background image

DEVICE CONFIGURATION THROUGH MODBUS RTU

MODBUS RTU INTERFACE

The Modbus Remote Terminal Unit (RTU) data link protocol uses EIA-485 as a two-wire, daisy chain network. A 
branch is a discrete chain of devices connected to a controller. The max number of devices per segment is (32), as 
per the Modbus specifications. 4000 ft (1219.2 m) is the maximum recommended length for a segment, which 
includes all devices from the controller to the last device in the daisy chain. 

Each branch must have all devices connected with (A) connected to (A) and (B) connected to (B). If a shielded 
cable is used, this is not to be connected to the devices. The shield cable should only be connected on one end to 
earth ground, usually at the controller. 

Each device must be configured for the correct baud rate and have a unique address in each branch. The baud 
rate for the branch is set by the controller.

EOL Termination Resistance Selection

RS-485 requires that the last device in a chain have a termination resistor. This is controlled using the J8 
switch as shown in 

FIGURE 7

.

 

When the jumper is set to ON(Enabled), a 120 Ohm resistance is added in 

parallel to the data line. When the jumper is set to the left(Disabled), the resistance is not added. By default, 
the jumper is placed in the disabled position. 

MODBUS MESSAGE

Automation Components, Inc.

2305 Pleasant View Road  |  Middleton, WI 53562

Phone:

 1-888-967-5224  |  

Website:

 workaci.com

Page 4

CRC Check

16 bits

Data

N x 8 bits

Address

8 bits

Function

8 bits

Start

≥3.5 char

End

≥3.5 char

A typical Modbus RTU mode message frame is shown below. In the Modbus RTU mode, the messages 
between frames are separated by at least 3.5 characters time’s silent interval. If the silent interval between 
two characters is more than 3.5 characters time, the former character was transferred successfully, and the 
current character’s transmission starts. 

ADDRESS SELECTION 

A typical Modbus RTU mode message frame is shown below. In the Modbus RTU mode, the messages 
between frames are separated by at least 3.5 characters time’s silent interval. If the silent interval between 
two characters is more than 3.5 characters time, the former character was transferred successfully, and the 
current character’s transmission starts. 

BAUD RATE, DATA BITS, PARITY, AND STOP BITS SELECTION

Baud rate is set to 9600, but can also be configured to 4800 via the register. 

The device that requests information is called the Modbus Master and the devices giving the information 
are Modbus Slaves.  The Modbus sensors are slave devices and the number of Data Bits needs to be the 
same as in the Master device configuration. ACI’s Modbus RTU sensors utilize 8 data bits during 
communication exchange.

Parity default setting is NONE. Stop bit default setting is 1. Both settings can adjusted via the register.

FUNCTION

The function code is the second data in the frame. Valid function codes are from 0~127 (01H~7FH). See the 
relevant Modbus standard. It supports 03H/06H function codes, shown as the following Modbus Poll 
software. The detail register addresses are in:  6 General registers table.

BROADCAST MODE TO WRITE DATA TO SLAVE

Using broadcast mode, customer can write data to all slaves connected to the network. Address of 
broadcast mode to write data is 0.

For example: change slave address with broadcast mode, customer can set a new slave address. Note: since 
this operation will modify all the addresses of the slavers to the same address, it is NOT applicable for 
network of more than one slave.

SPECIAL MODE TO READ DATA FROM SLAVE

With the special mode, customer can read the register data under the circumstance of NOT knowing the 
slave address.

Address of special mode read data: 255(0xFF)

Note: this operation is applicable for ONLY ONE slave in the network.

Version: 2.0

I0000939

Summary of Contents for VOC-ROOM

Page 1: ...using the indoor air quality sensor described in this document to avoid erroneous readings and to prevent the device from permanent damage The sensor must not be exposed to high concentrations of org...

Page 2: ...transformer IF THE 24 VDC OR 24VAC POWER IS SHARED WITH DEVICES THAT HAVE COILS SUCH AS RELAYS SOLENOIDS OR OTHER INDUCTORS EACH COIL MUST HAVE AN MOV DC AC TRANSORB TRANSIENT VOLTAGE SUPPRESSOR ACI...

Page 3: ...evice in a chain have a termination resistor This is controlled using the J8 switch as shown in FIGURE 7 When the jumper is set to ON Enabled a 120 Ohm resistance is added in parallel to the data line...

Page 4: ...r and the devices giving the information are Modbus Slaves The Modbus sensors are slave devices and the number of Data Bits needs to be the same as in the Master device configuration ACI s Modbus RTU...

Page 5: ...d Function register Control setting point 1 Control setting point 2 Control setting point 3 Return difference Range for LED color to change Baud rate Parity Remarks Product code equivalent CO2 value U...

Page 6: ...4 20mA Default 0 10VDC 4 20 mA 500 Ohms maximum 0 10VDC 2K Ohms Minimum N O rated 3A 30VDC 3A 250VAC 230ppb 5 seconds 15 minutes Modbus RTU EIA RS 485 1 247 4800 or 9600 None Even Odd 1 8 ScrewTermin...

Page 7: ...Automation Components Inc 2305 Pleasant View Road Middleton WI 53562 Phone 1 888 967 5224 Website workaci com Page 7 Version 2 0 I0000939...

Page 8: ...c 2305 Pleasant View Road Middleton WI 53562 Phone 1 888 967 5224 Website workaci com Page 8 Automation Components Inc 2305 Pleasant View Road Middleton WI 53562 Phone 1 888 967 5224 Website workaci c...

Reviews: