38
S G M 1 4 0 0 S e r i e s S m a r t M e t e r U s e r M a n u a l – S M E T S 2
Profiles
If the RMS voltage returns to a value below the RMS Extreme Over Voltage
Threshold longer than the configured measurement period, the meter will generate
a corresponding entry in the Power Event Log and send an alert to the HAN
interface.
RMS extreme Under Voltage
If the RMS voltage falls below the RMS Extreme Under Voltage Threshold for a
duration longer than the configured measurement period, the meter will generate a
corresponding log entry and send an alert to the HAN interface.
When the RMS voltage returns to a value above the RMS Extreme Under Voltage
Threshold for a duration longer than the configured measurement period, the
meter will generate a corresponding log entry and send an alert to the HAN
interface.
RMS Voltage Sag
If the RMS voltage falls below the RMS Voltage Sag Threshold for a duration
longer than the configured measurement period, the meter will generate a
corresponding entry in the Power Event Log and send an alert to the HAN
Interface.
When the RMS voltage returns to a value above the RMS Voltage Sag Threshold
for a duration longer than the configured measurement period, the meter will
generate a corresponding log entry and send an alert to the HAN interface.
RMS Voltage Swell
If the RMS voltage rises above the RMS Voltage Swell Threshold for a duration
longer than the configured measurement period, the meter will generate a
corresponding entry and send an alert to the HAN interface.
When the RMS voltage returns to a value below the RMS Voltage Swell
Threshold for a duration longer than the configured measurement period, the
meter will generate a corresponding log entry and send an alert to the HAN
interface.
Supply Outage Reporting
The meter may be configured to record the date and UTC when the supply is
interrupted and when it is restored. Once configured, the meter will generate a
corresponding entry in the Power Event Log. Once the supply has been restored,
the meter will send an alert to the HAN interface that includes the date and UTC
of both the interruption and restoration.
Profiles
The SGM1400-B Series meter supports non-volatile recording of two profiles of a
number of quantities (channels) at discrete time intervals (periods).
These two profiles are load profile (profile 1) and instrumentation profile (profile
2). These profiles are usually defined by the quantity type captured in each profile:
Summary of Contents for SGM1400 Series
Page 2: ......
Page 4: ...ii S G M 1 4 0 0 S e r i e s S m a r t M e t e r U s e r M a n u a l S M E T S 2...
Page 12: ...2 S G M 1 4 0 0 S e r i e s S m a r t M e t e r U s e r M a n u a l S M E T S 2 Aclara Support...
Page 54: ...44 S G M 1 4 0 0 S e r i e s S m a r t M e t e r U s e r M a n u a l S M E T S 2 Billing Data...
Page 94: ...84 S G M 1 4 0 0 S e r i e s S m a r t M e t e r U s e r M a n u a l S M E T S 2 Disposal...