background image

 

DevType 

Addr 

Stdval 

ThrTyp 

Dirty 

FrmVer 

PrdDate 

TstDate 

Op Mode 

Set Mod / 

Set Op 

Customer 

Battery 

All analogue smoke 
detectors 

 

 

 

 

All analogue smoke 
and thermal 
detectors     

 

 

 

 

All analogue 
thermal detectors 

 

 

 

 

Enhanced conven-
tional smoke 
detector 

 

 

 

 

 

Enhanced conven-
tional smoke and 
thermal detector 

 

 

 

 

Enhanced conven-
tional thermal 
detector 

 

 

 

 

 

All analogue 
resettable call 
points 

 

 

 

 

 

All analogue wall 
sounders     

 

 

 

 

 

Base loop sounder 
(non 32 tones) 

 

 

 

 

 

32 tones base loop 
sounder and audio-
visual variant 

 

 

 

All analogue input 
modules and 
channels 

 

 

 

not used 

not used 

All analogue 
supervised output 
modules and 
channels   

 

 

 

 

 

All analogue relay 
output modules 
and channels     

 

 

 

 

 

All multiple chan-
nel module devices 

 

 

not used 

not used 

All multi-modules 

 

 

Conventional zone 
module 

 

 

 

Analogue loop 
beacon 

 

 

 

 

 

Analogue remote 
indicator lamp 

 

 

 

 

 

Picture 1 - 

overview of the 

programming 

unit 

Picture 2 - the 
adaptor base 
for sensors on 
the program-
ming unit 

Picture 4 - the 
programmer’s  
socket  

Picture 5B - the jack to female 

plug-in terminal block cable 

Picture 7 - an example of 
cable connection between 
the programmer and a 
conventional zone module 

Picture 8 - the cable’s 

plug-in female terminal 

block in detail 

Picture 9 - the key-

display interface 

in detail 

UP 

DOWN 

WRITE 

READ 

 

GENERAL DESCRIPTION 

 
This product permits to set and read various parameters stored in the devices of the analogue-intelligent and the enhanced conventional 
series family. Connection to the devices is made through the adaptor base of the programming unit for the detectors or through one of the 
two plug-in cables (supplied with the product) for all other devices (only for the analogue-intelligent series). 
 
The user can interact with the programming unit by using its in-built keypad and display; through this interface the user navigates through a 
menu-based set of options and commands, permitting him to program certain parameters on the devices or to read data from them. 
 
The programming unit can be used, for example, to: 
 
- read and set an analogue address on a device, 
 
- change a conventional or analogue temperature sensor from Rate Of Rise to High Temperature or vice versa, 
 

 

- read the firmware version of a device and other data, 
 
- activate or deactivate input or output channels on a multi-module device, 
 
- programming a conventional zone module, 
 
- program the operating mode on a 32 tones analogue base sounder or its audio-visual variant. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

POWER SUPPLY 

 
The programming unit needs to be power supplied: for this purpose a 9 V battery (supplied with the 
product) is needed; to install the battery into the programming unit follow these steps: 
 
1) Slide-off the battery lodgment cover from the programming unit. 
 
2) Connect the device’s snap connector to the power supply battery. 
 
3) Insert the battery into its lodgment. 
 
4) Slide-in the battery lodgment cover onto the programming unit. 
 

CONNECTING DEVICES TO THE PROGRAMMING UNIT 

 
Only one device can be connected to the programming unit at a time; depending on the device type, 
one of the three following ways of connection must be selected: 
 
- Detector devices must be installed on the programming unit’s adaptor base. 
 
- Analogue 32 tones base sounders (and their audio-visual variants) must be connected to the pro-
gramming unit with the supplied jack to jack cable (see picture 5A): insert  one jack plug into the 
programmer’s socket and the other jack into the sounder’s lateral socket (see picture 6). 
 
- All other devices (only analogue-intelligent) must be connected to the programming unit with the jack 
to female plug-in terminal block cable (picture 5B): insert the cable’s jack pin into the programmer’s 
socket and the cable’s female plug-in terminal block into the device’s analogue loop male socket (see 
picture 7 as an example and check the product’s specific installation manual). 
 

Important note: avoid having a detector installed onto to the programming unit and another 
device connected through the cable: if so is done, the programming unit will give you false 
information. 

 

You can notice that the “jack to terminal block” cable is composed of two wires: one is positive (red 
color) and the other one is negative (black color). When inserting the plug-in female terminal block, 
check the corresponding polarity on the device’s analogue loop male socket: positive polarity coincides with positive polarity and negative 
polarity coincides with negative polarity (see picture 8); in order to perform this operation you need to look at the polarity label on the device 
itself and its installation instructions manual. 
 
 
 
 
 
 
 
 
 
 
 
 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 
 
 
 
 
 
 
 
 
 
 
 
 
 

PROGRAMMING UNIT’S KEYS - THE READ KEY 

 
The 

READ 

key has two purposes:  

 
- Enter into the main menu 
 
- Enter into the address menu. 
 
- “Refresh” the address menu 
 
- Cancel a programming action that has not been yet executed. 
 

PROGRAMMING UNIT’S KEYS - THE WRITE KEY 

 
The 

WRITE 

key has two purposes: 

 
- Enter into a sub-menu. 
 
- Confirm and program a selected parameter into the connected device. 
 
 

PROGRAMMING UNIT’S KEYS - THE ‘UP’ AND ‘DOWN’ KEYS 

 
The 

UP 

and 

DOWN 

keys have the following functions: 

 
- Increase (

UP

) or decrease (

DOWN

) the address that can be assigned to an analogue device. 

 
- Increase (

UP

) or decrease (

DOWN

) the “operating mode” setup number to be assigned to a device. The “operating  mode” feature, that is 

applied only to certain analogue-intelligent devices, will be explained later. 
 
- Navigate through the device’s menu or sub-menu. 

Picture 3 - the programming 

unit, the power supply 

battery and its cover 

ACTIVATING THE PROGRAMMING UNIT 

 
After having connected the programming unit to a device, press 

READ 

once; on the display will appear the indication of the programming 

unit’s firmware version. Programming unit’s firmware version can be assessed only in this activation phase. 
 
After this initial phase, the display will visualize automatically the address menu. 
 

ADDRESS MENU 

 
This menu is used to read and set the address of the connected analogue-intelligent device and it will work only on this type of devices. This 
menu is accessible automatically at start up or from the main menu by pressing the 

READ

 key. 

The 

Address

 caption will be visualized on the display, and under it a three digit number (indicating the actual address of the device) or a 

No 

Addr

 (no address, if the device hasn’t got, actually, an address). 

When in this menu, by just clicking 

READ

 once, it is possible to read again the address of the connected device, performing a menu 

“refresh” function. 
By using the 

UP

 and 

DOWN 

keys, it is possible to increment or decrement the indicated number, and, after it is chosen, press the 

WRITE

 

key to memorize it on the connected analogue device (address storing will fail if an enhanced conventional detector is connected!). 
 

STORING WARNING 

 

WHEN STORING A PARAMETER, DO NOT DISCONNECT THE DEVICE: THIS CAN DAMAGE IT IRREPARABLY.

 

 

THE MAIN MENU 

 
From the address menu press the 

READ

 key for some seconds: 

Family

 caption will appear giving the user the following options, scrollable 

with the 

UP 

and 

DOWN 

keys: 

 

Aurora

: this option must be selected if an enhanced conventional detector is connected to the programmer; if selected, an enter test is 

made: if successful the main menu is visualized and if not, an error is visualized. 
 

Vega

: this option must be selected if an analogue-intelligent device is connected to the programmer; no enter test is performed, but the main 

menu will not work for a conventional sensor. 
 
The main menu permits to view the data of the connected device and to perform certain setting operations on it. 
 
Visualized data and available commands are not the same for all the devices, but the most of them are common. 
 
A description of the possible menu options and visualized data will be given: 
 

DevType

: “device type”: under this caption, the programming unit will visualize the short name of the connected device type. 

Device type datum is visualized for every device. 
 

Addr

: “address”: this caption, followed by an analogue address number, indicates, under it, the device type associated to such address; is 

used only for multiple channel module devices and multi-modules, where, for each channel, its address and “sub-device” type needs to be 
visualized on the programming unit. 
 

Stdval

: “standard value”: depending on the device type connected, it indicates: 

 
- If an analogue-intelligent device is connected, it indicates its “analogue standard value”: this is a common internal index for the analogue 
series devices; this value ranges from 0 to 255, but in normal condition is stable around 32; when the device is alarmed or activated, this 
value is set to 192. 
Standard value datum is visualized for every analogue-intelligent device. 
 
- If an enhanced conventional detector is connected, it indicates the “photo value”: this is a non standardized internal  index and it is visual-
ized only for conventional detectors having a smoke sensing feature. 
 

ThrTyp

: “thermal type”: indicates whether the thermal sensor, installed on the programming unit, is a a standard ROR (Rate Of Rise)  or an 

high temperature one. By pressing the 

WRITE

 key, it is possible to access the sub-menu that permits to program the thermal operating 

mode (ROR or high temperature). 
Thermal type datum is visualized for enhanced conventional and analogue-intelligent detectors having a thermal sensing feature. 
 

Dirty

: indicates the pollution percentage present in the optical chamber of analogue-intelligent and enhanced conventional smoke and 

smoke-thermal detectors. 
 

FrmVer

: “firmware version”: indicates the version release number of the firmware loaded into the connected enhanced conventional or 

analogue-intelligent device. 
This datum is common to all enhanced conventional and analogue-intelligent devices. 
 

PrdDate

: “production date”: indicates the date (year and week) of firmware’s programming into the connected device. 

Production date firmware datum is common for every enhanced conventional and analogue-intelligent device. 
 

TstDate

: “test date”: indicates the date (year and week) of the connected device’s functional test in the producer’s factory. 

Test date datum is common for every enhanced conventional and analogue-intelligent device. 
 

Op Mode

: “operating mode”: indicates a decimal value that, if programmed into certain analogue-intelligent devices, sets its functional 

operating characteristics. 
Operating mode datum is visualized and used only for analogue multi-modules, conventional zone modules and analogue 32 tone base 
sounders and their audio-visual variants. 
 

Set Mod / Set Op

: “set (operating) mode”: when this caption appears, the pressing of the 

WRITE

 key permits to access the operating mode 

value selection sub-menu (with the 

Sel Op

 caption on the display). 

Operating mode datum is visualized and used only for analogue multi-modules, conventional zone modules and analogue 32 tone base 
sounders and their audio-visual variants. 
 

Customer

: indicates the customer code security value programmed into the connected analogue-intelligent device. 

Customer code value datum is visualized for all analogue-intelligent devices. 
 

Battery

: indicates the remaining battery’s power supply percentage of the programming unit. 

Battery datum is always visualized, even if the programmer is not connected to any analogue-intelligent device. 

Picture 5A - the jack 
to jack cable 

Picture 6 - an example of cable 
connection to the 32 tones 
analogue base sounder 