EV/DV300 Series Power Meter
V:2.0 Revised October 2018
46
4.3 Data Address Table
Basic metering data
All the measuring data in this register area are stored in this register area and are read by
using function code 03.
Table 4.14 Metering data address table
Address
Parameter
Range
Object
Type
Access
0110H
Phase Voltage U1
0~65535
Word
R
0111H
Phase Voltage U2
0~65535
Word
R
0112H
Phase Voltage U3
0~65535
Word
R
0113H
Line Voltage U12
0~65535
Word
R
0114H
Line Voltage U23
0~65535
Word
R
0115H
Line Voltage U31
0~65535
Word
R
0116H
Current I1
0~65535
Word
R
0117H
Current I2
0~65535
Word
R
0118H
Current I3
0~65535
Word
R
0119H
Average phase voltage Uavg
0~65535
Word
R
011AH
Average line voltage Ulavg
0~65535
Word
R
011BH
Average current Iavg
0~65535
Word
R
011CH
Power P
-32768~32767
Integer
R
011DH
Reactive Power Q
-32768~32767
Integer
R
011EH
Apparent Power S
0~65535
Word
R
011FH
Frequency F
4400~6500
Word
R
0120H
Power factor PF
-1000~1000
Integer
R
0121H
Load nature RT
76/67/82 (L/C/R)
Word
R
0122H
Analog output 1 AO1
0~65535
Word
R
0123H
Analog output 2 AO2
0~65535
Word
R
0124H
Neutral current In
0~65535
Word
R
Energy Data (read by using function code 03, writing by using function code 16)
010CH (Low 16 bit)
Energy Ep
0~999999999
Dword
R/W
010DH (High 16 bit)
010EH (Low 16 bit)
Reactive energy Eq
0~999999999
Dword
R/W
010FH (High 16 bit)