WARRANTY
The ACI Room Series temperature sensors are covered by ACI’s Five (5) Year Limited Warranty, which is located in
the front of ACI’S SENSORS & TRANSMITTERS CATALOG or can be found on ACI’s website: www.workaci.com.
W.E.E.E. DIRECTIVE
At the end of their useful life the packaging and product should be disposed of via a suitable recycling
centre. Do not dispose of with household waste. Do not burn.
PRODUCT SPECIFICATIONS
TROUBLESHOOTING
Automation Components, Inc.
2305 Pleasant View Road | Middleton, WI 53562
Phone:
1-888-967-5224 |
Website:
workaci.com
Page 4
Version: 4.0
I0000195
2 Wire, 4-20 mA current loop
+7 VDC for LCD Display
+/- 0.5% of span
3 ½ Digit LCD (-199.9 to 199.9) | F (Fahrenheit), C (Centigrade) or No Descriptor
Dry Contact “N/O” Contact | Minimum: 10 uA @ 1 VDC; Maximum: 50 mA @ 24 VDC
0.1 Ohms maximum | 100,000 Cycles
+/- 10% | 4-20 mA: 4 mA (Far Left) | 20 mA Far Right (DA- Direct Acting (Default)
20 mA (Far Left / 4 mA Far Right (RA- Reverse Acting (Optional)
+24 VDC +/-10%
35 to 131ºF (1.5 to 55ºC)
-40 to 160ºF (-40 to 71ºC)
5 to 95% non-condensing
Screw Terminal Blocks | 16 (1.31 mm2) to 26 AWG (0.129 mm2)
0.5 Nm (Minimum); 0.6 Nm (Maximum)
SENSOR NON-SPECIFIC INFORMATION
Input:
Maximum Voltage Drop:
Display Accuracy:
LCD Resolution | Descriptors:
Override Contact Type | Contact
Ratings:
Override Contact Resistance | Life
Expectancy:
Set Point Accuracy:
Setpoint Supply Voltage: (4 to 20 mA
Only):
Operating Temperature Range:
Storage Temperature Range:
Operating Relative Humidity Range:
Connections | Wire Size:
Terminal Block Torque Rating:
PROBLEM
Display Not Working
SOLUTION(S)
•
Wires not connected correctly, no signal from transmitter or
common ground. Also make sure the display is plugged in correctly
after mounting.
TEMPERATURE DISPLAY ADJUSTMENTS
The Temperature Display may be adjusted by adjusting the ZERO Potentiometer as shown on the above
diagram. Adjust zero pot until the LCD Display reading matches your sensor if necessary. Do not adjust the
SPAN pot.
SETPOINT CONTROL
Adjust slider at bottom of housing for set point control. Slide to right to increase set point temperature.
Slide to left to decrease temperature control. Units can be setup from factory for Direct Acting (resistance
increases when adjusted to right), or Reverse Acting (resistance decreases when adjusted to right).
OVERRIDE ADJUSTMENTS
Override will be set to Dry Contact.