Accuthermo Technology Corp.
20
TR2
(10K)
-10.0 °C ~ 150.0°C
x002D
HILT
Same as LOLT parameters
200.0
°C/°F
x002E
TUNT
x0022 / Sec (controller time unit in sec)
Sec
Index
Code
x0023 / Min (controller time unit in min)
x002F
EROP
(Select output operation when alarm latch)
x0024 / 00 (Alarm1 & Alarm2 OFF, PWM & ENB OFF)
00
Index
Code
x0025 / 01 (Alarm1 ON, Alarm2 OFF, PWM & ENB ON)
x0026 / 10 (Alarm1 ON, Alarm2 ON, PWM & ENB OFF)
x0027 / 11 (Alarm1 ON ,Alarm2 ON, PWM & ENB OFF)
x0030
SPOF
-200.0 ~ 200.0
(set-point offset)
0.0
°C/°F
x0031
PVOF
-200.0 ~ 200.0
(process-value offset)
0.0
°C/°F
x0032
FILT
0.0 ~ 99.9 (noise filter, larger value filter noise better but delay process
operation)
0.0
Coefficient
x0033
ID
255 ~ 1 (controller ID address)
255
address
x0034
STAT
x0028 / OFF (don't save position)
OFF
Index
Code
x0029 / ON (save current position)
x0035
STAR
x002A / ZERO
(run program start SV-t from 0C)
PV
Index
Code
x002B / PV
(run program start SV-t from current PV)
x0036
BAND
0.0 ~ 200.0
20.0
°C/°F
x0037
RT1
0 ~ 9999 (Ramp Time)
60
Sec/Min
x0038
SP1
LOLT ~HILT (1
st
Set Point Value)
20.0
°C/°F
x0039
ST1
0 ~ 9999 (1
st
SP Sock Time)
60
Sec/Min
x003A
SF1
x002C / RT8 (after ST time jump to RT8)
END
Index
Code
x002D / RT7 (after ST time jump to RT7)
x002E / RT6 (after ST time jump to RT6)
x002F / RT5 (after ST time jump to RT5)
x0030 / RT4 (after ST time jump to RT4)
x0031 / RT3 (after ST time jump to RT3)
x0032 / RT2 (after ST time jump to RT2)
x0033 / RT1 (after ST time jump to RT1)
x0034 / END (After prog turn off output)
x0035 / HOLD (After prog hold temperature)
x0036 / NEXT (After prog goto RT2)
x003B
LN1
1~9998 (x270E) Loop number
Infinite loop = 9999 (x270F)
1
count
x003C
RT2
0 ~ 9999
60
Sec/Min
x003D
SP2
LOLT ~HILT
20.0
°C/°F
x003E
ST2
0 ~ 9999
60
Sec/Min
x003F
SF2
x002C / RT8 (after ST time jump to RT8)
END
Index
Code
x002D / RT7 (after ST time jump to RT7)
x002E / RT6 (after ST time jump to RT6)
x002F / RT5 (after ST time jump to RT5)
x0030 / RT4 (after ST time jump to RT4)
x0031 / RT3 (after ST time jump to RT3)
x0032 / RT2 (after ST time jump to RT2)
x0033 / RT1 (after ST time jump to RT1)
x0034 / END (After prog turn off output)
x0035 / HOLD (After prog hold temperature)
x0036 / NEXT (After prog goto RT3)
x0040
LN2
1~9998 (x270E) Loop number
Infinite loop = 9999 (x270F)
1
count