background image

Automation Components, Inc.

2305 Pleasant View Road  |  Middleton, WI 53562

Phone:

 1-888-967-5224  |  

Website:

 workaci.com

Page 1

Version: 6.0

I0000705

EX2432D OUTPUT EXPANSION
MODULE FOR RM2432 RECEIVER

Installation & Operation Instructions

Phone:

 1-888-967-5224

Website:

 workaci.com

PRECAUTIONS
SENSORS, REPEATERS AND RECEIVERS SHOULD NOT BE INSTALLED IN THE FOLLOWING AREAS:
• INSIDE METAL ENCLOSURE / PANEL 
• INSIDE OR IMMEDIATELY NEXT TO ELEVATOR SHAFT / ELEVATOR BANKS
• IN FRONT OF OR IMMEDIATELY NEXT TO LARGE TREES OR LARGE BODY OF WATER
TRANSMISSION DISTANCE AND PERFORMANCE WILL BE DRASTICALLY REDUCED.

CAUTION:
DO NOT USE THIS PRODUCT IN ANY SAFETY RELATED APPLICATIONS WHERE HUMAN LIFE 
MAY BE AFFECTED.

  

 

!

 

!

CAUTION:
DO NOT USE THIS PRODUCT IN ANY SAFETY RELATED APPLICATIONS
WHERE HUMAN LIFE MAY BE AFFECTED.

GENERAL INFORMATION

T

The EX2432D is an expander module designed for use with the RM2432D receiver to add sensors to a system.  The 

EX2432D has four (4) analog and four (4) digital outputs and is powered by the RM2432D.  A maximum of two (2) 
EX2432D expander modules can be added to the RM2432D for a total of 12 analog (0-5 VDC, 0-10 VDC) and 12 
digital (dry contact) outputs.

MOUNTING INSTRUCTIONS

Mount the EX2432D Modules next to the RM2432D receiver using four #8 screws (mounting dimensions 
see 

Figure 1

). The RM2432D/EX2432D system should be located as close to the external controller as 

possible. The maximum wiring distance for the analog outputs is 100 ft. 

CONFIGURATION

The sensors need to be configured using the configuration program (included), a laptop, and the CK2432D 
programing cable. Refer to the RM2432D Configuration Manual for instruction. The CK2432D 
programming cable is required. A serial to USB adapter might be needed. 

WIRING INSTRUCTIONS

CAUTION:
Observe polarity when connecting analog outputs to the controller inputs.  

The EX2432D is powered from the RM2432D using the terminals marked A, B, C and  on both devices with 
the maximum wire length of 2’. ACI recommends 16-22 AWG shielded cable or twisted pair wire between 
the RM2432D and the EX2432D. If a second EX2432D is needed, daisy chain from the first EX2432D.

Select 0-10VDC or 0-5VDC output by moving J4 jumper (see 

Figure 1

 on RM2432D Installation 

Instruction). 

Using the RM2432D configuration information, connect the analog and digital outputs to the appropriate 
control input terminals on the controller using 16-26 AWG wire. The controller input connecting to the 
RM2432D should have a minimum analog input resistance of 20K Ohms. Do no jumper commons for relay 
outputs.

Note:

 Always connect the Low Battery (or Lost Sensor) relay contact output (see 

Figure 1

) to the 

appropriate alarm input on the controller.

Summary of Contents for EX2432D

Page 1: ...0 ft CONFIGURATION The sensors need to be configured using the configuration program included a laptop and the CK2432D programing cable Refer to the RM2432D Configuration Manual for instruction The CK2432D programming cable is required A serial to USB adapter might be needed WIRING INSTRUCTIONS CAUTION Observe polarity when connecting analog outputs to the controller inputs The EX2432D is powered ...

Page 2: ... SHAFT ELEVATOR BANKS IN FRONT OF OR IMMEDIATELY NEXT TO LARGE TREES OR LARGE BODY OF WATER TRANSMISSION DISTANCE AND PERFORMANCE WILL BE DRASTICALLY REDUCED CAUTION DO NOT USE THIS PRODUCT IN ANY SAFETY RELATED APPLICATIONS WHERE HUMAN LIFE MAY BE AFFECTED FIGURE 1 ENCLOSURE DIMENSIONS 8 26 209 8mm 8 78 223mm 3 5 88 9mm 7 625 184 5mm 4 72 119 89mm TOP VIEW TOP SIDE VIEW 2 365 60 1mm 8 26 209 8mm ...

Page 3: ... Components Inc 2305 Pleasant View Road Middleton WI 53562 Phone 1 888 967 5224 Website workaci com Page 3 Version 6 0 I0000705 SIDE VIEW TOP VIEW TOP 5 74 145 8mm 8 74 222mm 8 24 209 3mm 4 56 115 8mm Ø0 18 Mounting Holes 8 74 222mm 2 96 75 2mm NEMA 4x ...

Page 4: ... Terminal Blocks 16 AWG 1 31 mm2 to 26 AWG 0 129 mm2 0 37 ft lb 0 5 Nm Nominal 32 to 122ºF 0 to 50ºC 30 to 50 RH Noncondensing 4 to 176ºF 20 to 80ºC 70 RH IEEE 802 15 4 2003 2006 900 MHz Operating Frequency 10 channels between 902 928 MHz Transmitter Power 11 dBm Receiver Sensitivity 11 dBm 200 300 ft horizontally depending on building type and constructions and typically one floor above and below...