FIGURE 1:

 DIMENSIONS

INTERFACE SERIES

Installation & Operation Instructions

6N1-ISO-STG

Phone:

 1-888-967-5224

Website:

 workaci.com

GENERAL INFORMATION

The 6N1-ISO-STG series is a microprocessor 

controlled interface designed to provide maximum 

flexibility with a minimum of cost. 

With a variety of standard inputs, the 6N1-ISO-STG 

provides the user with the ability to interface 

several devices to a single analog output. 

The 6N1-ISO-STG is a true staging device. It can be 

used in retrofit applications of interfacing a two or 

three stage thermostat to an SCR heater. It will 

convert 24VAC staged signals to a proportional 

analog output. The 6N1-ISO-STG offers two 

different modes. The first mode will check inputs 

sequentially high(#6) to low(#1), to set output 

percentage. The output percentage is based on 

highest input pressed, and ignores others. The 

other mode will check the total number of inputs, 

to set an output percentage. The output 

percentage is based on total number of active 

inputs.

Input ranges are jumper selectable and all modes 

and analog outputs are DIP switch selectable. The 

output signal is optically isolated from the input 

signals.  The power output terminal can be used for 

power if the inputs are only contact closures.

MOUNTING INSTRUCTIONS

The interface device can be mounted in any position. If circuit board slides out of snap track, a 

non-conductive “stop” may be required.  Use only fingers to remove board from snap track.  Slide out of 

snap track or push up against side of snap track and lift that side of the circuit board to remove. 

 Do not 

flex board or use tools.

WIRING INSTRUCTIONS

PRECAUTIONS

•     6N1-ISO-STG is powered by 24 VAC only.

•     Remove power before wiring. Never connect or disconnect wiring with power applied.

•    When using a shielded cable, ground the shield only at the controller end. Grounding both 

ends can cause a ground loop. 

•   This device needs to have its own Isolated Transformer. This transformer cannot be 

connected/or shared with any other device. It is recommended you use an isolated UL-listed class 

2 transformer. 

•    All wiring must comply with all local and National Electric Codes.

Note:

 ACI recommends to remove the pluggable terminal blocks to terminate wires first.  The terminal 

blocks can be removed using pliers.  Once wired, rotate the terminal block 90 Degrees so they are facing 

upward, and insert onto pins. This eliminates any wires getting pinched by the snaptrack.  See 

Figure 4

 (p.3).

4.00”

(101.6mm)

4.60” (116.84mm)

4.00”

(101.60mm)

3.88” (98.55mm)

0.70” 

(17.78mm)

Summary of Contents for 6N1-ISO-STG Series

Page 1: ...lectable The output signal is optically isolated from the input signals The power output terminal can be used for power if the inputs are only contact closures MOUNTING INSTRUCTIONS The interface device can be mounted in any position If circuit board slides out of snap track a non conductive stop may be required Use only fingers to remove board from snap track Slide out of snap track or push up ag...

Page 2: ...put 1 Input 1 Common Input 2 Input 2 Common Input 3 Input 3 Common Input 4 Common Input 5 Common Input 6 Common Input 4 Input 5 Input 6 Power Out Output Common Analog Output J1 J2 J11 J12 J21 J22 J31 J32 J41 J42 J51 J52 Jxx Analog Digital 10V 20V 20mA 5V Jxx 15V 24V J60 AI1 AI2 AI3 AI4 AI5 AI6 24 VAC PWR OUT PWR Status L2 6N1 ISO STG SW2 SW1 SIG OUT AI1 AI2 AI3 AI4 AI5 AI6 PWR OUT Thermostat PWR O...

Page 3: ... low 1 to set output percentage The output percentage is based on highest input pressed and ignores others This is based on the Input priority Example 1 4 Inputs used 0 10VDC output Activate Input 3 Output 7 5VDC 3 4 75 Example 2 6 Inputs used 0 10VDC output Activate Input 4 Output 6 6VDC 4 6 66 6 Fan Mode 2 Check total number of inputs to set output percentage The output percentage based on total...

Page 4: ...ED will blink at a rate of every two seconds 1 2 3 4 On WARRANTY The ACI 6N1 ISO STG Series is covered by ACI sTwo 2 Year LimitedWarranty which is located in the front of ACI S SENSORS TRANSMITTERS CATALOG or can be found on ACI s website www workaci com PRODUCT SPECIFICATIONS 24 VAC 10 50 60 Hz 255 mA maximum 24 VDC or 15 VDC Jumper Selectable 100 mA maximum 15 VDC 24 VDC or 24 VAC 10 100 000Ω 0 ...

Reviews: