 Wiring                                   

ACI recommends the use of a 2 conductor 16 to 22 AWG shielded cable,

copper wire only

 for all 4 to 20mA current sensor

installations.  A maximum wire length of less than 30 meters (98.4 feet) should be used between the A/CTA series current sensors 
and the Building Management System or controller. 

Note: When using a shielded cable, be sure to connect only (1) end of the 

shield to ground at the controller. Connecting both ends of the shield to ground may cause a ground loop.  

 When removing the 

shield from the sensor end, make sure to properly trim the shield so as to prevent any chance of shorting.  The current sensors 
terminals are polarity sensitive and represent a linear and proportional 4 to 20mA output signal.  The current sensors are available 
in either an Average or True RMS output version.  The recommended torque to be used on the terminal block connections is 0.67 
Nm or 5.93 in-lbs. The aperture (hole) size of the current sensor is 0.75” (1.90 cm) and will accept a maximum cable diameter of 
350 MCM’s.

 Operating Specifications

*Note: All current sensors are shipped from the factory with the jumper set in the high range.

** Note:  All -VFD models have True RMS outputs and should be used with Variable Frequency Drives.

Wiring Example

Supply

Power

 +12 to 30 VDC

4 to 20 mA

+

_

DC

_

+

Signal Input

+

Building Automation

GND (Shield)

System

Common

 Troubleshooting

Problem

Solution

No reading

- Confirm that you have +12 to 30VDC in series with the current sensor output
   terminals and the analog input of the control panel.
- Check the polarity of the circuit.
- Verify that the terminals are screwed down, wires are firmly in place.
- Disconnect the input to the control panel and then insert a current meter 
  (mA range) in series with the current sensor output to verify that the circuit is
   working properly.

Erratic readings

- Verify that the wires are terminated properly.
- Check that the +12 to 30VDC input is clean.  In areas of high RF interference,
   shielded cable may be necessary to stabilize signal.

Inaccurate readings

- If you suspect that the current sensor is not reading within the accuracy specifications, please 
contact the factory for assistance.

ACI Model #

Range

Jumper *

Max. Sensing 

Current Voltage

Max. Continuous 

Current.

Max. Current for

6 seconds

CE Compliance

A/CTA-5

0-5 Amps

None

600 VAC

100 Amps

125 Amps

Yes

A/CTA-50

0-10 Amps
0-20 Amps
0-50 Amps

Low

Middle

High

600 VAC

100 Amps
150 Amps
200 Amps

125 Amps
225 Amps
300 Amps

Yes

A/CTA-250

 0-100 Amps
 0-200 Amps
 0-250 Amps

Low

Middle

High

600 VAC

200 Amps
360 Amps
400 Amps

250 Amps
450 Amps
500 Amps

Yes

A/CTA-5-VFD **

0-5 Amps

None

600 VAC

60 Amps

100 Amps

No

A/CTA-50-VFD **

0-10 Amps

 0-20 Amps
 0-50 Amps

Low

Middle

High

600 VAC

60 Amps

100 Amps
160 Amps

80 Amps

200 Amps
300 Amps

No

A/CTA-250-VFD **

0-100 Amps

 0-200 Amps
 0-250 Amps

Low

Middle

High

600 VAC

160 Amps
320 Amps
400 Amps

200 Amps
400 Amps
500 Amps

No