Technical Data
7.1
Auxiliary power supply
Supply voltage U
S
10,5…35V
DC
, reverse polarity protected
Residual ripple U
PP
≤ 2V
PP
/ U
Smin
≤ U
S
≤ U
Smax
Supply current I
In
≤ 60mA
Current output max. 22,5mA
Switch output with no load
7.2
Output
7.2.1
Analogue output – current 4…20mA
Operating range I
Out
3,9…21mA, min. 3,8mA, max. 22mA
Permitted load R
L
≤ (U
S
- 10,5V) / 20mA
Step response time T
90
≤ 3ms (t
d
= 0s)
Start-up time t
On
≤ 1s
7.2.2
Switch output S1 / S2
Function
PNP switch to +L
Output voltage U
Out
U
Out
≥ U
S
– 2V
Output current I
L
0… ≤ 200mA, current limited, short circuit protected
Step response time T
90
≤ 4ms (t
d
= 0s)
Rise time T
90
< 30µs (R
L
< 3kR / I
Out
> 4,5mA)
Start-up time t
On
≤ 1s
Switch cycles
≥ 100.000.000
7.3
Measuring accuracy
Reference conditions
EN/IEC 60770-1, EN/IEC 61003-1
Environmental temperature
25°C
Environmental air pressure
860..1060kPa
Air humidity
45...75% r.h.
Warm-up time t
On
240s
Supply voltage U
S
24V
DC
±0,1V
Calibration position
Vertical
Process connection bottom