39
3.2.15. TSP parameters to be set on the interface and using the Remote Control
Parameter
Editable value
Default values
Notes
P01
Selects boiler type
0 ÷ 8
0
0 = instantaneous
1 = with boiler thermostat
2 = with boiler temperature probe
3 = heating only
P02
Selects gas type
0 … 1
0
0 = natural gas
1 = GPL
P03
Selects the ACS control type
0 ÷ 3
1
0 = flow switch
1 = flow meter
2 = flow meter dedicated to shinoo pump
P04
Adjusting coefficient with external probe
0 ÷ 90
30
P05
Anti Fast Cycles time
0 ÷ 10 min
3
P06
1
DO NOT CHANGE
P07
Ignition Heating ramp [value 1=10s]
0 ÷ 80
12
P08
Selects the maximum heating power (PREMIX)
P10...100
70%
P09
Selects the maximum ACS power
P10…100
80%
P10
Selects the minimum power
0…P09
0%
P11
Selects the minimum heating set-point value
20...P12
25°C
P12
Selects the maximum heating set-point value
P11…80
80°C
P13
Selects the maximum ACS set-point value
35 ÷ 65
55°C
P14
Selects the calibration type
0 ÷ 20
0
0 = manu
5 = auto
P15
Selects the boiler power
0 ÷ 4
4
0 = 24 kW
1 = 28 kW
2 = 32 kW
3 = 16 kW
4 = 20 kW
P16
Not used
P17
Not used
P18
Not used
P19
Thermostat (0) / Fumes probe (1)
0 … 1
1
DO NOT CHANGE
P20
Selects ACS minimum set-point value
10 ÷ 50
10
P21
Selects the low temperature areas
0 … 1
0
0 = high temperature
1= low temperature
P22
Not used
P23
Selects the pump activation time (min): cold
area
0 ÷ 10
0
P24
Children safety
0 ÷ 1
0
1 = enabled
P25
Not used
P26
Selects thewater hammer delay (sec)
0 ÷ 3
0
P27
Selects the pre-heating temperature OFF (°C)
30 ÷ 75
45
P30
Not used
P31
Selectsthe fan start-up speed (P31 x 25) rpm
80 ÷ 160
140
P32
Selectsthe fan maximum speed (P32 x 25) +
2000) rpm
P33...255
170
P33
Selectsthe fan minimum speed (P33 x 25)
30 ÷ 60
36
P36
Not used
P37
Probe AUX configuration
3 ÷ 3
3
DO NOT CHANGE
P38
Selects the antifreeze temperature
0…+10
5
P39
Selects the heating post-circulation time
0 ÷ 99 sec x 10
120
P40
Selects the heating ignition delay time
0 ÷ 60 sec x 5
0
P41
Selects the domestic hot water modulation with
flow meter
0 ÷ 1
1
0 = not enabled
1 = enabled
P42
Enables / disables the ACS pre-heating function
0 ÷ 1
0
0 = disabled
1 = enabled
P43
Selects the ACS activation delay time with solar
configuration
0 ÷ 30 sec
0
P44
Selects the pressure sensor type
0 … 1
1
0 = pressure switch
1 = transducer
P45
Selects the anti-Legionella function (boiler only)
54, 55 ÷ 80
54
54 = disabled
55 ÷ 80 = delivery temperature set
P46
Selects the pump modulating speed
0 … 1
1
0= not modulated
1 = automatic 60% ÷ 100%