 Calibration of Adjustable Trip Point 

The adjustable current switch has an operating range of 0-150 Amps.  

Do not exceed!

  The adjustable current switch comes with 

its fifteen-turn adjustment potentiometer set to the 100 Amp trip point position.  The adjustable current switch can be used to 
monitor Under Load, Normal Load, and Over Load conditions, depending on how it’s set.  The procedure below is for the Normal 
load condition for part numbers A/MCS-A & A/MSCS-A. 

 
 

 Normal Loads 

With current flowing through the aperture of the A/MCS-A and A/MSCS-A current switches, first verify that the Blue LED is on.  
If the Blue LED is on, now slowly adjust the potentiometer clockwise until the Red LED just turns on and stop immediately.  This 
will set the trip point at your normal operating load current.  If the RED LED is on after initial power up, this means that you will 
need to slowly adjust the potentiometer counter-clockwise until the Blue LED turns on and then slowly adjust the potentiometer 
clockwise until the Red LED just turns on and stop immediately.  The adjustable current switch is now tripped.  Now verify the 
output with an Ohmmeter to verify that the contacts of the switch are approximately 0.200 Ohms.  The adjustable current switch 
Hysteresis (Dead Band) is typically 10% of the trip point. 
 

 

 Troubleshooting 

 

Problem

 

Solution

 

Red LED is on but the current switch didn’t activate 

Disconnect the wires from the current switch output.  Measure the 
resistance across the contacts with an Ohmmeter.  

See Figure 7

 below 

for resistance readings for a good unit. 

Red LED didn’t turn on and the current switch didn’t 
activate 
 

Verify that the conductor you are monitoring is above the adjustable 
trip point.  If the sensor is monitoring less than the adjustable trip point  

See Figure 3

 on Page 1. 

Sensor doesn't switch at all, regardless of current 
level.  

Adjustment potentiometer is probably set to its maximum or minimum 
position.  Turn the Pot counter-clockwise all the way and verify if the 
LED switches from Red to Blue. 

 
 

ACI Model # 

Resistance if switch open 

Resistance if switch closed 

A/MCS-A 

Greater than 1 Meg ohms 

Approximately 0.2 ohms 

A/MSCS-A 

Greater than 1 Meg ohms 

Approximately 0.2 ohms 

Figure 7 

 

 WEEE Directive 

At the end of their useful life the packaging and product should be disposed of via a suitable recycling centre.  Do not dispose of 
with household waste.  Do not burn. 
 
 

                                                    

              

           