6.5.4 Analog Output Configuration
The AVT
’s
Analog Output is primarily used to provide an analog signal representing the Airflow
Volume flowing through the valve. The signal type and full-scale range of the Analog Output
are user-defined values that are configured by clicking on the boxes adjacent to each heading.
The following examples show the two different options for configuring the Analog Output.
Example 1
shows the Signal Source set to “Valve Airflow” which is the most common
configuration. Example 2
shows the Signal Source set to “Manual Output” which is typically
used for troubleshooting wiring issues.
EXAMPLE 1
EXAMPLE 2
Analog Output Signal Source =
Valve Airflow
Analog Output Signal Source =
Manual Output
Select Signal Source
; Valve Airflow or Manual Output
Select Signal Type
; 0-20mA, 4-20mA, 0-5v, 1-5v, 0-10v, 2-10v
Enter
the Analog Output
Full Scale Range
Displays the real time value based on the Full Scale units
Displays the real time analog signal value