Manuale di Installazione e Manutenzione unità di recupero calore ad altissima efficienza -
Very high efficiency heat recovery unit
pag. 29
4 - COLLEGAMENTI ELETTRICI
4 - ELECTRIC CONNECTIONS
fig. 13
4.2 UNIT POWER SUPPLY
• To supply the base unit, connect the supplied 3-wire cable (line, neu-
tral, ground) of section 3G 0,75 to the unit with the electric line pro-
vided.
Only if it is necessary to pass to orientation 2, do the following:
•
Invert the connection of the external air temperature probe (SE)
with the room air probe (SA), exchanging the connectors X21
with X22 on the electronic board (as shown by the arrows in
fig.13).
•
Invert the connection of the supply fan signal cable with the re-
turn fan signal cable, exchanging the connectors X5 with X6 on
the electronic board (as shown by the arrows in fig. 13).
Elenco Ingressi - Uscite scheda elettronica -
List of I / O main PCB
Lay out scheda elettronica -
Main PCB layout
UFL
LINEA ALIMENTAZIONE: PREDISPORRE A
MONTE UNA ADEGUATA PROTEZIONE CON
INTERRUTTORE MAGNETOTERMICO
DIFFERENZIALE
POWER LINE: PROVIDE A PROPER SAFETY
DEVICES EQUIPPED WITH DIFFERENTIAL
MAGNETOTHERMAL SWITCH
Riferimento -
Reference
Funzione -
Function
Pin
UFL
Connettore antenna /
Antenna connector
UFL
UFL
X3
Micro switch 1
1 terra ; 2 sensore
1 - ground ; 2 sensor
X5 (nero /
black)
Controllo ventilatore 1 (ripresa)
Fan 1 control (exhaust)
1) tachimetrica
2) uscita PWM o 0/10V
3) terra
4) +10V
1) tacho
2) uscita PWM o 0/10V
3) ground
4) +10V
X6 (bianco / white
)
Controllo ventilatore 2 (mandata)
Fan 2 control (supply)
1) tachimetrica
2) uscita PWM o 0/10V
3) terra
4) +10V
1) tacho
2) uscita PWM o 0/10V
3) ground
4) +10V
X7
Micro switch 2
1 terra ; 2 sensore
1 ground ; 2 sensor
X8
Relè allarme /
Fault relay output
1 - 2 contatto pulito
1 - 2 potential dry contact
X13, X14
Alimentazione ventilatori /
Fans power supply
1 linea; 2 terra; neutro
1 L switched; 2 ground; 3 neutral
X17
Resistnza Preriscaldo /
Preheater
1) Linea
2) Terra
3) Neutro
1) Line
2) Ground
3) Neutral
X28
Serranda di bypass 230 V /
By-pass 230V motor
1) uscita 2 / chiuso
2) uscita 1 / aperto
3) linea
1) out 2 / close
2) out 1 / open
3) Line
X20 (nero / black)
-
-
-
X21 (nero / black)
Sensore di temperatura aria ripresa SA /
Return air temperature sensor input
SA
1 terra ; 2 sensore
1 ground ; 2 sensor
X22 (bianco/white)
Sensore di temperatura aria esterna SE /
External air temperature sensor input SE
1 terra ; 2 sensore
1 ground ; 2 sensor
X23 (bianco/white)
-
-
-
X27
Alimentazione 230 Vac /
230Vac power supply input
1) Linea
2) Terra
3) Neutro
1) Line
2) Ground
3) Neutral
X25
Fireplace /
Hood input
1 terra ; 2 contatto sensore
1 ground ; 2 switch
4.2 COLLEGAMENTO ALIMENTAZIONE UNITÀ
• Per l’alimentazione dell’unità base, collegare il cavo a 3 poli (linea,
neutro e terra) in dotazione di sezione 3G 0,75 all’unità con la linea
elettrica predisposta.
Solo se si deve passare all’orientamento 2, eseguire le seguenti
operazioni:
• Invertire il collegamento della sonda di temperatura aria esterna
(SE) con aria di ripresa (SA), scambiando tra loro i connettori
X21 con X22 sulla scheda elettronica (come evidenziato dalle
frecce in fig.13)
• Invertire il collegamento del cavo di segnale ventilatore mandata
con ventilatore ripresa, scambiando tra loro i connettori X5 con
X6 sulla scheda elettronica (come evidenziato dalle frecce in
fig.13).