SGM3000 Series Smart Meters
User Manual
80
GEH-7111-1.00-2
Restricted
demand will begin); summations and demands for the
programmed default TOU rate will also be updated.
8.9.1.2 Er 000 200
—Non-Volatile Data Error
The Non-Volatile Data error indicates a failure in the memory used to store configuration
information, billing data, self-reads, event logs, and load profile data. When the meter is not
communicating, it continually tests the integrity of the data stored in non-volatile memory. If
the meter detects an error in the non-volatile data, it sets the Non-Volatile Data error. If
subsequent tests pass, the error is cleared. A meter with a persistent Non-Volatile Data error
should be removed from service and returned to GE.
Table 10 Er 000 200
Date & Time:
OK
Load Profile recording:
May be corrupt
Register Function:
Unchanged
Program:
May be corrupt
TOU schedule:
May be corrupt
TOU calendar:
May be corrupt
Billing Data:
May be corrupt
8.9.1.3 Er 001 000
—Firmware Code Error
The Firmware Code error indicates a failure in the memory used to store firmware. When the
meter is not communicating, it continually tests the integrity of the firmware stored in memory.
If the meter detects an error in the firmware, the meter sets Firmware Code error. If
subsequent tests pass, the error is cleared. A meter with a Firmware Code error should be
removed from service and returned to GE.
Table 11 Er 001 000
Date & Time:
May be corrupt
Load Profile recording:
May be corrupt
Register Function:
Unchanged
Program:
May be corrupt
TOU schedule:
May be corrupt
TOU calendar:
May be corrupt
Billing Data:
May be corrupt
8.9.1.4 Er 100 000
—Meter Chip Error
The Meter Chip error indicates the meter has detected an error in the operation of its meter
chip. If subsequent correct operation occurs, the error is cleared. A meter with a persistent
Meter Chip error should be taken out of service and returned to GE.
Table 12 Er 100 000
Date & Time:
OK
Load Profile recording:
Corrupt data