25

26

Working temperature of 4-way 
valve changing way

-10℃

10℃

-2℃

Adjustable

 

76

27

Power on time for 4-way valve 
after compressor working

0-15min

2min

Adjustable

 

76

28

Electrical expansive valve 
action selection after 
compressor off

0-1

0

0: Invalid 1: Valid

76

29

Heat pump setting temperature 
control

0-1

0

0: TS1=Real value

1: TS1=Manual value

76

30

Compensation temperature

-10-10℃

0℃

Adjustable

76

31

The sampling period of 
Ambient temperature

2-120min

15min

Adjustable

76

32

E-heater control after Heat
pump reach the temperature

0-1

1

Adjustment

29

33

Temp difference to start e-
heater

1-10℃

3℃

Adjustable

29

34

The max setting temp of e-
heater

65-85℃

75℃

Adjustable

76

35

Switch port application

0-1

0

0: On/off 1: PV 

function   

Adjustment

29

25

Summary of Contents for GREEN 500 S NEW

Page 1: ...1 GREEN 500 S NEW Monobloc heat pump water heater with sanitary storage with additional exchangers GREEN 500 S NEW INSTALLATION MANUAL...

Page 2: ...2 TABLE OF CONTENT 3 3 3 4 5 6 7 8 8 9 11 11 1 1 1 1 1 2 2 2 1 1 2 30 31 SPECIFICATION TEMPERATURE SENSOR CONVERSION TABLE J...

Page 3: ...e experienced particularly in the humidseason Storage room cooling Units can be placed in the storage room as the low temperature keeps the food fresh Hot water and fresh air ventilation Units can be...

Page 4: ...ncorrect operation due to ignoring of instructions may cause harm or damage Install the unit only when it complies with local regulations by laws and standards Check the main voltage and frequency Thi...

Page 5: ...an injury due to possible fire electric shocks the unit falling etc Perform the installation securely and please refer to the installation instructions Incorrect installation could cause an injury due...

Page 6: ...instruction If there is a defect in the drainage piping work water could leak from the unit and household goods could get wet and be damaged Do not clean the unit when the power is ON Always shut OFF...

Page 7: ...S INSIDE PRODUCT BOX Before starting the installation please make sure that all parts are found inside the box The Unit Box Item Quantity Domestic hot water heat pump 1 Operation and Installation Manu...

Page 8: ...scriptions 8 Parts and descriptions 1 000 Water tank Compressor Electronic expansion valve Evaporator 4 way valve Fan plate PCB Fan Controller Thermostat Switch Electrical box PCB for titaniumanode Tr...

Page 9: ...c e l E t e l n i r a l o S t e l t u o r e t a w t o H C B A N O L M H D K F G E Lower tank water temp sensor 80 automatic reset protector 85 manual reset protector External Aluminum pipe Upper tank...

Page 10: ...e water contained in the tank In case the titanium anode does not work correctly the error code E6 appears in the display of the Unit This unit has automatic disinfection cycle which starts every 7 da...

Page 11: ...t it is done with care an inclination angle up to 30 degrees is permitted both during transport and storage Ambient temperatures of 20 to 70 degrees Celsius are permitted Transport using a forklift Wh...

Page 12: ...connected portion airflow and capacity in heat pump unit willlose If the unit connects with air ducts it should be DN 180mm for pipes or 180mm internal diameter flexible hose Total length of the duct...

Page 13: ...on sketch The discharge pipe connected to the one way safety valve is to be installed in a continuously downward direction and in a frost free environment 13 Domestic Hot Water T h e r m a l S o l a r...

Page 14: ...t the tank is full Turn off all valves and check all pipes If any leakage please repair If the inlet water pressure is less than 0 15MPa a pressure pump should be installed at the water inlet For ensu...

Page 15: ...very low outside temperatures during the winter 2 Hot water and dehumidification Units can be placed in the laundry room or clothing room When it produces hot water it lowers the temperature and dehum...

Page 16: ...ent corrosion damage make sure that the materials used in the piping system are compatible 6 When installing the pipe work on the customers site any contamination of the piping system must be avoided...

Page 17: ...ke sure that the power supply is normal and the wire connectionis ok Check the inlet water pressure make sure that the pressure is sufficient above 0 15Mpa Check if any water flows out from the hot wa...

Page 18: ...power whole icons are displayed on the controller screen for 3 seconds After checking if everything is ok the unit enters into the standby mode 2 button Press this button and keep for 2 seconds when...

Page 19: ...e clock setting interface hour and minute icons 88 88 flash together Short press button to switch hour minute setting press the and buttons to set the exact hour s and minute s Press button again to c...

Page 20: ...em parameterchecking interface Pressthe and buttonsto check the system parameters 3 Adjust thesystem parameters 8 Error codes During standby or running status if there isamalfunction theunit will stop...

Page 21: ...the fan will stop when the water temperature reaches the set point and unit is standby 3 Electrical heating The icon indicates that the electrical heating function is enabled The electrical heater wil...

Page 22: ...3 Extra PV control function The new PV function has been added in the main control board it can be used to store energy in the tank in case of good solar insolation To enable the PV function it s nece...

Page 23: ...mp disinfection TS3 Upper tank water temp 50 70 70 Adjustable 29 5 High temp disinfection time t2 0 90min 30min Adjustable 29 6 Defrosting period t3 30 90min 45min Adjustable 76 7 Temp to enter defros...

Page 24: ...eturn water pump 1 15 2 Adjustable 29 17 Temperature difference to start solar water pump 5 20 5 Adjustable 29 18 Temperature difference to stop solar water pump 1 4 2 Adjustable 29 19 E heater or hea...

Page 25: ...p setting temperature control 0 1 0 0 TS1 Real value 1 TS1 Manual value 76 30 Compensation temperature 10 10 0 Adjustable 76 31 The sampling period of Ambient temperature 2 120min 15min Adjustable 76...

Page 26: ...mp sensor failure P3 3 flashes 1 dark Suction temp sensor failure P4 4 flashes 1 dark Ambient temp sensor failure P5 5 flashed 1dark Return water solar water tank temp sensor failure P6 Bright Emergen...

Page 27: ...make sure the electrical components are good and the wiring is well If there is a damaged part or a strange smell please replace it in time If the heat pump is not used for a long time please drain o...

Page 28: ...his equipment contains fluorinated greenhouse gases covered by the Kyoto Protocol It should only be serviced or dismantled by professional trained personnel This equipment contains R134a refrigerant i...

Page 29: ...29 c or control board electronic anode T6 WIRING DIAGRAM GREEN 500 S NEW Additionally the sensor T6 shall be connected The load connect the...

Page 30: ...30 4501 HEA 0 2 0 94 02 4 4 2 0 2 0 0 Model 4 2 20 2 2009 4 2 2 40 2 GREEN 500 S NEW U M Model TECHNICAL DATA TABLE GREEN 500 S NEW...

Page 31: ...5 38 3 037 3 082 3 128 79 0 796 0 819 0 842 2 15 231 15 561 15 896 39 2 929 2 974 3 019 80 0 773 0 795 0 818 1 14 559 14 867 15 18 40 2 826 2 87 2 915 81 0 751 0 773 0 795 0 13 92 14 208 14 501 41 2 7...

Page 32: ...7 3 589 7 230 7 28 43 89 63 11 06 98 3 482 6 219 29 42 05 64 10 67 99 3 378 5 208 30 40 28 65 10 29 100 3 278 4 197 6 31 38 61 66 9 936 101 3 182 3 187 7 32 37 01 67 9 591 102 3 088 2 178 4 33 35 49 6...

Page 33: ...33...

Page 34: ...34...

Page 35: ...35...

Page 36: ...itolo puramente indicativo la A2B Accorroni E G S r l si riserva di apportare eventuali modi che senza alcun preavviso web site www accorroni it e mail a2b accorroni it A2B Accorroni E G s r l Via d A...