34
16.3
MODEL
HPE
60
Configuration with integrated circulator, control via 0-10 volt analogic signal
16.4
MOD.
HPE
60 &
HPE
70
Curves for the model equipped with pump driven by AC inverter.
Absorbed Power
Head pressure
16.5
CIRCULATOR CHARACTERISTICS
Model
i-HP 0125-0135
i-HP 0250-0250F
i-HP 0260
i-HP 0260-0270
Configuration:
Integrated
Auto adaptive
Integrated
Auto adaptive
Integrated
Pump driven by
AC inverter
Max. absorbed power [kW]
310
305
550
450
730
1100
Max. absorbed current [A]
1,37
1,33
2,05
2
3,2
2,5
EEI (energy efficiency index)
≤ 0,23
≤ 0,23
≤ 0,23
≤ 0,23
≤ 0,23
/
Because of the circulators have got similar prevalence curves to those integrated, please refer to Paragraph 15 for plant designing.
17
HEAD LOSS CURVES OF THE HYDRONIC CIRCUIT
We obtain the pressure head of the circulating pump from the addition of the head losses of the hydronic circuit and the available
head pressure.
For example: for the model i-HP 0125 with nominal water flow 1,01 L/s we obtain: 30 kPa (head loss) + 88 kPa (available head
pressure)=118 kPa (circulator head pressure).
It’s advisable to use:
-
the adjustment scale on the right of the knob (constant
∆
P) in the case of use of thermostatic valves on the plant
-
the adjustment scale on the left of the knob (variable
∆
P) in the case of use of 3-way valves on the plant
Head pressure
Input power P1