PRODUCT SPECIFICATIONS

24 VAC, 60 Hz (Full wave rectified)

300 mA

Screw Terminal Blocks

16 AWG (1.31 mm2) to 26 AWG (0.129 mm2) 

0.37 ft-lb (0.5 Nm) Nominal

32 to 140ºF (0 to 60ºC)

30 to 50% RH, Noncondensing

-4 to 176ºF (-20 to 80ºC), 70% RH

IEEE 802.15.4-2003/2006

900 MHz, Operating Frequency 10 channels between 902 – 928 MHz

Transmitter Power:

 11 dBm  |  

Receiver Sensitivity

: -11 dBm 

200 – 300 ft horizontally depending on building type and constructions, and typically 

one floor above and below the transceiver vertically  

 

 

Two (2) SPDT Pilot Duty Relays, Dry Contact

1.0A, 30 VDC @ 104ºF (40ºC), 0.5A, 125 VAC @ 104ºF (40ºC) Resistive

Mechanical: 

5,000,000 operations minimum @ 36K operations/hr

Electrical: 

100,000 operations minimum (under rated load @ 1.8K operations/hr)

(1) SPDT, Dry contact relay, 1.0A, 30 VDC @ 104ºF (40ºC), 0.5A, 125 VAC @ 104ºF (40ºC) 

Resistive

Included; Data registers need to be configured prior to use

• Laptop with Windows 98, XP, Vista, Windows 7 or Windows 10, Ethernet Port, and 10 GB 

memory

• Direct connection from PC to RM2402D using CK2432D serial to RJ11 Programming 

Cable

• USB to Serial Adapter (Not provided by ACI)

• IP Address of PC must have static address of 192.168.0.2 or above

Standard:

 ABS Plastic  |  UL94-5VA  |  

NEMA 4X:

 Polycarbonate Plastic  |  UL94 HB 

Supply Voltage:

Supply Current:

Connections:

Wire Size:

Terminal Block Torque Rating:

Operating Temperature Range:

Operating Humidity Range:

Storage Temperature Range:

Data Protocol:

RF Characteristics:

Transmission Distance:

Digital Outputs:

Contact Rating:

Relay Durability:

Lost Signal Alarm:

Configuration Software:

System Requirements:

Enclosure Material  |  Flammability 

Rating:

Automation Components, Inc.

2305 Pleasant View Road  |  Middleton, WI 53562

Phone:

 1-888-967-5224  |  

Website:

 workaci.com

Page 4

Version: 6.0

I0000692

Summary of Contents for RM2402D Series

Page 1: ...tor status or alarms and is compatible with any DDC controller that accepts a dry contact closure The maximum radio transmission distance is dependent on the building type In a typical commercial building with steel I Beam construction concrete floors with reinforcing rod and metal stud walls it can be expected that transmissions will penetrate horizontally approximately 200 300 feet of floor wall...

Page 2: ... you use an isolated UL listed Class 2 transformer when powering the unit with 24 VAC Failure to wire the devices with the correct polarity when sharing transformers may result in damage to any device powered by the shared transformer Observe polarity when connecting analog outputs to the controller inputs WIRING Connect 24VAC 60Hz to the TB1 terminals using 16 26 twisted pair wire Check all conne...

Page 3: ...ci com Page 3 Version 6 0 I0000692 6 75 171 5mm 3 5 88 9mm Ø0 190 4 PLCS 7 285 185mm 6 12 155 5mm 4 72 119 89mm 2 367 60 12mm TOP TOP VIEW SIDE VIEW Antenna Active LED Data Link LED 24VAC RJ Connector for Device Configuration 6 73 171mm 4 76 121mm 6 26 159mm 3 58 91mm 6 73 171mm Ø0 18 Mounting Holes 2 17 55 1mm TOP VIEW SIDE VIEW TOP 24VAC ...

Page 4: ...VAC 104ºF 40ºC Resistive Mechanical 5 000 000 operations minimum 36K operations hr Electrical 100 000 operations minimum under rated load 1 8K operations hr 1 SPDT Dry contact relay 1 0A 30 VDC 104ºF 40ºC 0 5A 125 VAC 104ºF 40ºC Resistive Included Data registers need to be configured prior to use Laptop with Windows 98 XP Vista Windows 7 or Windows 10 Ethernet Port and 10 GB memory Direct connecti...

Reviews: