RG66004288-09
all copying, even partial, of this manual is strictly forbidden
11
5 TECHNICAL FEATURES
5.1
RPE
WATER CHILLERS RATED TECHNICAL DATA
»
RPE
water chillers rated technical data
RPE
019
023
027
Power supply
V-ph-Hz
400 - 3 - 50
Cooling capacity
(1)(E)
kW
19,70
22,50
26,40
Total power input
(1)(E)
kW
6,61
7,53
9,50
Absorbed rated current
(1)
A
13,11
14,68
16,67
EER
(1)(E)
2,98
2,99
2,78
SEER
(2)(E)
3,80
3,80
3,80
Eurovent efficiency class
(1)(E)
B
B
C
Maximum current absorption
A
24
26
32
Star up current
A
105
133
133
Startup current with soft starter
A
72
110
91
Compressors / circuits
1 / 1
no. of axial fans
4
4
4
Air flow rate
(3)
m³/h
9990
9307
9307
Water flow
(1)
l/h
3406
3883
4560
Water pressure drop
(1)(E)
kPa
51
49
34
Available pressure head - LP pumps
(1)
kPa
124
94
111
Buffer tank volume
dm³
50
50
50
Expansion vessel volume
dm³
5
5
5
Unit connections diameter
“
1 1/4
1 1/4
1 1/4
Height
mm
1274
1274
1274
Depth
mm
605
605
605
Length
mm
1588
1588
1588
Sound power level
(4)(E)
dB(A)
71
72
72
Sound pressure level
(5)
dB(A)
43
43
44
Refrigerant charge
kg
4,2
5,8
6,0
Transport weight unit with pump and tank
kg
281
297
313
Operating weight unit with pump and full tank
kg
317
333
350
(1) Outdoor air temperature 35°C, water temperature 12°C / 7°C (EN14511:2013)
(2) I valori di efficienza η in riscaldamento e raffreddamento si calcolano rispettivamente con le seguenti formule: [η = SCOP / 2,5 - F(1) - F(2)] e [η = SEER / 2,5 - F(1) - F(2)]. Per maggiori informazioni fare riferimento all’approfondimento tecnico
“DIRETTIVA ErP 2009/125/EC” nelle pagine introduttive del catalogo o alla normativa EN14825:2017.
(3) Outdoor air temperature 35°C, water temperature 12°C / 7°C (14511:2013)
(4) Sound power level measured according to ISO 9614
(5) Sound pressure measured at a distance of 10 m in a free field with a directivity factor of 2