Automation Components, Inc.

2305 Pleasant View Road  |  Middleton, WI 53562

Phone:

 1-888-967-5224  |  

Website:

 workaci.com

Page 2

Version: 1.0

I0000352

MOUNTING

 (Continued)

LCD Installation

The LCD Module should then be gently inserted into the 10 pin connector. Tighten the cover down, using 

the (2) 1/16” Allen screws located in the bottom of the housing. Take care to make sure the LCD module 

lines up with the enclosure LCD window. The LCD module can be bent if adjustments are needed. A 1/16” 

Hex driver is needed to secure the cover to the base.

WIRING INSTRUCTIONS

ACI recommends 16 to 26 AWG twisted pair wires or shielded cable for all sensors. Signal wiring must be 

run separate from low and high voltage wires (24/120/230 VAC). All ACI thermistors and RTD temperature 

sensors are both non-polarity and non-position sensitive. All thermistor type room units are supplied with 

a two-pole terminal block and all RTD’s can be supplied with either a two or three-pole terminal block. The 

number of wires needed depends on the application. All wiring must comply with all local and National 

Electric Codes.

The ACI/LCD must be powered with either a 24 

VAC or 9-35 VDC power source. The ACI/LCD uses 

a half-wave bridge rectifier to convert the AC 

voltage to a useable DC voltage. Two separate 

cables must be pulled for the ACI/LCD to work 

properly. One 2 conductor 18 to 22 AWG shielded 

cable for the supply voltage and a second 18 to 

22 AWG 3 to 8 conductor shield cable for the 

Temperature sensor, Set Point and Override 

Outputs to the controller.

FIGURE 3: 

LAYOUT

TABLE 1: 

TERMINAL BLOCK CONNECTIONS

TERMINAL
BLOCK

COM

SEN

SET

O/R

O/R

-(LCD)ONLY
+(LCD)ONLY

CONNECTIONS

Thermistor, Override, and Setpoint Common 
to controller analog input
Temperature sensor signal to controller 
analog input
Temperature set point signal to controller 
analog input
Override signal to controller analog input

Override signal common to controller 
analog input
24VAC or 9-35VDC Ground/Common
24VAC or 9-35VDC

TABLE 2: 

COMMUNICATION TERMINAL

BLOCK CONNECTIONS

COM. TERMINAL 

BLOCKS

TXD
GND
RXD

CONNECTIONS

RS232 Communication (Transmit)
RS232 Communication (Ground)
RS232 Communication (Receive)

Tip (TXD)

Mid (RXD)

Ring (GND)

RS232 Plug Diagram