WIRING INSTRUCTIONS 

Shielded cable with 14 to 24AWG conductors is 
recommended. Use the Wiring Connections table 
below to determine the proper wiring for your 
application. Insert the wire into the depluggable 
terminal block sockets and tighten the screws. In 
some circumstances, it may be easier to remove 
the terminal blocks while connecting the wires. 
Refer to 

TABLE 1

 (below).

All wiring must comply with local and National 
Electric Codes. 

Note:

 When using a shielded cable, be sure to 

connect only (1) end of the shield to ground 
at the controller. Connecting both ends of the 
shield to ground may cause a ground loop. When 
removing the shield from the sensor end, make 
sure to properly trim the shield to prevent any 
chance of shorting. 

OUTPUT SIGNAL

SUPPLY VOLTAGE

WIRE CONNECTIONS

0-5/10VDC

AC/DC

VIN

GND

OUT

4-20mA

AC

VIN

GND

OUT

4-20mA

DC

VIN

-----

OUT

Summary of Contents for MLP2 Series

Page 1: ...m 1 354i 1 354in n Using the two 8 x 3 4 self drilling mounting screws supplied by ACI mount the unit vertically with the brass fittings pointing towards the ground Attach the unit to the mounting surface using the two mounting openings located on the top and bottom flanges This ensures that any condensation that may form in the tubing does not have an effect on the pressure sensor If mounting the...

Page 2: ...ws In some circumstances it may be easier to remove the terminal blocks while connecting the wires Refer to TABLE 1 below All wiring must comply with local and National Electric Codes Note When using a shielded cable be sure to connect only 1 end of the shield to ground at the controller Connecting both ends of the shield to ground may cause a ground loop When removing the shield from the sensor e...

Page 3: ... piece of tubing can be connected between the HI and LO brass fittings to neutralize any external pressure effects Press and hold the Zero button for 5 seconds MLP2 will enter zero mode AFTER push button is released The Zero adjustment should only be performed with no pressure applied CALIBRATION MLP2 utilizes a digital pot for Span calibration and is factory set There is no Span potentiometer for...

Page 4: ...pdate Rate 0 5 Second intervals Zero Function Pushbutton Zero Function Recommended after 15 minutes warm up Proof Pressure Burst Pressure Ranges 1 wc 248 84 Pa Proof 270 wc 67 2 kPa Burst 415 wc 103 3kPa Ranges 1 wc 0 2488 kPa to 10 wc 2 488 kPa Proof 350 wc 87 12 kPa Burst 550 wc 136 9kPa Ranges 10 wc 2 488 kPa to 40 wc 9953 6 kPa Proof 562 wc 140 kPa Burst 1004 7 wc 250 kPa Media Types Dry air o...

Reviews: