aci ROOM Series Installation & Operation Instructions Download Page 3

WARRANTY

The ACI Room Series temperature sensors are covered by ACI’s Five (5) Year Limited Warranty, which is located in 
the front of ACI’S SENSORS & TRANSMITTERS CATALOG or can be found on ACI’s website: www.workaci.com.

W.E.E.E. DIRECTIVE 

At the end of their useful life the packaging and product should be disposed of via a suitable recycling 
centre. Do not dispose of with household waste. Do not burn.

PRODUCT SPECIFICATIONS

Automation Components, Inc.

2305 Pleasant View Road  |  Middleton, WI 53562

Phone:

 1-888-967-5224  |  

Website:

 workaci.com

Page 3

Version: 5.0

I0000345

WIRING INSTRUCTIONS 

(Continued)

Note:

 ACI’s stats are not two-way communicating. Communication jacks allow the user to query and 

modify operating parameters of the local room terminal unit from the portable operator’s terminal 
(laptop). This feature allows a technician to commission or service the controller via the sensor.

TEMPERATURE DISPLAY ADJUSTMENTS

The Temperature Display may be adjusted by adjusting the ZERO or OFFSET Potentiometer (P2) as shown on 
the above diagram. Adjust (P2) until the LCD Display reading matches your controller if necessary.

SETPOINT CONTROL

Adjust slider at bottom of housing for set point control. Slide to right to increase set point temperature. Slide to 
left to decrease temperature control. 

One
1/16” Allen screws (2 qty) / 1/16” Hex Driver
Short Thermistor (Default); Field (Jumper) Selectable 
“Dry Contact” Closure (Separate Input);
1.5 to 50 °C (35 to 122 °F) | -40 to 65 °C (-40 to 149 °F)
10 to 95% RH, non-condensing
Screw Terminal Blocks (Non-Polarity Sensitive)
16 (1.31 mm²) to 26 AWG (0.129 mm²) 
0.5 Nm (Minimum); 0.6 Nm (Maximum)

 “R” Enclosure:

 ABS Plastic | Beige UL94-HB 

A/AN (Type III):

 10 KΩ nominal

+/- 0.2 °C (+/- 0.36 °F)

SENSOR NON-SPECIFIC INFORMATION

 

Number Temperature Sensing Points:
Housing Screw Size / Drive Size:
Override Option:

Operating | Storage Temperature Range:
Operating Humidity Range:
Connections / Wire Size:

Terminal Block Torque Rating:
Enclosure Material | Color: 
Sensor Output @ 25 °C (77 °F):
Accuracy @ 0-70 °C (32 - 158 °F):

Summary of Contents for ROOM Series

Page 1: ...gisters diffusers vents and windows Avoid confined areas such as shelves closed cabinets closets and behind curtains Eliminate and seal all wall and conduit penetrations Air migration from wall cavities may alter temperature readings A thermally insulated backing should be used when fitting to solid walls concrete steel etc ACI part A ROOM FOAM PAD Do not install near heat sources eg lamps radiato...

Page 2: ...low and high voltage wires 24 120 230 VAC All ACI thermistors are non position sensitive All thermistor type room units are supplied with a two pole terminal block The number of wires needed depends on the application All wiring must comply with all local and National Electric Codes Note When using a shielded cable be sure to connect only 1 end of the shield to ground at the controller Connecting ...

Page 3: ...MPERATURE DISPLAY ADJUSTMENTS The Temperature Display may be adjusted by adjusting the ZERO or OFFSET Potentiometer P2 as shown on the above diagram Adjust P2 until the LCD Display reading matches your controller if necessary SETPOINT CONTROL Adjust slider at bottom of housing for set point control Slide to right to increase set point temperature Slide to left to decrease temperature control One 1...

Page 4: ...ty Verify sensor or wires are not shorted together Verify controller is setup for correct sensor curve Disconnectwiresfromsensorterminalblock tightenterminalblock screwsdown andtakearesistance ohm readingwithamultimeter Compare the resistance reading to theTemperatureVs Resistance Curves online http www workaci com content thermistor curves 0 Verify proper mounting location to confirm no external ...

Reviews: