3.5.2 PV connection
It is very important for system safety and efficient operation to use appropriate cable for
PV module connection. To reduce risk of injury, please use the proper recommended cable
size as below.
Wire Size
Cable(mm
2
)
12AWG
4
When selecting proper PV modules, please be sure to consider below parameters:
1
)
Open circuit Voltage (Voc) of PV modules not exceeds max. PV array open circuit voltage of
inverter.
2
)
Open circuit Voltage (Voc) of PV modules should be higher than min. start voltage.
Max. Input Current (A)
12.5A/12.5A
PV Array MPPT Voltage Range
200Vdc-850Vdc
No. of MPP Trackers
2
No. of Strings per MPP Tracker
1+1
3
)
The minimum isolation resistance to ground of the PV string must exceed 33.33kΩ in case
of any shock hazard.
Note: BAT plugs are similar with PV plugs, please confirm before use it.
Follow the steps below to complete the PV connection:
1
)
Prepare PV cables and PV plugs.
Note: Please use PV plugs and connectors in accessory box.
2
)
Connect PV cable to PV connectors.
Note:
1.
PV cable must be tightly crimped into the connectors.
2.
For Amphenol connector, the limit buckle cannot be pressed.
3.
T here will be a click sound if connectors are inset correctly into PV plugs.