7
#:
Meter identification code: ARTU remote signal unit 201
Note: SOE address from 25 to 12824, total 12,800 *2=25600 bytes;1600 sets of data (each set of data is 16 bytes,
it is recommended that users read 16 bytes continuously to avoid reading errors);1600 data loop stores.It is
recommended that the user first read the SOE counter, and that the address of the SOE record that recently occurred
is the contents of address 11.
Examples:
25
(Data 1) Milliseconds (integer)
26
(Data 1) Second Minutes (BCD code)
27
(Data 1)hour day (BCD code)
28
(Data 1) Month year (BCD code)
29
(Data 1) Channel has events 32-17
30
(Data 1) Channel has events 16-1
31
(Data 1) Channel event status 32-17
32
(Data 1) Channel event status 16-1
Address 25: The millisecond hexadecimal 03 45H event takes place is 837 milliseconds
Address 26: The seconds in which the event occurred (seconds before and after) are 45 minutes and 23 seconds
for BCD code 23 45H
Address 27: The time of the event (time after the previous day) BCD code 12 30H is 12 o 'clock on the 30th
Address 28: The month year of the incident (month after the year before last) BCD code 07 07H is July 2007
Address 29 and 30: Each bit corresponds to a channel, which corresponds to channel 32-1 in turn. The highest
value of address 29 is 1, which means that channel 32 has an event at this time, and 0, which means that no event has
occurred in this channel.
Address 31 and 32: If the corresponding bit of address 29 and 30 is 1, it means that an event has occurred in the
corresponding channel; if the bit is 1, it means that the channel hops from opening to closing; if the bit of address 29
and 30 is 0, the contents of the corresponding address 31 and 32 have no meaning.
Assume address 29 is 0x0002, address 30 is 0x0004, address 31 is 0x0002, address 32 is 0x0000 means channel
18 hops become closed and channel 3 hops become disconnected.
12817
(Data n) Ms (integer)
Fixed-poin
t number
R
03
、
04
2
12818
(Data n) seconds, minutes
(BCD code)
Fixed-poin
t number
R
03
、
04
2
12819
(Data n)hour, day (BCD code)
Fixed-poin
t number
R
03
、
04
2
12820
(Data n)Month, year (BCD code)
Fixed-poin
t number
R
03
、
04
2
12821
(Data n)There is an event channel
32-17
Fixed-poin
t number
R
03
、
04
2
12822
(Data n)There is an event channel
16-1
Fixed-poin
t number
R
03
、
04
2
12823
(Data n)Channel event status 32-17
Fixed-poin
t number
R
03
、
04
2
12824
(Data n)Channel event status 16-1
Fixed-poin
t number
R
03
、
04
2