of the system. Generally not less than 2~4 times of the maximum measured residual current: 4 times 

of the branch line; Branch line 2.5 times; Main line 2 times. According to the empirical formula: 

Single-phase circuit: I

n

 ≥In/2000 (lighting) 

Three-phase loop: I

n

 ≥In/1000 (power or power lighting hybrid) I

n

 is the maximum current. 

4)  In  order  to  ensure  the  selectivity  of  hierarchical  protection  action,  the  current  and  time 

coordination between the upper and lower levels shall conform to the following provisions: 

I

n1

 (upper) ≥I

n2

 (lower) 

tF (upper ASJ return time) > tFA (low ASJ break time), the time difference is not less than 0.2s. 

General branch line and end: 30~100mA, ≤0.1s;Branch line: 300~500mA, 0.2~0.8S; 

Main line: 500~1000mA, ≤2s. 

5

System Selection Instructions 

Type of 

system 

Wiring of system 

description 

TT system 

 

ASJ  is  recommended.  The  earth  fault 

current  is  very  small  and  difficult  to  be 

estimated,  operating  current  can  not  be 

reached,  and  the  hazardous  voltage  will 

appear on the shell.   

TN-S 

system 

 

ASJ  can  be  used.  cut  off  the  fault  more 

quickly  and  sensitively,  improve  the  safety 

and reliability. PE line is not allowed to pass 

through the transformer.   

TN-C 

system 

 

ASJ  can  not  be  used,  if  PEN  line  is  not 

iterative earthing, the ASJ refuse to operate; 

if PEN line is iterative earthing, ASJ will be 

misoperated.   

TN-C-S 

system 

 

If it is the TN-C system in front of the point 

F,  ASJ  is  not  allowed;  if  it  is  the  TN-S 

system  at  the  back  of  point  F,  ASJ  can  be 

used,  but  PE  line  cannot  pass  through  the 

transformer.   

IT system 

 

ASJ  can  be  applied.  The  insulation 

monitoring  device  is  applied  firstly  and  the 

residual current device is applied to prevent 

the reduction of insulation in the system and 

make it the secondary backup protection,   

 

5.5 Instructions for the selection of transformer 

type 

hole 

Main loop rated current 

ratio 

AKH-0.66L45 

45mm 

80A 

1A:1mA 

Summary of Contents for ASJ Series

Page 1: ...041 ASJ Series Residual Current Operated Relay Installation and Operation Instruction V1 9 Acrel Co LTD...

Page 2: ...tions in this operation manual and Acrel does not take responsibility for personal injuries or economic losses caused by ignoring tips of this manual The contents of the manual will be continuously up...

Page 3: ...ing attention 4 5 Operating Guide 5 5 1 Description of AC type Panel 5 5 2 Description of A type panel 5 5 3 Description of LCD type panel 5 5 4 Description of Selection 6 5 5 Instructions for the sel...

Page 4: ...Rated residual operating current can be measured Limit non driving time can be set Two sets of relay output With local and remote test and reset functions Guide DIN 35mm ASJ10 LD1A A type residual cu...

Page 5: ...0 0 06 0 1 0 2 0 3 0 5 0 8 1 4 10 s note 4 Rated residual non operating current I no 50 I n 50 I n Performance characteristics Sinusoidal AC Sinusoidal AC and pulsating DC Frequency 50Hz 5Hz 50Hz 5Hz...

Page 6: ...1 Installation Steps ASJ20 series instrument installation method is panel installation both sides of the buckle extrusion fixed the specific operation is as follows 1 On the switchboard choose the ap...

Page 7: ...xiliary power supply and signal input terminal Auxiliary power supply Signal input 4 3 2 Switching quantity input output terminal DI1 DI2 COM1 24 25 33 Relay output terminal Switching input terminal n...

Page 8: ...t button To reset the system 3 Alarm light Lights when the rated residual operating current I n is exceeded 4 Test button To test whether the indicator light is normal and the relay can operate normal...

Page 9: ...ing time setting value and communication status The LCD backlight is green in normal operation When alarming the residual current reaches the alarming value and the backlight is red When the residual...

Page 10: ...nded The earth fault current is very small and difficult to be estimated operating current can not be reached and the hazardous voltage will appear on the shell TN S system ASJ can be used cut off the...

Page 11: ...and next section only applies to ASJ10L LD1A First Menu Second Menu Third menu Descriptions Addr 1 247 none Address setting bAUd 1200 2400 4800 9600 19200 38400 none Communication Baud rate setting AL...

Page 12: ...turn value of alarm and prewarning operating current is 85 When the leakage current is less than 85 of the rated residual operating current the alarm relay AL1 is reset and when the leakage current is...

Page 13: ...irst event record is generated by the residual current alarm action the alarm value is 200 mA the occurrence time is 11 03 12 08 2 Set the residual current operating value to 50mA _ represents the mod...

Page 14: ...0ms Long press PROG Press Td to modify Press Td to modify number password confirm press PROG Press PROG Press RESET Press Td Press PROG Press RESET Press Td or Td Press PROG Press Td Running PASS Addr...

Page 15: ...Press PROG Press RESET Running PASS XXXX Long press PROG Press Td to modify press Td to modify number password confirm Press PROG Password confirm N Press RESET Addr bAUd AL Td 1 247 Press RESET Pres...

Page 16: ...byte n byte 2 bytes Address code the address code is composed of one byte 8 bit binary at the beginning of the frame and the decimal is 0 255 Only 1 247 is used in the residual current relay and othe...

Page 17: ...ion there is a method to calculate CRC by using the preset table Its main feature is that the calculation speed is fast but the table needs a large storage space This method will not be described here...

Page 18: ...H retain 3 0008H Rated residual operating current setting R W 10 30000mA word 4 0009H Prewarning operating current value R W 10 30000mA word 5 000AH 000FH retain 6 0010H Limit non driving time value R...

Page 19: ...parsing The parameter of address 001CH represents the current setting value as shown in the table below High 8 bit Bit15 Bit14 Bit13 Bit12 Bit11 Bit10 Bit9 Bit8 Low 8 bit Bit7 Bit6 Bit5 Bit4 Bit3 Bit...

Page 20: ...break line alarm 3 201812 V1 5 Add chapter 4 2 2 4 201912 V1 6 Delete ASJ10L 5 202012 V1 7 Add ASJ10L modify address contact 6 202104 V1 8 Modify AC type output as open Modify some mistake add transf...

Page 21: ...Fax 0086 21 69158303 Web site www acrel electric com E mail ACREL008 vip 163 com Postcode 201801 Manufacturer Jiangsu Acrel Electrical Manufacturing Co LTD Address No 5 Dongmeng Road Dongmeng industr...

Reviews: