aci BACnet AVERAGING Series Installation & Operation Instructions Download Page 1

Automation Components, Inc.

2305 Pleasant View Road  |  Middleton, WI 53562

Phone:

 1-888-967-5224  |  

Website:

 workaci.com

Page 1

FIGURE 1: 

ENCLOSURE 

DIMENSIONS

BACnet / Modbus AVERAGING SERIES

Installation & Operation Instructions

Phone:

 1-888-967-5224

Website:

 workaci.com

GENERAL INFORMATION

The BACnet MS/TP / Modbus RTU Averaging Series 
sensor is designed for use with electronic controllers 
in commercial heating and cooling building manage-
ment systems.  The ACI BACnet MS/TP / Modbus RTU 
Averaging Series sensor monitor the average 
temperature in commercial HVAC ductwork and 
provides a better average temperature of the air 
inside the duct compared to a single point duct 
sensor.  Averaging sensors are sold in either Copper 
or Flexible Averaging variations.  The Copper 
Averaging sensors include a continuous sensing 
element, which covers the entire length of the probe.  
The Flexible Averaging sensor has either 4 or 9 
sensing points depending on the length.  It uses 
BACnet MS/TP or Modbus for RTU for physical 
connection to a BAS or controller, has dip switches to 
set addresses and baud rate, parity and stop bits 
(Modbus RTU only), and has on board end-of-line 
termination. There is no analog output.

WIRING INSTRUCTIONS

The BACnet MS/TP /Modbus RTU Averaging Series 
temperature sensor has a depluggable terminal 
block located on the front of the PCB. For ease of 
wiring, we recommend removing the block, wiring, 
and reattaching before mounting. 16 to 22 AWG 
two conductor shielded cable is recommended for 
powering the sensors. 

ACI recommends using Belden 3105 or compatible 
cable for RS-485 communication wiring. This wire has 
120 ohm input impendence. The terminal blocks 
allow for (1) or (2) wires to be connected in each 
position for daisy chaining. Daisy chain the RS-485 
wiring and do not use “Star” or “T” wiring. Avoid 
running communication wires next to AC line 
voltage wires. These can be sources of noise that can 
affect signal quality.

3.60"

(91.44 mm)

2.25"

(57.15 mm)

4.79"

(121.55 mm)

2.35"

(59.80 mm)

PRECAUTIONS
•  Remove power before wiring. Never 

connect or disconnect wiring with power 
applied.

•  It is recommended you use an isolated 

UL-listed class 2 transformer when powering 
the unit with 24 VAC. Failure to wire the 
devices with the correct polarity when 
sharing transformers may result in damage 
to any device powered by the shared 
transformer. 

• If the 24 VDC or 24VAC power is shared with 

devices that have coils such as relays, 
solenoids, or other inductors, each coil must 
have an MOV, DC/AC Transorb, Transient 
Voltage Suppressor (ACI Part: 142583), or 
diode placed across the coil or inductor. The 
cathode, or banded side of the DC Transorb or 
diode, connects to the positive side of the 
power supply. Without these snubbers, coils 
produce very large voltage spikes when 
de-energizing that can cause malfunction or 
destruction of electronic circuits.

MOUNTING INSTRUCTIONS

Drill a 3/8" (9.53 mm) hole in the duct. Gently uncoil 
the copper tubing and insert the averaging 
element through the hole until the foam pad is 
tight to the duct. The sensor should then be strung 
in a criss-cross pattern throughout the duct using 
the mounting clips provided - see 

FIGURE 5 

(P.3)

.

Use a pattern that covers the greatest surface area 
of the duct to ensure that there is no stratification. 
When bending the copper tubing, be careful that 
you use a gradual bend and that you 

DO NOT 

kink 

the copper tubing. Bends should be a minimum of 
2” (50.8 mm). Each unit includes nylon wire ties 
and mounts for mounting. Optional copper 
capillary (ACI Item #

130525) 

or universal plastic 

mounting clips (ACI Item #

145421

) can be 

ordered. Plastic mounting clips will help insulate 
the copper sensing element from the metal duct. 
The capillary clips help avoid kinks when bending. 
When using Flexible averaging, do not cover the 
heatshrink that is located throughout the sensor 
(sensing points).

Drill pilot holes for the (2) mounting screws. Use the enclosure flange as a guide, or use the 
dimensions listed below to measure out. Now fasten and insert (2) screws #8 x 3/4" TEK (provided and 
recommended) through the mounting holes in the flange and tighten until the unit is held firmly to 
the duct. Make sure the foam pad is tight to the duct to eliminate any possible air leaks.

For optimal temperature measurement, follow these tips:  

Mount coil horizontal for vertical stratification.

Mount coil vertical for horizontal stratification.

The sensor must be spread evenly over the full duct.

The entire length of the sensor coil must be installed completely inside the duct. Do not have any part of 
the sensor exposed to exterior air. 

When installing the sensor near air-handling units, place the sensor downstream from the fan discharge. 
The stratified airstream will be more uniform across the duct cross-section. If the air is not well-mixed, the 
reading may be inaccurate.

If UV Lights are installed in duct, do not use Flexible Averaging. There is no UV protectant on outer cable 
jacket. Copper averaging must be used in this situation.

FIGURE 2: 

LAYOUT

DIP SWIT

CH

BAU
D

ADDRESS

OFF

ON

PA

R

SW4

BAC

NET

MOD

BUS

RESET

BUTTON

END OF LINE

TERMINATION

LED

EN

DIS

D+

D-

GN

V

64

32

16

8

4

2

1

4

2

1

1

ON

1

2

2
3
4

TERMINAL

BLOCKS

Version: 2.0

I0000932

Summary of Contents for BACnet AVERAGING Series

Page 1: ...sical connection to a BAS or controller has dip switches to set addresses and baud rate parity and stop bits Modbus RTU only and has on board end of line termination There is no analog output WIRING INSTRUCTIONS The BACnet MS TP Modbus RTU Averaging Series temperature sensor has a depluggable terminal block located on the front of the PCB For ease of wiring we recommend removing the block wiring a...

Page 2: ...S Drill a 3 8 9 53 mm hole in the duct Gently uncoil the copper tubing and insert the averaging element through the hole until the foam pad is tight to the duct The sensor should then be strung in a criss cross pattern throughout the duct using the mounting clips provided see FIGURE 5 P 3 Use a pattern that covers the greatest surface area of the duct to ensure that there is no stratification When...

Page 3: ...he reading may be inaccurate If UV Lights are installed in duct do not use Flexible Averaging There is no UV protectant on outer cable jacket Copper averaging must be used in this situation BACnet MS TP and Modbus RTU INTERFACE The BACnet Master Slave Token Passing MS TP and Modbus Remote Terminal Unit RTU data link protocol uses EIA 485 as a two wire daisy chain network A branch is a discrete cha...

Page 4: ...te Auto Baud not available for Modbus RTU DIP 1 PAR2 only applies to Modbus DIP 2 PAR1 only applies to Modbus DIP 3 OPEN For Future Use DIP 4 OFF is BACNET ON is MODBUS BAUD RATE SELECTION By default BACnet Protocol and Auto Baud is factory set If the sensor is field adjusted for Modbus RTU the baud rate should be selected at this time to match the Master configuration If Modbus RTU protocol is se...

Page 5: ...et DEVICE INSTANCE The Device Instance by default is 1035000 plus the Address For example an Address of 21 results in a default address of 1035021 This can be changed once the device is connected to the network but each device instance must be unique within the network not just this segment DEVICE NAME By default the device name is based on the type of device and the address The device name can be...

Page 6: ...ation exchange Parity and stop bit selection is performed via the SW4 switch located on the board Dipswtiches 1 and 2 are adjusted to select the parity and stop bits see TABLE 7 Where 0 is OFF and 1 is ON If BACnet protocol is selected these dipswitches are irrelevant TEST MODE Modbus RTU There are 5 data values in test mode Coil 1001 Holding Registers HR 1001 and 1002 and the Input Registers IR 0...

Page 7: ... 02 00 000 90 Sensors Present Reserved Temperature Sensor Value RH Sensor Value Temperature Range Min Temperature Range Max RH Range Min RH Range Max Unsigned Integer Test Value Signed Integer Test Value Test String Test Value Serial Number Firmware Version 0 1 2 3 2000 2001 2002 2003 9000 9001 9002 Thru 9005 9006 Thru 9009 9010 Thru 9015 1 2 3 Value Units 62 Degrees Celsius 63 Degrees Kelvin 64 D...

Page 8: ...17 Thru 9048 9049 Thru 9080 Device Name Device Location and Device Description are user settable character strings Null terminated that can be used to allow for system customization and device identification For example Device Name Modbus 9001 thru 9016 could be set to a system ID S2253 Device Location Modbus 9017 thru 9048 could be set to Building 5 Floor 2 Duct 3 Device Description Modbus 9049 t...

Reviews: