GENERAL INFORMATION
The 6N1-ISO-STG series is a microprocessor
controlled interface designed to provide maximum
flexibility with a minimum of cost.
With a variety of standard inputs, the 6N1-ISO-STG
provides the user with the ability to interface
several devices to a single analog output.
The 6N1-ISO-STG is a true staging device. It can be
used in retrofit applications of interfacing a two or
three stage thermostat to an SCR heater. It will
convert 24VAC staged signals to a proportional
analog output. The 6N1-ISO-STG offers two
different modes. The first mode will check inputs
sequentially high(#6) to low(#1), to set output
percentage. The output percentage is based on
highest input pressed, and ignores others. The
other mode will check the total number of inputs,
to set an output percentage. The output
percentage is based on total number of active
inputs.
Input ranges are jumper selectable and all modes
and analog outputs are DIP switch selectable. The
output signal is optically isolated from the input
signals. The power output terminal can be used for
power if the inputs are only contact closures.
MOUNTING INSTRUCTIONS
The interface device can be mounted in any position. If circuit board slides out of snap track, a
non-conductive “stop” may be required. Use only fingers to remove board from snap track. Slide out of
snap track or push up against side of snap track and lift that side of the circuit board to remove.
Do not
flex board or use tools.
WIRING INSTRUCTIONS
PRECAUTIONS
• 6N1-ISO-STG is powered by 24 VAC only.
• Remove power before wiring. Never connect or disconnect wiring with power applied.
• When using a shielded cable, ground the shield only at the controller end. Grounding both
ends can cause a ground loop.
• This device needs to have its own Isolated Transformer. This transformer cannot be
connected/or shared with any other device. It is recommended you use an isolated UL-listed class
2 transformer.
• All wiring must comply with all local and National Electric Codes.
Note:
ACI recommends to remove the pluggable terminal blocks to terminate wires first. The terminal
blocks can be removed using pliers. Once wired, rotate the terminal block 90 Degrees so they are facing
upward, and insert onto pins. This eliminates any wires getting pinched by the snaptrack. See
Figure 4
(p.3).
4.00”
(101.6mm)
4.60” (116.84mm)
4.00”
(101.60mm)
3.88” (98.55mm)
0.70”
(17.78mm)