PRECAUTIONS 

(Continued)

• If the 24 VDC or 24VAC power is shared with devices 
that have coils such as relays, solenoids, or other 
inductors, each coil must have an MOV, DC/AC Transorb, 
Transient Voltage Suppressor (ACI Part: 142583), or 
diode placed across the coil or inductor. The cathode, or 
banded side of the DC Transorb or diode, connects to 
the positive side of the power supply. Without these 
snubbers, coils produce very large voltage spikes when 
de-energizing that can cause malfunction or 
destruction of electronic circuits.

MOUNTING INSTRUCTIONS

For optimal readings, follow these tips:  

Mount in shade on North side of the structure to 

minimize sun exposure.  In the Southern hemisphere 
the South side of the building is where the sensor 
should be mounted.

Mount at least 1’-2’ (0.3-0.6 m) below eave to prevent 

thermal radiation from affecting performance – see 
FIGURE 2.

Mount at least 4’ (1.22 m) above ground to prevent 

thermal radiation rising up affecting performance.

The plastic tube that houses the sensor must be 

pointed down to avoid debris, water, or ice 
potentially affecting sensor performance.

Avoid mounting to chimney walls, above windows, 

above vents, near doors, or dampers.

Remove the cover from the housing by turrning counter 
clockwise. Attach the base directly to the wall.  Mounting 
holes are located at the  bottom of the housing – see 

FIGURE 1

.  Drill pilot holes for the mounting screws. Use the 

enclosure mounting holes as a guide, or use the dimensions 
listed above to measure out.  

Install the PG11 watertight fitting supplied with the sensor if not 
using conduit.  The outer knockout ring (PG 11/16) on housing 
should not be removed when using a ½” NPT conduit fitting. Take 
care when mounting.  Sensors should not be placed in 
direct sunlight, or any other potential heating or cooling sources that could affect temperature being sensed.

Refer to the wiring instructions below to make necessary connections. After wiring, tighten the -EH cover clockwise onto the enclosure. 
Confirm gasketed cover is fastened securely in order to prevent any moisture being introduced into housing.  

Version 1.0

I0000806

FIGURE 2: 

MOUNTING LOCATIONS

FIGURE 3: 

LAYOUT

TERMINAL BLOCKS

RESET BUTTON

DIP SWITCH

END OF LINE 

TERMINATION

LED

POWER

ADDRESS

BAUD

D+

EN DIS

BACNET

V

D-

GN

4

6

2

3 6

1 8 4 2 1 4 2 1

Recommended 1-2 ft 

(0.3-0.6 m) Below Eave

Install Sensor

Downward

Roof

Ground

TABLE 1: 

WIRING CONNECTIONS

TERMINAL BLOCKS

+V
GN
D-
D+

CONNECTIONS

Power Supply Positive 12-36VDC / 24 VAC
Power Supply Common or Ground
EIA-485 Data Negative
EIA-485 Data Positive