![Acrel ASL100 Series Instructions Manual Download Page 4](http://html1.mh-extra.com/html/acrel/asl100-series/asl100-series_instructions-manual_2841054004.webp)
ASL100 Series of Power Module
- 2 -
1.
Overview
ASL100-P640/30 bus power module (hereinafter referred to as power supply) is a bus power supply based on
Acrel-bus intelligent control system. All control modules on the bus are coupled with the power supply by the
choker in the power supply. This product meets the enterprise standard Q31/0114000129C032-2017
ASL100
Intelligent Lighting Control System
. The bus is connected by the standard EIB wiring terminal and standard KNX
bus. After the reset key on the module is pressed, the power supply will be reset for 20s (the bus power supply is
disconnected and the auxiliary power supply normally provides the power supply during reset period) and the bus
and power supply are disconnected physically. If the power supply needs to be cut off for more than 20s during use,
the power line needs to be cut off. This model of module is also attached with a 30V DC auxiliary output power
supply. This auxiliary power supply may power on the external power module, such as IP module and touch screen
and so on.
2.
Specification and model
3.
Technical parameters
Power input
Input voltage
85—265V AC
50/60Hz
Power consumption
<5W
Efficiency
≥75%
Power output
Bus power supply
30V DC
Built-in choking coil output
Auxiliary power supply
30V DC
No choking coil output
Output current
Bus auxiliary current≤640mA
External connection
KNX-TP1
Use twisted-pair cable conforming to KNX standard
Wiring terminal at load
end
Terminating with 0.5nm
~
0.6nm torque
Operation and display
interface
Programming key and
relevant indicator
LED indicator is in red when waiting for programming and
is in green during and after programming.
Acrel
智能照明系列产品标志
Acrel intelligent lighting product mark
电源模块标志
Power module mark
输出电流:
640mA
Output current: 640mA
输出电压:
30V
Output voltage: 30V
Summary of Contents for ASL100 Series