available Wide range power supply from 20 to 253V AC and DC L a u t e r b a c h s t r 5 7 8 4 3 0 7 E...

Page 2: ... display elements 7 Technical data 8 Order code GWA 250 U0 Version input signals 0 10V 0 20mA resp 4 20mA with on site control GWAS 250 U0 Version input signals 0 10V 0 20mA resp 4 20mA with remote control GWAP 250 U0 Version input signal Pt100 from 50 C 650 C with on site control GWAPS 250 U0 Version input signal Pt100 from 50 C 650 C with remote control ...

Page 3: ...a signal current of 10mA At standard signal 4 20mA the setting 50 equals a signal current of 8mA 50 of 16mA 4mA 12mA The connected signal device at the input can be powered by the integrated measurand transducer supply Version GWAP 250 GWAPS 250 The voltage drop at the connected temperature sensor Pt100 is compared by the evaluation circuit with the set limit value at the key coding switches in of...

Page 4: ...both output relays A and B the safety function can be set separately This can be carried out by two switches one per relay inside the device Two position control s The activation of the two position control is made by a switch inside the device Two position control with minimum safety Two position control with maximum safety The set limit value A equals the switching value and the limit value B eq...

Page 5: ...installation on a standard fastening rail acc to DIN EN 60715 TH 35 7 5 resp TH35 15 DIN EN 60715 TH 35 7 5 DIN EN 60715 TH35 15 The device must be installed protected against dust and humidity e g in control stations or in a suitable protection housing with a minimum protection classification IP55 acc to DIN EN 60529 The devices must be installed wheather and stroke protected ideally at places wi...

Page 6: ...f the inputs at the limit value switch GWA 250 current input maximum 400mA 30V voltage input 50V must not be transgressed The current input is equipped with a self resetting fuse At activation of the fuse the signal current wire must be disconnected for app 5 seconds If more than two limit values to a standard signal V mA should be evaluated at the limit value switch GWA 250 additional devices cou...

Page 7: ...OFF ON channel B maximum safety switching state S5 switching state S6 safety function ON OFF channel A minimum safety OFF ON channel A maximum safety Switch 3 7 SB1 switching delay switch switching state ON switching state OFF 3 channel B 4 seconds channel B 0 4 seconds 7 channel A 4 seconds channel A 0 4 seconds Switch 4 SB1 operation function switch switching state ON switching state OFF 4 two p...

Page 8: ...ng range Measurand transmitter supply overload and short circuit protected 3 wire sensor 21 2V at 20mA 20 7V at 27 5mA min 27 5mA max 25V 2 wire sensor 20 0V at 20mA 19 0V at 27 5mA min 27 5mA max 25V Signal input GWAP 250 Temperature resistor Pt100 3 wire 2 wire measuring resistance linear measuring current 2 x 0 515mA 10µA Measuring range Zero value 50 C 0 C 50 C range 30 Kelvin 50 Kelvin 100 Ke...

Reviews: