Acer S205F / S200F User’s Manual
24
2.4 Power Supply/Cooling Module
Installation
Install in the rear of the enclosure in positions 1 and 5.
Warning
Do not remove covers from the Power Supply/Cooling (PSU) module. Danger of electric shock
inside. Return the PSU to your supplier for repair.
2.4.1 Parts Check List
Power Supply/Cooling Modules of the following type:
• AC’ 450W PSU
2.4.2 AC Power Supply/Cooling Module Procedure
Important
If the cable strain relief wire tab is upside down it must be inverted by squeezing together the two
sides of the tab removing them from their mountings, inverting and then replacing them, as shown
in
1
Check for damage, especially to the rear connector on the supply.
Caution
Handle the module carefully and avoid damaging the connector pins. Do not install the module if
any pins appear to be bent.
2
With the PSU handle in the open position (
), slide the module into the enclosure (
).
Important
install the Power Supply/Cooling module in the right hand bay (Rear Bay 1) of the enclosure in an
“upside down* orientation.
3
Cam the module home by manually closing the PSU handle (
). A click should be heard as
the handle latches engage.
4
Connect the power supply cord to the power source and switch the power supply ON.
Figure 2–4
Inverting the Cable Strain Relief