EV/DV300 Series Power Meter
Chapter 3: Operation and Setting
V:2.0 Revised October 2018
30
Access code is needed for going into the
parameter setting mode. Only the person
who knows the access code can do the
parameter setting. The access code is 4
digits decimal number. It is from 0000 to
9999. The factory default is 0000. After key
in the right access code, press V/A to go to
the first parameter setting page, otherwise
go back to the metering data display page.
The first screen: Setting address for
communication purpose in this page. It is
any digit number from 1 to 255. As in Fig
3.12, the address is 17. Changing method
is simple, press key to move cursor to the
digit need to change and press E key for
increasing or P key for decreasing. Then
press V/A key for acknowledgment and
go to the next setting page.
Note:
Each meter on the same RS485 net
should has different address according to
the Modbus-RTU protocol.
The second screen: Baud rate setting page.
The communication protocol Modbus. RTU
in meter is based on asynchronous mode: 8
data bit, no parity, 1 start bit and 1 stop bit.
Baud rate could be one of the five, 1200,
2400, 4800, 9600, 19200 bps. As in Fig 3.13,
the baud rate is 9600 bps. Press E key to
select one baud rate. Press V/A key, go to
the next setting page.
Note:
Please use the same baud rate in
meters on the same communication net.