ACPro 024K Series Installation Instructions Manual Download Page 4

4

area where they will be shaded from the afternoon sun, when 

the heat load is greatest.

•  Consideration should also be given to availability of electric 

power, service access, noise, and shade.

•  Overhead obstructions, poorly ventilated areas, and areas 

subject to accumulation of debris should be avoided. The 

hot condenser air must be discharged up and away from the 

home, and if possible, in a direction with the prevailing wind. 

Do not place the unit in a confined space. See 

Figure 9 (page 

17)

 for unit dimensions.

• Sufficient clearance for unobstructed airflow through the 

outdoor coil must be maintained in order to achieve rated 

performance (except on supply & return duct (rear) side). For 

minimum clearances to obstructions, see 

Figure 1

.

Minimum Clearances

Minimum clearances MUST be maintained from adjacent 

structures to provide room for proper servicing and air circulation. 

DO NOT install unit in a confined or recessed area that will allow 

discharge air from the unit to re-circulate into the condenser air 

inlet, through the coil. See 

Figure 1

.

Service Access Clearance:

Blower and electrical access panels .......................... 24”
Compressor compartment access panel ................. 12”
Clearance from top of unit  .................................... 72”
Clearance around condenser coil area to
wall or shrubs (excludes duct panel side) .................. 12”

Clearances to Combustibles:

Combustible base - wood or Class A, B, or C
roof covering material ................................................. 0”
Supply & return air ducts ............................................ 0”
Duct connection side .................................................. 0”

REQUIREMENTS & CODES

•  All electrical wiring must be completed in accordance with 

local, state & national codes and regulations and with the 

National Electric Code (ANSI/NFPA 70) or in Canada the 

Canadian Electric Code Part 1 CSA C.22.1.

•  The installer must comply with all local codes and regulations 

which govern the installation of this type of equipment. 

Local codes and regulations take precedence over any 

recommendations contained in these instructions. Consult 

local building codes and the National Electrical Code (ANSI 

CI) for special installation requirements.

•  Air Ducts must be installed in accordance with the standards 

of the National Fire Protection Association “Standards for 

Installation of Air Conditioning and Ventilation Systems” (NFPA 

90A), “Standard for Installation of Residence Type Warm Air 

Heating and Air Conditioning Systems” (NFPA 90B), these 

instructions, and all applicable local codes.

• Consult 

Table 1 (page 9)

, and the rating plate for the 

proper circulating air flow and temperature rise. It is important 

that the duct system be designed to provide the correct flow 

rates and external pressure rise. An improperly designed 

duct system can result in nuisance shutdowns, and comfort 

or noise issues.

•  This unit is designed for outdoor installations only and should 

be positioned as described in Locating the Heat Pump.

GENERAL INFORMATION

Single packaged heat pumps are ready for easy and immediate 

installation and can be readily connected into the high static duct 

system of a home. This unit is completely assembled, wired, 

and run tested at the factory. 

This heat pump is designed 

for outdoor installation only. 

The only connections needed 

for installation are the supply and return ducts, line voltage, 

thermostat wiring and the condensate drain. Use of components 

other than those specified may invalidate AHRI Certification, 

Code Agency Listing, and limited warranty on the air conditioner.

Before You Install this Unit

 The cooling load of the area to be conditioned must be 

calculated and a system of the proper capacity selected. It is 

recommended that the area to be conditioned be completely 

insulated and vapor sealed.

 Check the electrical supply and verify the power supply is 

adequate for unit operation. If there is any question concerning 

the power supply, contact the local power company.

 All units are securely packed at the time of shipment and 

upon arrival should be carefully inspected for damage prior 

to installing the equipment at the job site. Verify coil fins are 

straight. If necessary, comb fins to remove flattened or bent 

fins. Claims for damage should be filed immediately with the 

carrier.

 Please consult your dealer for maintenance information 

and availability of maintenance contracts. Please read all 
instructions before installing the unit.

Locating the Heat Pump

•  Survey the job site to determine the best location for mounting 

the outdoor unit. Select a solid, level position, preferably on a 

concrete slab, slightly above the grade level, and parallel to 

the home. Unit can also be mounted on a roof curb or a metal 

stand. High wind kits are available to prevent unit movement 

in adverse conditions. If possible, select a site for the unit that 

is as close as possible to the proposed return grille location. 

DO NOT PLACE UNIT UNDER THE HOME.

•  The unit should be located with consideration of minimizing 

the length of the supply and return ducts with no sharp radius 

bends. If practical, place the heat pump and its ducts in an 

0"

12"

24"

72”

 CLEARANCE  FR

OM 

TO

P

OF UNIT

0"

Rear (Duct) Side

Front Side

Figure 1. Minimum Unit Clearances

Summary of Contents for 024K Series

Page 1: ...s an important role as well Pay attention to all safety warnings and any other special notes highlighted in the manual Improper installation of the furnace or failure to follow safety warnings could r...

Page 2: ...0 Start Up Procedure 10 Air Circulation 10 System Heating 10 System Cooling 10 Short Cycle Protection 10 Emergency Heat 10 Anti Short Cycle Timer Test 10 Heating Mode 10 Cooling Mode 10 UNIT MAINTENAN...

Page 3: ...Disturbing the insulation of this product during installation maintenance or repair will expose you to fiberglass wool Breathing this material may cause respiratory irritations or may cause lung canc...

Page 4: ...w and temperature rise It is important that the duct system be designed to provide the correct flow rates and external pressure rise An improperly designed duct system can result in nuisance shutdowns...

Page 5: ...or insulation material requirements HEAT PUMP INSTALLATION Unpacking the Unit It is recommended that the unit be unpacked at the installation site to minimize damage due to handling CAUTION Do not tip...

Page 6: ...ble if a minimum two inch clearance is available 1 Start the installation from under the home by cutting a small hole in the sub floor Determine how the floor joist location will affect cutting the op...

Page 7: ...ecttheline voltageleadstotheterminalsonthecontactor inside the control compartment Extend leads through power wiring hole See Figure 7 Connect L1 L2 directly to the contactor Use only copper wire for...

Page 8: ...ere is no Y1 IN input present Without resetting using the test pins the fault codes will stay in the board s memory continuously even through loss of power for 7 days Electric Heat Package optional Th...

Page 9: ...37 796 40 Tap T2 1308 24 1271 25 1230 26 1185 27 1136 28 1084 29 1027 31 967 33 Tap T3 1266 25 1332 24 1291 24 1245 25 1192 27 1132 28 1067 30 995 32 Tap T4 1518 21 1481 21 1442 22 1400 23 1355 23 13...

Page 10: ...ure Allow the cooling system to operate for several minutes and check for the discharge of cool air at the supply registers Short Cycle Protection The control circuit is equipped with a time delay fea...

Page 11: ...is closed If the suction pressure falls below 5 psig then the switch will open and de energize the unit The switch will close again once the suction pressure increases above 20 psig The low pressure s...

Page 12: ...75 80 85 90 95 100 105 LIQ PRESS DIS TEMP LIQ PRESS DIS TEMP LIQ PRESS DIS TEMP LIQ PRESS DIS TEMP LIQ PRESS DIS TEMP LIQ PRESS DIS TEMP LIQ PRESS DIS TEMP LIQ PRESS DIS TEMP 135 238 135 137 239 139...

Page 13: ...R TEMPERATURE F 70 75 80 85 90 95 100 105 LIQ PRESS DIS TEMP LIQ PRESS DIS TEMP LIQ PRESS DIS TEMP LIQ PRESS DIS TEMP LIQ PRESS DIS TEMP LIQ PRESS DIS TEMP LIQ PRESS DIS TEMP LIQ PRESS DIS TEMP 135 26...

Page 14: ...e suction pressure will vary from design value if outdoor air flow entering dry bulb or entering wet bulb temperatures vary NOTES 1 All pressures are listed psig and all temperatures in F 2 Discharge...

Page 15: ...63 124 69 283 130 84 307 145 105 352 166 126 396 188 43 231 109 52 249 116 61 268 122 70 287 128 85 314 142 106 359 162 127 403 182 44 238 107 53 255 114 62 273 120 71 290 126 86 321 139 107 366 157 1...

Page 16: ...115 47 242 123 58 268 132 69 294 141 84 324 158 104 374 183 124 424 208 38 223 113 48 248 121 59 273 130 70 298 139 85 331 155 105 381 178 125 431 201 39 230 111 49 254 119 60 278 128 71 301 137 86 3...

Page 17: ...02 2 48 Figure 9 Physical Data Unit Dimensions A 3 Opening for 12 Diameter Supply Duct 9 15 17 50 9 0 Opening for 14 Diameter Return Duct 10 15 5 5 B 1 3 15 Alternate Power Supply Entry Rear View L W...

Page 18: ...connections use copper conductors only 3 Not suitable on systems that exceed 150V to ground 4 For replacement wires use conductors suitable for 105 C 1 Couper le courant avant de faire letretine 2 Emp...

Page 19: ...servicing 2 For supply connections use copper conductors only 3 Not suitable on systems that exceed 150V to ground 4 For replacement wires use conductors suitable for 105 C 1 Couper le courant avant...

Page 20: ...1 Disconnect all power before servicing 2 For supply connections use copper conductors only 3 Not suitable on systems that exceed 150V to ground 4 For replacement wires use conductors suitable for 105...

Page 21: ...nd stage outdoor thermostat is field supplied NOTE 2 HUD outdoor thermostat is not factory installed in all models For HUD applications Remove white wire between terminal W2 and W2 IN terminal C G O W...

Page 22: ...22...

Page 23: ...23...

Page 24: ...NSTALLATION ADDRESS CITY STATE UNIT MODEL UNIT SERIAL Unit Installed Minimum clearances per Figure 1 page 4 YES NO INSTALLER NAME CITY STATE Has the owner s information been reviewed with the customer...

Reviews: