Ace Heating Solutions Packaged Storage Water Heater Steam-to-Water System Operating And Maintenance Manual Download Page 22

2

2600 Emrick Blvd., B

et

hle

he

m, P

A

 18020-8010    www

.W

ar

re

nC

on

tr

ols

.c

om

Te

l: 800-922-0085  or  610-317-0800  F

ax: 610-317-2989

Description

W

arren Controls Series 2800 Precision Globe Control V

alves feature rugged bronze 

or stainless steel bodies with a variety of trim materials and port sizes. The equal

per

centage and linear plugs in the 2-way valves and linear plugs in the 3-way 

valves provide excellent modulating control of a wide variety of fluids for pressure,

temperature, level, and flow applications from –20 to 500ºF

. The Series 2800 is ideally

suited where value and long life are important objectives for applications including 

but not limited to the Chemical, Food & Beverage, General Ser

vice, Refining, and

Pharmaceutical Industries. 

SERIES:

2800

P

recision Globe 

Contr

ol V

alv

es

2830

Three-W

ay Mixing V

alve

Bronze Body

Fluoraz O-Ring 

Upper and Lower 

Body Seals in 

Stainless Steel 

Body V

alves

Guided Low-Friction

TFE V

-Ring Packing

Spring Loaded

Adjustable Graphite

Packing

2832

Three-W

ay

Diverting/Mixing V

alve

Bronze Body

2820

Two-W

ay Single Seat Unbalanced V

alve

The most commonly applied solution with ANSI Class IV and VI shut-off.

Sizes:

1/2, 3/4, 1, 1-1/4, 1-1/2, 2 inch

Body:

ANSI B16.15 Bronze 250LB Threaded (NPT) or

316 Stainless Steel 300LB Threaded (NPT)   

Trim:

EQ% or Linear

, 316 Stainless Steel, Alloy 6, TFE, PEEK, or

17-4 PH Hardened Stainless Steel  

Shut-off:

ANSI Class IV (Stainless Steel and Alloy 6 T

rim),

ANSI Class VI (TFE and PEEK T

rim)

Packing:

Guided Low-Friction TFE V

-Ring, Spring Loaded 

(+32 to 450°F), 

Adjustable Graphite Packing (+32 to 500°F)

Temperature:

+32 to 400°F (Bronze 250LB Threaded Body)

+32 to 450°F (316 Stainless Steel 300LB Threaded Body  

w/ TFE or PEEK T

rim) 

+32 to 500°F (316 Stainless Steel 300LB Threaded Body  

w/ Stainless Steel or Alloy 6 T

rim)

Rangeability:

50:1

2830

Three-W

ay Mixing V

alve

This valve has two inlets and one outlet, and is the simplest solution for mixing 

or bypass applications with ANSI Class IV shut-off. In normal applications the

inlet pressures are near equal and control is possible from 5% to 95% of travel

with inlet pressures up to 100 PSI.   

Sizes:

1/2, 3/4, 1, 1-1/4, 1-1/2, 2 inch

Body:

ANSI B16.15 Bronze 250LB Threaded (NPT) or

316 Stainless Steel 300LB Threaded (NPT)

Trim:

Linear

, 316 Stainless Steel 

Packing:

Guided Low-Friction TFE V

-Ring, Spring Loaded 

(+32 to 450°F),

Adjustable Graphite Packing (+32 to 500°F)   

Temperature:

+32 to 400°F (Bronze 250LB Threaded)

+32 to 500°F (316 Stainless Steel 300LB Threaded) 

Rangeability:

50:1

2832

Three-W

ay Diverting/Mixing V

alve

Designed as a diverting valve with one inlet and two outlets with ANSI Class III

shut-off. However

, flow can be reversed for mixing if this port configuration is

desirable. The difference between the upper port and lower port pressure must not

exceed 50 PSID.  

Sizes:

1, 1-1/2, 2 inch

Body:

ANSI B16.15 Bronze 250LB Threaded (NPT) or

316 Stainless Steel 300LB Threaded (NPT)

Tr

im

:

Linear

, Bronze (Bronze 250LB Threaded), or 

316 Stainless Steel (316 Stainless Steel 300LB Threaded) 

Packing:

Guided Low-Friction TFE V

-Ring, Spring Loaded

(+32 to 450°F),  

Adjustable Graphite Packing (+32 to 500°F)

O-Ring:

EPR (Bronze 250LB Threaded), 

Fluoraz 797 (316 Stainless Steel 300LB Threaded) 

Temperature:

+32 to 300°F (Bronze 250LB Threaded) 

+32 to 500°F (316 Stainless Steel 300LB Threaded)

Rangeability:

50:1

Temperature (F)

250 THD

300 THD

Bronze

SS

+32°

To

 150°F

400

720

150°

400

670

175°

392

645

200°

385

620

225°

375

605

250°

365

590

275°

350

575

300°

335

560

325°

317

548

350°

300

537

375°

275

526

400°

250

515

450°

-

497

500°

-

480

Bronze

50 PSID

316 Stainless Steel

100 PSID

TFE

100 PSID

PEEK

100 PSID

17-4 pH 

Hardened Steel

200 PSID

Alloy 6

300 PSID

Body S

tyle 

V

ersus Application

3

PS 2800 C 0305

For additional applic

at

ions

, and/or pr

oduc

ts

 c

all: 800-922-0085  or  vi

sit

: www

.W

ar

re

nC

on

tr

ols

.c

om

2-W

ay V

alves 

(Control of Liquids, Gases, and Steam)

3-W

ay V

alves 

(Control of Liquids)

Flo

w

Flo

w

Stem Do

wn

The v

alv

e closes

Stem Up

The v

alv

e opens

Stem Do

wn

The upper por

t opens

and the lo

w

er por

t closes

Upper P

o

rt

Common P

o

rt

Lo

w

er P

o

rt

Flo

w

Flo

w

Flo

w

Stem Up

The upper por

t closes

and the lo

w

er por

t opens

Upper P

o

rt

Common P

o

rt

Lo

w

er P

o

rt

Flo

w

Stem Do

wn

The upper por

t opens

and the lo

w

er por

t closes

Upper P

o

rt

Lo

w

er P

o

rt

Common P

o

rt

Stem Up

The upper por

t closes

and the lo

w

er por

t opens

Upper P

o

rt

Lo

w

er P

o

rt

Common P

o

rt

Flo

w

Flowing

Differential

Trim Materials

Pressure Limit

Body Pressure-T

emperature Ratings:

Pressure ratings are PSIG

For applications below 32º consult factor

y.

For applications above 375º, 300 THD Stainless Steel Body is recommended.

Summary of Contents for Packaged Storage Water Heater Steam-to-Water System

Page 1: ...Operating and Maintenance Manual Designed and Manufactured in Accordance with ASME Code Section VIII Photo shown may vary from actual model Packaged Storage Water Heater Steam to Water System U...

Page 2: ......

Page 3: ...ction 10 Before Start up Installation and hook up Start up Instruction Shut down instruction Safety features Operation of storage water heater 13 Trouble shooting Guide 14 Maintenance Instruction Remo...

Page 4: ...to control the heated water within the tank at the desired temperature This close control is accomplished by placing the temperature control element directly in the constant flow path of the circulat...

Page 5: ...tmospheric temperature H Serial number I Year built J Model number K Capacity L Square feet M Job number The Packaged Storage Water Heater Model Number P H G 72 10 G 2 1066 S A P Packaged H Type H Hor...

Page 6: ...anks Lifting Lug Water to Water Pneumatic Horizontal Water to Water Pneumatic Vertical Drain Storage Section Control Valve Press Temp Gauge Circulator Pump Boiler Water Supply Inlet Hot Water Outlet C...

Page 7: ...for domestic hot water the temperature control bulb will sense the drop in water temperature The temperature bulb sends a signal to the control valve to open and allow steam or hot boiler water into t...

Page 8: ...h all federal state and local codes as well as meet good industry practices as shown in publications issued by ASME AGA UL ASHRAE ABMA etc Placement The storage heater was either fabricated as a verti...

Page 9: ...each stud bolt and nut generously with penetrating oil before re torque Gasket thickness before compression All partition gaskets are in width before compression All gaskets expand twice their width a...

Page 10: ...wired according to the wiring diagram Verify the electrical supply using a voltmeter The voltage tie in leads are indicated on the wiring diagram This unit contains sensitive control components and sh...

Page 11: ...hook up condensate return to boiler condensate return tank Pipe size to correspond to opening size provided This pipe must run horizontal or pitch gradually to condensate tank with condensate level t...

Page 12: ...he circulator pump is running Please refer to the pump instruction manual for details 9 Manually open the main steam shut off valve upstream of the control valve and SLOWLY allow steam to pass through...

Page 13: ...steam control valve may require adjustment to set to desired tank temperature If the tank does not get hot enough the steam valve should be adjusted screwed in to a higher number If the tank temperatu...

Page 14: ...the setting of the pilot controller and adjust the hand wheel as necessary 2 Confirm steam supply pressure to the control valve meets that specified in the list of materials Check for a clogged strain...

Page 15: ...h or vacuum cleaner 8 Inspect anodes on glass lined tanks Replace anodes if 5 8 or less in diameter Failure to maintain anodes will void warranty Keep all records of anode inspection and replacement f...

Page 16: ...thin metal The bundle therefore should rest on parts designed to carry it i e on the tube sheets baffles or support plates For withdrawing tube bundles from the tank the use of steel eye bolts which a...

Page 17: ...and accept the product when received as conforming to their purchase order specifications and approved drawings All claims for non conformance errors shortages etc must be made within 10 days after re...

Page 18: ...boiler com mail ajaxboiler com February 2007 ACE Heating Solutions LLC 2701 S HARBOR BLVD SANTA ANA CA 92704 PHONE 714 540 2230 FAX 714 540 2239 www aceheatingllc com Ace Heating Solutions LLC Novembe...

Page 19: ...anta Ana California 92704 United States Tel 714 437 9050 Fax 714 437 9060 http www ajaxboiler com mail ajaxboiler com ACE Heating Solutions LLC 2701 S HARBOR BLVD SANTA ANA CA 92704 PHONE 714 540 2230...

Page 20: ...arious scales and foreign material by chemical cleaning is now being quite extensively practiced Certain qualified organizations will check the nature of deposits to be removed furnish proper acid sol...

Page 21: ...risis and optimum control Trim available in 316SS 17 4 pH Alloy 6 PEEK and PTFE Port Guided Plug Assembly provides stability and desired equal percentage flow characteristic Lower Plug offers easy acc...

Page 22: ...Threaded NPT or 316 Stainless Steel 300LB Threaded NPT Trim Linear 316 Stainless Steel Packing Guided Low Friction TFE V Ring Spring Loaded 32 to 450 F Adjustable Graphite Packing 32 to 500 F Tempera...

Page 23: ...70 1 97 1 22 0 96 0 70 0 43 0 17 0 626 4SR 3 40 3 41 2 38 1 64 1 20 0 75 0 51 0 39 0 26 0 13 LINEAR 1 676 FULL 17 2 15 5 13 8 12 0 10 3 8 60 6 88 5 16 3 44 1 72 1 1 2 EQ 1 676 FULL 24 0 22 5 19 7 15...

Page 24: ...Actuator Air Signal to Actuator IN IN IN Actuator Range 3 15 PSI 1 17 PSI 0 30 PSI 0 40 PSI 3 15 PSI 1 17 PSI 0 30 PSI 0 40 PSI 0 626 1 2 9 16 DL49 Low N A 67 226 560 720 720 thru Full N A 226 386 N A...

Page 25: ...e Models BFI_ Full Range Signal 4 20 mA BLI_ Low Range Signal 4 12 mA BHI_ High Range Signal 12 20 mA Options 2SPDT Limit Switches 4 20 mA Feedback Ingress Corrosion Protection NEMA 4X IP66 Approvals...

Page 26: ...itches 4 20 mA Feedback Intelligent with Foundation Fieldbus Models 540_ Full Range Signal 4 20 mA Calibration 3 Button Keypad Foundation Fieldbus Options 2SPDT Limit Switches 4 20 mA Feedback All Mod...

Page 27: ...roximity MARK 1 Position Indication Switches Feedback Settings Valve Type Position Switch 1 3 5 Switch 2 4 6 2820 Valve Closed Closed Open Valve Open Open Closed 2830 32 Upper Port Closed Closed Open...

Page 28: ...g and tagging together B is optional Warren Controls does not assume responsibility for the selection use or maintenance of any product Responsibility for proper selection use and maintenance of any W...

Page 29: ...embly provides stem guiding and protects packing box from entrained solids for longer packing life Thick Balancing Chamber in bronze 300 SS or 17 4pH EPDM O Ring or Fluoraz O Ring for higher temperatu...

Page 30: ...inless Steel or Alloy 6 Packing Guided Low Friction TFE V Ring Spring Loaded O Ring EPDM BRZ Fluoraz 797 300 SSTrim 17 4 pH or Alloy 6 Trim Temperature 32 to 300 F BRZ 32 to 350 F 125 FLG w 300 SSTrim...

Page 31: ...7 23 1 14 0 6 40 6 EQ 360 333 298 255 203 144 83 6 34 1 14 6 7 10 Valve Trim Travel Size IN Style 100 2 1 2 LINEAR 69 3 LINEAR 86 4 LINEAR 156 5 LINEAR 270 6 LINEAR 347 8 LINEAR 450 Valve Trim Travel...

Page 32: ...control signals coming directly from I P transducers with matching ranges The 0 30 and 0 40 columns apply to valves with a positioner or an I P transducer of suitable range 4 N A indicates that the a...

Page 33: ...N A High 10 30 40 N A N A N A 131 N A DL84 Low N A N A 12 N A 54 88 310 N A Full N A N A 12 N A N A N A 208 N A High 63 97 114 N A N A N A 208 N A DL84XR Xtra High 114 148 165 N A N A N A 208 N A DL1...

Page 34: ...ct 21 5 8 22 1 2 23 1 2 24 1 8 24 3 4 N A N A DL84 or 84XR Reverse 21 21 7 8 22 7 8 23 1 2 24 1 8 N A N A DL115 or 115XR Direct 34 34 7 8 35 7 8 36 1 2 37 1 8 38 3 8 39 1 8 DL115 or 115XR Reverse CF C...

Page 35: ...A N A See Note DL84XR DL115XR Reverse N A N A N A See Note Note The spring range of XR eXtended Range actuators varies with travel These actuators require positioners or I P s for modulating control A...

Page 36: ...s 2SPDT Limit Switches 4 20 mA Feedback Intelligent with Foundation Fieldbus Models 540_ Full Range Signal 4 20 mA Calibration 3 Button Keypad Foundation Fieldbus Options 2SPDT Limit Switches 4 20 mA...

Page 37: ...m depending on actuator and travel Proximity MARK 1 Position Indication Switches Feedback Settings Valve Type Position Switch 1 3 5 Switch 2 4 6 2920 22 23 Valve Closed Closed Open Valve Open Open Clo...

Page 38: ...s copper SS tubing T is optional SS tagging G Two lines 24 characters line is optional SS tubing and tagging together B is optional Warren Controls does not assume responsibility for the selection use...

Page 39: ...ody Cast Steel ASTM A216 WCB Stem 303 St Stl ASTM A582 Disc 3 4 5 420 St Stl ASTM A743 CA 40 Disc 6 12 304 St Stl ASTM A167 A240 Seat 3 4 5 420 St Stl ASTM A743 CA 40 Seat 6 12 316 St Stl ASTM A743 79...

Page 40: ...6 7 D8 1 D 869 2 5 D 5 2 D 75 0 D 1 D 52 BD929 D 2C D 8 D D 87 5 D 58 D 58 2 BD D 1 D D 9 D 9 D 7 2 287D 2 D 866 7 D D 98 2 5 D 82 D D 1 9 7D 58 D 8D 1 D 0 5 8 D 8 5 D 7 D D 55 1 D 877 287D 8D 1 D58 D...

Page 41: ...D 869 D 3 270D 9 270 7 25D 1 D 5 D 89 7 D 7 D 4 D 87 85D D 2 D 9 5 7 5BD 184 D 8 7D 87D 1 D B 9 D 7 D 89 7D 8 5 D 89 5 D 7 25D 1 D 0 5 8 D2 D87D 1 D527 D D27 2 2 5D27 287 8 D8 1 D9258 D 3 270D 9 270D8...

Page 42: ...0 5 F 0 3 C Mounting 1 2 NPT Air or Water Connections 1 8 NPT Drain Connection water only 1 4 NPT Shipping Weight 4 lbs 1 8 kg Sensitivity adjustable 3 1 to 27 9 kPa C 1 4 to 2 1 4 psi F Maximum Press...

Page 43: ...limeters Inches TC744 1 Page 3 The parts in Figure 7 are identified by letter in order of disas sembly For item number reference see Parts Drawing A item 3 adjusting knob with set screw B item 10 cove...

Page 44: ...Set Screw holds Accritem in well 1 2 NPT Brass Union Assembly No 744 106 Provides pressure tight connection for installing Accritem in pipe or tank where space does not permit rotation of Accritem bo...

Page 45: ...ed such defects are not due to abuse or chemical decomposition by chemical or galvanic action This express warranty is in lieu of and excludes all other warranties guarantees or representations expres...

Page 46: ...0 14 370 000 Series 174A Set 3 4 x 1 1 x 1 1 4 1 1 4 x 1 1 2 1 1 2 x 2 2 x 2 1 2 Pressure 20 x 25mm 25 x 32mm 32 x 40mm 40 x 50mm 50 x 65mm psi bars Model M3 Model M1 Model M1 Model M Model M 30 2 07...

Page 47: ...5 0 0 1 2 4 3 5 6 S t a r S 2 1 S t a r S 1 6 Wilo Star S 60 Hz 2 Circulating Pumps Product review Wilo Star Star S Function Equipment Technical data Wilo Star Cast iron body Wilo Star Star S Heizung...

Page 48: ...Regelger te Pumpenmanagement Wilo Star S Cast iron body S 16 F S 16 FX S 21 F S 21 FX Approved fluids other fluids on request Heating water Water glycol mixtures max 1 1 mixtures with more than 20 gly...

Page 49: ...roved fluids other fluids on request Heating water Water glycol mixtures max 1 1 mixtures with more than 20 glycol require reassessment of the hydraulic criteria Domestic hot water Performance Max del...

Page 50: ...lation Solarthermie Service Zubeh r Systeme Schalt und Regelger te Pumpenmanagement Wilo Star S Bronze body S 16 BFX S 21 BFX Approved fluids other fluids on request Heating water Water glycol mixture...

Page 51: ...0 7 Q 0 8 0 9 1 0 1 1 1 2 m 3 h 0 0 1 0 2 0 3 0 4 0 02 0 0 04 0 06 0 08 0 5 0 6 0 7 0 8 0 9 1 0 1 1 1 2 Wilo Star 3 BS 60 Hz H ft 1 0 0 2 P 1 W P 1 hp H m 10 0 30 70 3 4 5 6 1 2 3 4 5 6 7 8 9 10 11 U...

Page 52: ...ft P 1 W P 1 hp H m 20 0 60 2 4 6 8 10 12 14 16 18 US gpm 0 m 3 h Q 0 4 0 8 1 2 1 6 2 0 2 4 2 8 3 2 3 6 4 0 4 4 0 24 22 20 5 2 4 8 5 6 2 4 6 8 10 12 14 16 18 US gpm 0 24 22 20 0 04 0 0 08 0 12 0 16 0...

Page 53: ...ar Star S Heizung Klima K lte Trinkwasserzirkulation Solarthermie Service Zubeh r Systeme Schalt und Regelger te Pumpenmanagement Wiring diagramm Single phase motor 2 pole 1 115 V 60 Hz with integrate...

Page 54: ...U 6 5 1 e 8 11 e 16 1 5 e 16 3 3 3 e 16 3 11 e 16 5 1 e 16 1 1 e 4 NPSM 6 5 3 Star 16 F 6 3 e 8 5 1 e 4 7 e 8 1 5 e 16 3 3 e 16 3 1 e 4 3 11 e 16 5 3 e 16 5 3 e 16 6 5 1 Star 16 FX 6 3 e 8 5 15 e 16 7...

Page 55: ...128 3 0 3 Star 16 F 162 134 22 34 81 82 93 5 132 3 0 1 Star 16 FX 162 150 22 50 81 81 93 5 128 3 0 2 Star 16 BFX 162 150 22 50 81 81 93 5 128 3 3 2 Star 17 FX 216 176 33 55 108 82 96 0 130 4 9 2 Star...

Page 56: ...ce Subject to standard terms and conditions of sale Copyright Instrument Division Dresser Industries Inc 5 95 CG 10 21 20M HG rev 10 97 Chicago Illinois 400 W Lake Street Suite 318 Roselle IL 60172 33...

Page 57: ...ange painted black Ring Black painted steel friction fit Chrome plated steel friction fit Window Glass Glass Dial Black figures on white background Black figures on white background Pointer Black alum...

Page 58: ...OUT PRIOR NOTICE AND WITHOUT INCURRING ANY OBLI GATION TO MAKE SUCH CHANGES AND MODIFICATIONS ON 7ATTS PRODUCTS PREVIOUSLY OR SUBSEQUENTLY SOLD 3ERIES AND 8 3ERIES 8 3ERIES 8 3ERIES OB AME ONTRACTOR O...

Page 59: ...and for reference only Certified drawings are available on request Vertical 3 8 1 2 3 4 1 1 1 4 1 1 2 1 4 3 8 1 2 3 4 1 1 1 4 1 1 2 1 3 4 2 1 8 2 3 8 2 15 16 3 1 16 1 1 8 1 3 8 1 5 8 1 7 8 2 5 16 2 1...

Page 60: ...thematically gives the relationship bet ween the rate of flow and the pressure drop The flow formula used was recommended by the Fluid Controls Institute INCHES HG VACUUM NOTE Capacities will vary sli...

Page 61: ...Engaged Length When piping in the vacuum breaker attention should be given to the engaged length E 1 The vacuum breaker should never be installed such that the screen is in the flow path In instances...

Page 62: ...TALLING DIRECT IMMERSION MODELS L6006B Install fitting in boiler tapping as follows 1 Be sure sealing washer is in place as shown in Fig 3 Make sure that spud of capsule compression fitting is screwed...

Page 63: ...To adjust models with adjustable differential rotate the wheel on the back of the snap switch until the desired reading is aligned with the V notch in the frame The wheel provides an adjustment from 5...

Page 64: ...e are covered in the manual supplied with the product All equipment must comply with local codes Ace Heating Solutions LLC 2701 S Harbor Blvd Santa Ana CA 92704 714 540 2230 Fax 714 540 2239 www acehe...

Reviews: