- Instruction Manual for ESS R050100-
21
Function
Inverter
Battery
CAN-L
Pin 5
Pin 1
CAN-H
Pin 4
Pin 2
Note:
1.
If you use the inverter's built-in CAN communication line, you need to re-press the battery side
RJ45 port according to the above table.
2.
If you use the system to configure the CAN communication line, you need to pass the
communication line through the inverter's BMS waterproof connector, and then press the inverter
side RJ45 port according to the above table.
3.
Pass the ground wire through the waterproof connector on the cabinet and connect it to the
ground point inside the cabinet.
For equipment safety, the housing of the equipment can be grounded or equipotentiality
connected for the second time. When the original protective conductor fails, it prevents the
current from being touched when the grounding fault occurs, causing personal harm.
The recommended wire specifications for grounding cables are as follows:
Cable requirements
10AWG
,
Yellow and green cable
Wire stripping size
8mm
connection terminal
the ring terminal M6
Note: The output terminal PE on the battery control box has been connected to the cabinet.
3.5 Hybrid inverter cable connection
3.5.1 Hybrid Inverter Grounding
Ground cable shall be connected to ground plate on grid side this prevents electric shock. If the
original protective conductor fails.