SGM3000 Series Smart Meters
User Manual
Restricted
GEH-7111-1.00-2
17
2.4 Operating
Range
Table 1 Operating Range
Voltage
127V , 220 V to 240 V ± 20%
Operating Temperature
−25 °C to +60 °C
(
−40 °C to +70 °C limit range of operation)
Storage Temperature
−40 °C to +70° C
Relative Humidity
non-condensing
Intended Use
Outdoor
Frequency
50 Hz
Starting Currents
Direct connect meters = 45 mA
SGM30C2 CT connect = 3 mA
Power Consumption (excluding communication
modules)
1.2 W for Single Phase
1.7 W for Three Phase
Accuracy
Class 1 per IEC® 62053
–21 / Class 2 per IEC 62053–
23
Current
100 A (maximum)
10 A (basic)
Enclosure
IP54 (IEC 60529, 2001
– 2002 Edition 2.1, outdoor
rating).
Insulation Class Index
Protective Class II
Mechanical Rating (Vibration & Shock)
The meter is designed to work in mechanical
environments classified as class M1 as described in
DIRECTIVE 2004/22/EC OF THE EUROPEAN
PARLIAMENT AND OF THE COUNCIL of 31 March
2004 on measuring instruments. This class allows the
instruments to be used in locations with vibration and
shocks of low significance.
Electromagnetic Rating
The meter is designed to work in Electromagnetic
environments classified as class E2 as described in
DIRECTIVE 2004/22/EC OF THE EUROPEAN
PARLIAMENT AND OF THE COUNCIL of 31 March
2004 on measuring instruments. This class allows the
instruments to be used in locations with
electromagnetic disturbances corresponding to those
normally to be found in industrial buildings.
2.5 Meter Models (Physical Variants)
The SGM3000 Series Smart Meters family is made up of eight meters that share common
physical characteristics and functionality.