9 / 11
8.3 Address table of AIM-T500
No.
Address
Parameter
Read/
write
Value range
Data
Type
1
0000H
Passwords
R
0000-9999 (default 0000)
word
2
0001H high
Address
R
1~247 (default 1)
word
0001H low
Baud rate
R
0~3: 4800, 9600, 19200, 38400
(unit bps) (default 9600)
3
0002H high
Contrast ratio
R
15-60 (default: 30)
word
0002H low
Display time
R
15~250 (unit second) (default 60, 15 light)
4
0003H high
Year
R/W 0~99
word
0003H low
Month
R/W 1~12
5
0004H high
Day
R/W 0~31
word
0004H low
Warning mark
R
0: none 1: warning 2: early warning and alarm
6
0005H high
Hour
R/W 0~23
word
0005H low
Minute
R/W 0~59
7
0006H high
Second
R/W 0~59
word
0006H low
Data stable
R
0 or 1 (0 invalid, 1 stable)
8
0007H high
Warning value
R/W 60~4999 (unit: k Ω) (default: 60)
word
0007H low
Warning value
9
0008H high
Alarm value
R/W 10~4999 (unit: k Ω) (default: 38)
word
0008H low
Alarm value
10
0009H high
Resistance value
R
1~10001 (unit: k Ω)
word
0009H low
Resistance value
11
000AH
SN (high 16 bits)
R
Default: 0000000000
word
12
000BH
SN (low 16 bits)
word
13
000CH
Reserve
word
14
000DH
Leakage capacity
R
0~500 (unit: μF)
word
15
000EH high
Symbol of broken
line
R
0: none
4:PE/KE broken line
word
000EH low
Current period
2~200 (unit s)
16
000FH high
Whether access
system
R
0: no access system
1: access system
word
000FH low
Reserve
17
0010H high
Fault
Record
1
STA1
R
The sequence number of incident record
word
0010H low
R
Incident1content: 0~2
0: a fault free record
1: early warning
2: alarm
18
0011H
resistance
value
R
incident 1 insulation resistance
word
19
0012H high
Year1
R
incident 1 time -year
word
0012H low
Month1
R
incident 1 time -month