background image

WARRANTY

The ACI Room Series temperature sensors are covered by ACI’s Five (5) Year Limited Warranty, which is located in 
the front of ACI’S SENSORS & TRANSMITTERS CATALOG or can be found on ACI’s website: www.workaci.com.

W.E.E.E. DIRECTIVE 

At the end of their useful life the packaging and product should be disposed of via a suitable recycling 
centre. Do not dispose of with household waste. Do not burn.

PRODUCT SPECIFICATIONS

TROUBLESHOOTING

Automation Components, Inc.

2305 Pleasant View Road  |  Middleton, WI 53562

Phone:

 1-888-967-5224  |  

Website:

 workaci.com

Page 4

Version: 4.0

I0000195

2 Wire, 4-20 mA current loop   
+7 VDC for LCD Display
+/- 0.5% of span
3 ½ Digit LCD (-199.9 to 199.9)  |  F (Fahrenheit), C (Centigrade) or No Descriptor
Dry Contact “N/O” Contact  |  Minimum: 10 uA @ 1 VDC; Maximum: 50 mA @ 24 VDC 

0.1 Ohms maximum  |  100,000 Cycles

+/- 10%  |  4-20 mA: 4 mA (Far Left)  |  20 mA Far Right (DA- Direct Acting (Default)
                                                    20 mA (Far Left / 4 mA Far Right (RA- Reverse Acting (Optional)
+24 VDC +/-10% 

35 to 131ºF (1.5 to 55ºC)
-40 to 160ºF (-40 to 71ºC)
5 to 95% non-condensing
Screw Terminal Blocks  |  16 (1.31 mm2) to 26 AWG (0.129 mm2)
0.5 Nm (Minimum); 0.6 Nm (Maximum)

SENSOR NON-SPECIFIC INFORMATION

 

Input: 
Maximum Voltage Drop:
Display Accuracy:
LCD Resolution  |  Descriptors:
Override Contact Type  |  Contact 
Ratings:
Override Contact Resistance  |  Life 
Expectancy:
Set Point Accuracy:

Setpoint Supply Voltage: (4 to 20 mA 
Only):
Operating Temperature Range:
Storage Temperature Range:
Operating Relative Humidity Range:
Connections  |  Wire Size:
Terminal Block Torque Rating:

PROBLEM

Display Not Working

SOLUTION(S)

Wires not connected correctly, no signal from transmitter or 

common ground. Also make sure the display is plugged in correctly 
after mounting.

TEMPERATURE DISPLAY ADJUSTMENTS

The Temperature Display may be adjusted by adjusting the ZERO  Potentiometer as shown on the above 

diagram. Adjust zero pot until the LCD Display reading matches your sensor if necessary. Do not adjust the 

SPAN pot. 

SETPOINT CONTROL

Adjust slider at bottom of housing for set point control. Slide to right to increase set point temperature. 

Slide to left to decrease temperature control. Units can be setup from factory for Direct Acting (resistance 

increases when adjusted to right), or Reverse Acting (resistance decreases when adjusted to right).

OVERRIDE ADJUSTMENTS

Override will be set to Dry Contact.

Summary of Contents for A/LCD-R-4-20MA

Page 1: ...ts are 48 60 1 2 1 5 m off the ground and at least 1 5 0 5 m from the adjacent wall The sensor should be mounted in an area where air circulation is well mixed and not blocked by obstructions see FIGURE 2 p 2 Note If mounting an LCD RS with setpoint you must mount to standard 2 x 4 junction box It cannot be surface mounted The set point PCB is located on back of enclosure see Figure 3 p 2 Refer to...

Page 2: ...KS SET located on back PCB SET located on back PCB O R O R CONNECTIONS 4 to 20 mA current loop input Input to Display from Transmitter or Controller Note If Set Point this wire will be factory installed 4 to 20 mA LCD current loop output to controller analog input 24VDC Supply Voltage 4 to 20 mA set point current loop output to controller analog input Note This wire will be factory installed into ...

Page 3: ...1 888 967 5224 Website workaci com Page 3 Version 4 0 I0000195 FIGURE 4 LAYOUT FIGURE 5 SETPOINT PCB FIGURE 6 WIRING ACI S GP PRESSURE SENSOR GP Sensor Automation Panel Power Supply 13 to 30 VDC Note The example below shows ACI s GP Pressure sensor wired to the A LCD R 4 20MA ...

Page 4: ... mm2 to 26 AWG 0 129 mm2 0 5 Nm Minimum 0 6 Nm Maximum SENSOR NON SPECIFIC INFORMATION Input Maximum Voltage Drop Display Accuracy LCD Resolution Descriptors Override Contact Type Contact Ratings Override Contact Resistance Life Expectancy Set Point Accuracy Setpoint Supply Voltage 4 to 20 mA Only Operating Temperature Range Storage Temperature Range Operating Relative Humidity Range Connections W...

Reviews: