REQUIREMENTS FOR THE COMMONWEALTH OF MASSACHUSETTS

The following requirements reference various Massachusetts 

and national codes not contained in this manual. For all 

sidewall horizontally vented gas fueled equipment installed 

in every dwelling, building or structure used in whole or in part 

for residential purposes, including those owned or operated 

by the Commonwealth and where the side wall exhaust vent 

termination is less than (7) feet above finished grade in the 

area of the venting, including but not limited to decks and 

porches, the following requirements shall be satisfied:

Installation of Carbon Monoxide Detectors

 At time of installation of side wall horizontally vented gas 

fueled  equipment,  the  installing  plumber  or  gas-fitter  shall 

observe that a hard wired carbon monoxide detector with an 

alarm and battery back-up is installed on the floor level where 

the gas equipment is to be installed. In addition, the installing 

plumber or gas-fitter shall observe that a battery operated or 

hard wired carbon monoxide detector is installed on each 

additional level of the dwelling, building or structure served 

by the side wall horizontal vented gas fueled equipment. It 

shall be the responsibility of the property owner to secure the 

services of qualified licensed professionals for the installation 

of hard wired carbon monoxide detectors. In the event that 

the side wall horizontally vented gas fueled equipment is 

installed in a crawl space or attic, the hard wired carbon 

monoxide detector with alarm and battery back-up may be 

installed on the next adjacent floor level. In the event that the 

requirements of this subdivision can not be met at the time 

of completion of installation, the owner shall have a period 

of thirty (30) days to comply with the above requirements; 

provided, however, that during said thirty (30) day period, a 

battery operated carbon monoxide detector with an alarm 

shall be installed.

Approved Carbon Monoxide Detectors

Each carbon monoxide detector as required in accordance 

with the above provisions shall comply with NFPA 720 and be 

ANSI/UL 2034 listed and IAS certified.

Signage

A metal or plastic identification plate shall be permanently 

mounted to the exterior of the building at a minimum of eight 

(8) feet above grade directly in line with the exhaust vent 

terminal for the horizontally vented gas fueled heating the 

appliance or equipment. The sign shall read, in print no less 

the one-half inch (1/2) in size, “GAS VENT DIRECTLY BELOW. 

KEEP CLEAR OF ALL OBSTRUCTIONS”.

Inspection

The state or local gas inspector of the side wall horizontally 

vented gas fueled equipment shall not approve the 

installation unless, upon inspection, the inspector observes 

carbon monoxide detectors and signage installed in 

accordance with the provisions of 248 CMR 5.08 (2) (a) 1 

through 4.

Exemptions

 The following equipment is exempt from 248 CMR 5.08 (2) 

(a) 1 through 4: The equipment listed in Chapter 10 entitled 

“Equipment Not Required To Be Vented” in the most current 

edition of NFPA 54 as adopted by the Board; and Product 

Approved side wall horizontally vented gas fueled equipment 

installed in a room or structure separate from the dwelling, 

building or structure used in whole or in part for residential 

purposes.

Manufacturer Requirements

Gas Equipment Venting System Provided: When the 

manufacturer of Product Approved side wall horizontally 

vented gas equipment provides a venting system design 

or venting system components with the equipment, the 

instructions provided by the manufacturer for installation of 

the equipment and the venting system shall include:
•  Detailed instructions for the installation of the venting 

system design or the venting system components; and

•  A complete parts list for the venting system design or 

venting system.

Gas Equipment Venting System NOT Provided

When the manufacturer of Product Approved side wall 

horizontally vented gas equipment does not provide the 

parts for venting the flue gases, but identifies “special venting 

systems”, the following requirements shall be satisfied by the 

manufacturer:
•  The referenced “special venting systems” instructions shall 

be included with the appliance or equipment installation 

instructions and;

•  The “special venting systems” shall be Product Approved 

by the Board, and the instructions for that system shall 

include a parts list and detailed installation instructions.

A copy of all installation instructions for all Product Approved 

side wall horizontally vented gas fueled equipment, all venting 

instructions, all parts lists for venting instructions, and/or all 

venting design instructions shall remain with the appliance or 

equipment at the completion of the installation.

OVERVIEW

Summary of Contents for AH2818i

Page 1: ...s probl mes de reproduction Pour plus d informations visitez www P65warnings ca gov Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance WH...

Page 2: ...Clackamas Oregon Standards ANSI Z21 88 2017 CSA 2 33 2017 Vented Gas Fireplace Heaters CSA 2 17 2017 Gas Fired Appliances for Use at High Altitudes CSA P 4 1 2015 Testing Method for Measuring Annual...

Page 3: ...S LINE CONNECTION 19 Gas Conversion sold separately 19 Gas Line Installation 19 FACING AND FINISHING 19 Clearances to Combustibles 19 LOG LINER SAFETY BARRIERS SURROUND INSTALLATION 20 GAS FIREPLACE I...

Page 4: ...nging The Batteries In My Remote Control 34 Why Did My Thermostat Disappear From My Remote 34 Why Won t It Turn On 34 ADJUSTMENT 34 Pressure Testing 34 Inlet Pressure Test 35 Manifold Pressure Test 35...

Page 5: ...eight 24 1 16 613 D Width 32 7 16 824 E Firebox Opening Width 28 5 8 727 F Firebox Opening Height 17 11 16 449 G Back To Gas Line Hole 8 5 8 218 H Bottom To Gas Line Access 1 5 8 42 J Front to Vent Ce...

Page 6: ...arts specifically approved with this appliance may result in property damage or personal injury Part Description A Latch glass assembly B Ember bed C Control valve with burner assembly D Control modul...

Page 7: ...n ignition device which automatically lights the pilot Do not try to light the pilot by hand 5 Locate the manual valve installed by your qualified service technician 6 Turn the manual valve clockwise...

Page 8: ...eight 8 feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating the appliance or equipment The sign shall read in print no less the one half inc...

Page 9: ...atures Children and adults should be alerted to the hazards of high surface temperature and should stay away to avoid burns or clothing ignition It will remain hot for a time after shutdown Allow surf...

Page 10: ...A 54 in the USA CSA B149 1 in Canada is mobile home approved must be properly connected to a venting system is approved to be vented using DuraVent BDM ICC and Olympia venting components The classific...

Page 11: ...ly before attempting installation Failure to do so could result in serious injury property damage or loss of life Operation of improperly installed and maintained venting system could result in seriou...

Page 12: ...s This fireplace insert must be installed on a level surface capable of supporting the fireplace insert and venting This fireplace insert may be installed in a bedroom Please be aware of the large amo...

Page 13: ...s appliance must not share or be connected to a chimney flue serving any other appliance TERMINATION LOCATION Approved vent caps require 12 in 305mm clearance to intersecting walls overhangs or eaves...

Page 14: ...cm B Clearance to window or door that may be opened 6 in 15 cm for appliances 10 000 Btu h 3 kW 12 in 30 cm for appliances 10 000 Btu hr 3 kW and 100 000 Btu h 30 kW 36 in 91 cm for appliances 100 00...

Page 15: ...in a proper workmanship like manner The access hole must be plugged with non combustible insulation after the gas supply line has been installed Run gas line to the gas fireplace insert through the ga...

Page 16: ...ombustion air intake pipes to total chimney length required 2 Slide the combustion air intake pipe over termination cap collar Secure to termination cap with three 3 self tapping screws 3 Place a bead...

Page 17: ...tallation manual 4 From inside the existing fireplace carefully pull ropes if used or the flexible pipes down until both exhaust pipe and combustion air intake are into the existing fireplace firebox...

Page 18: ...le through access slot at the top of appliance and place pull handle hook through the hole in pull rod Simultaneously push the gas insert into existing fireplace and pull the air duct forward until se...

Page 19: ...ved 1 2 in 13 mm tee handle manual shut off valve and flexible gas connector are to be connected to the 1 2 in 13 mm control valve inlet If substituting for these components please consult local codes...

Page 20: ...STALLATION Certified Log Sets Ridgewood Timber AH2818LGRT Riverside AH2818LGR Certified Surrounds AH2818SSM AH2818SLG Certified Liner Sets Aged Red Brick AH2818LARB Black Tie AH2818LBT Baker Street AH...

Page 21: ...of the 2 tabs located at the top of the firebox Install Glass Assembly 1 Align the slots on top of the glass assembly over the tabs at the top of the firebox while lowering the bottom of the glass as...

Page 22: ...hich has been under water Electrical Grounding Instructions This appliance is equipped with a three prong grounding plug for your protection against shock hazard and should be plugged directly into a...

Page 23: ...23 Wiring Schematics MALE END VARIABLE SPEED FAN VARIABLE LIGHT APPLIANCE GROUND STAR BATTERY PACK 885 PROFLAME MAIN ON OFF SWITCH PILOT PILOT BURNER FLAME SENSOR IGNITER SW1 BUTTON RED INSTALLATION...

Page 24: ...cated in the bottom cavity of the firebox Complete Valve Assembly To make working on components easier this fireplace has been designed with the valve pilot shutter boxes shutter cables and gas lines...

Page 25: ...Shutter Cable Shutter Cable Tube MTG Brkt Shutter Adjustment Sleeve Shutter Adj Top Assembly Shutter Adj Bottom Assembly Bulk Head Burner Orifice Pilot MTG Box Weldment Burner Mount Plate Valve Assemb...

Page 26: ...e is stable and does not lift off burner If flame lifts off burner turn off and check that all vent pipes are twist locked and leak proof the vent cap is right side up and that 1000 F sealant has been...

Page 27: ...desired temperature is displayed in the thermostat temperature window The fan will turn on 5 minutes after startup and will turn off 12 1 2 minutes after the flames turn off The flame height can be ad...

Page 28: ...b If the thermostat icon displays as ON Normal Thermostat it will only ignite if the thermostat temperature is greater than the room temperature c If the thermostat icon displays as SMART Smart Thermo...

Page 29: ...IPI And CPI Modes Intermittent Pilot and Continuous Standing Pilot Features First lights a pilot then uses the pilot to ignite the main burners The pilot can be set in the CPI Continuous Pilot Ignitio...

Page 30: ...niter will begin to spark After the pilot lights and is established the valve will automatically open and the burner will light The burner will initially light to full flame Adjust it to an appealing...

Page 31: ...tats Unis seulement ou une maison mobile install e en permanence l o les codes locaux le permettent Voir le manuel d installation du foyer pour les d tails Cet appareil ne doit pas fonctionner avec u...

Page 32: ...n Recommended steps for yearly maintenance IMPORTANT Any adjustments to burner pilot or logs must be done by a qualified authorized service person 1 Remove logs and coals and clean away any foreign ma...

Page 33: ...press both the mode button and the thermostat button 3 Look at the LCD display to verify that your desired indicator F or C is being displayed If not repeat Step 2 What Should I Do If Sooting Occurs...

Page 34: ...may have been pressed while the batteries were changed To make your thermostat reappear follow these steps 1 Remove one battery 2 Press and hold the thermostat button on the remote 3 Reinstall the ba...

Page 35: ...sure tap B to verify it is completely sealed The manometer should read no pressure when pilot and burner are on Make sure to apply these incoming pressure test with all other gas fireplaces on or at f...

Page 36: ...all shutter adjustments can be made by the following procedure 1 Air shutter controls are located at the bottom of the fireplace next to the valve assembly 2 If flame is too blue push the air shutter...

Page 37: ...ual to determine that all wiring connections are secure and correct Gas supply turned off Check remote shut off valves from the fireplace Usually there is a valve near the main gas line There may be m...

Page 38: ...ssary Excessive draft A restrictor may need to be installed or modified Soot appears on glass Improper log placement Refer to Log Set Installation section Improper venturi setting Venturi air shutter...

Page 39: ...ervice Person Frequency Every 6 months Action Disconnect the fans from electrical current and vacuum The bearings are sealed and require no oiling Vent System If the vent air intake system is disassem...

Page 40: ...for servicing an appliance must be replaced prior to operating the appliance Performed by Qualified Service Person Frequency Annually Action Inspect the glass for cracks scratches and nicks Verify the...

Page 41: ...etir pour entretenir un appareil doit tre r install avant une r utilisation de l appareil Effectu par Technicien d entretien qualifi Fr quence Annuelle Action Inspectez la vitre pour d tecter les fiss...

Page 42: ...s 6 mois Action D branchez les ventilateurs du courant lectrique est passez l aspirateur Les roulements sont herm tiques et ne n cessitent aucune lubrification Syst me d vent Si le syst me d admission...

Page 43: ...es si n cessaire Tirage excessif L installation ou la modification d un r ducteur peut tre n cessaire De la suie appara t sur la vitre Placement incorrect des b ches Voir la section Installation des s...

Page 44: ...blis et s curis s L alimentation en gaz est teinte V rifier les vannes d arr t distance du foyer En principe il y a une vanne pr s de la conduite de gaz Il peut y avoir plus d une 1 vanne entre le foy...

Page 45: ...t tre r alis s en suivant la proc dure ci apr s 1 Les commandes de l obturateur d air sont situ es au bas du foyer c t de l assemblage de la vanne 2 Si la flamme est trop bleue poussez le bouton de l...

Page 46: ...orsque la veilleuse et le br leur sont en marche Assurez vous d appliquer ces tests de pression d entr e avec tous les foyers au gaz en fonctionnement ou pleine capacit de la maison afin d obtenir des...

Page 47: ...n du thermostat de la t l commande et maintenez le enfonc 3 R installez la pile tout en maintenant le bouton du thermostat enfonc 4 Si vous voyez set s afficher le bouton du thermostat est maintenant...

Page 48: ...ppuyez simultan ment sur le bouton du mode et le bouton du thermostat 3 Regardez l cran cristaux liquides pour v rifier que l unit souhait e s affiche F ou C Dans le cas contraire r p tez l tape 2 Que...

Page 49: ...uel IMPORTANT Tout ajustement du br leur de la veilleuse ou des b ches doit tre r alis par un technicien qualifi et agr 1 Retirez les b ches et les braises et nettoyez toute mati re trang re peluches...

Page 50: ...un autre type de gaz moins d installer un kit de conversion de gaz certifi Cet appareil doit tre install selon les codes locaux s il y en a suivez le National Fuel Gas Code ANSI z223 1 NFPA 54 ou le...

Page 51: ...ilisation de la veilleuse la vanne va s ouvrir automatiquement et le br leur va s allumer Le br leur va s allumer initialement pleine flamme Adaptez la un environnement attrayant avec la t l commande...

Page 52: ...llement Modes IPI et CPI Les fonctions de veilleuse intermittente IPI et veilleuse continue constante CPI allument d abord une veilleuse puis l utilsent pour allumer les br leurs principaux On peut r...

Page 53: ...lumer seulement si la temp rature du thermostat est sup rieure la temp rature ambiante c Si l ic ne du thermostat affiche SMART thermostat intelligent il va s allumer seulement si la temp rature du th...

Page 54: ...t Le ventilateur se met en marche 5 minutes apr s le d marrage et s teint 12 minutes apr s que les flammes s teignent On peut r gler la hauteur de flamme en cours d utilisation et la vitesse du ventil...

Page 55: ...La flamme est stable et ne se d colle pas du br leur Si la flamme se d colle du br leur mettez hors tension et v rifiez que tous les tuyaux de ventilation sont verrouill s twist locked et qu il n y a...

Page 56: ...Manchon d ajustement de l obturateur R glage de l obturateur Assemblage sup rieur R glage de l obturateur Assemblage inf rieur T te du br leur Orifice du br leur Bo tier soud de la veilleuse Plaque de...

Page 57: ...nts ce foyer a t con u avec la vanne la veilleuse les caissons obturateurs les c bles obturateurs et les conduites de gaz en tant que pi ces d un assemblage pouvant tre retir es Module de commande de...

Page 58: ...AA 1 5 V type AA 1 5 V type AA 1 5 V type AA 885 PROFLAME INTERRUPTEUR PRINCIPAL MARCHE ARR T FUSIBLE 3 15 A T VEILLEUSE BR LEUR D TECTEUR DE FLAMME ALLUMEUR BOUTON SW1 ROUGE MARCHE ARR T MOTEUR D BIT...

Page 59: ...ou contr le de gaz ayant t immerg e dans l eau Instructions de mise la terre Cet appareil est quip d une fiche trois broches de mise la terre pour votre protection contre les risques d lectrocution e...

Page 60: ...anguettes se trouvant en haut de la bo te combustion Installer l assemblage vitr 1 Alignez les encoches en haut de la vitre par dessus les languettes se trouvant en haut de la bo te combustion tout en...

Page 61: ...les mat riaux homologu s lors du remplacement d une d fectueuse ou endommag e AVERTISSEMENT INSTALLATION Simili b ches homologu es Bois Ridgewood AH2818LGRT Riverside AH2818LGR Enceintes homologu es...

Page 62: ...ivent tre raccord s l entr e de la vanne de contr le de po 13 mm En cas de remplacement de ces composants veuillez vous conformer aux codes locaux Si l encastrable est install dans des dimensions mini...

Page 63: ...reil et placez le crochet de la poign e de tirage travers l ouverture dans la tige de traction Poussez l encastrable dans le foyer tout en tirant simultan ment sur la conduite d air vers l avant jusqu...

Page 64: ...u fabricant du syst me d vent 4 De l int rieur du foyer existant tirez soigneusement les c bles si vous en avez utili s es ou les tuyaux flexibles vers le bas jusqu ce que le tuyau d chappement et d e...

Page 65: ...requise de la chemin e 2 Faites glisser le tuyau d entr e d air combustion au dessus du collier du chapeau de sortie Fixez le chapeau de sortie l aide de trois 3 vis autotaraudeuses 3 Placez un cordo...

Page 66: ...rs ou la partie inf rieure de la bo te combustion selon les r gles de l art L orifice d acc s doit tre branch avec une isolation non combustible apr s que la conduite d entr e de gaz ait t install e I...

Page 67: ...po B D gagement c t d une ou d une porte pouvant tre ouverte 6 po 15 cm pour les appareils 10 000 Btu h 3 kW 12 po 30 cm pour les appareils 10 000 Btu hr 3 kW et 100 000 Btu h 30 kW 36 po 91 cm pour l...

Page 68: ...eil ne doit ni partager ni tre connect un conduit de fum e desservant un autre appareil EMPLACEMENT DE SORTIE Les chapeaux d vent approuv s exige un d gagement de 305 mm 12 po autour des parois en int...

Page 69: ...stall sur une surface plane en mesure de soutenir l encastrable et l vacuation du foyer Cet encastrable de foyer doit tre install dans une chambre coucher Veuillez pr ter attention la grande quantit d...

Page 70: ...r des blessures graves des dommages mat riels ou la mort Le fonctionnement d un syst me d vacuation mal install et mal entretenu peut entra ner des blessures graves des dommages mat riels ou la mort N...

Page 71: ...est homologu pour les maisons mobiles doit tre correctement raccord un syst me d vacuation est homologu pour une vacuation l aide des composants d vacuation DuraVent BDM ICC et Olympia La classificat...

Page 72: ...temp ratures lev es Les enfants et les adultes doivent tre inform s des risques que comportent les surfaces haute temp rature et doivent demeurer l cart de celles ci pour viter les br lures corporelle...

Page 73: ...horizontalement de l appareil ou l quipement de chauffage La plaque doit comporter l inscription suivante en caract res d au moins un demi pouce 1 2 po VACUATION DE GAZ JUSTE EN DESSOUS NE PAS OBSTRUE...

Page 74: ...une odeur de gaz ARR TEZ Passez l tape B des instructions de s curit sur la portion sup rieure de cette ttiqutte S il n y a pas d odeur de gaz passez l tape suivante 8 Tournez le robinet en sens anti...

Page 75: ...areil sont utilis es des blessures corporelles ou des dommages mat riels peuvent survenir AVERTISSEMENT D B A C E F G Description des pi ces A Assemblage de la vitre du loquet B Lit de braises C Vanne...

Page 76: ...argeur d ouverture de la bo te combustion 26 11 16 678 F Hauteur d ouverture de la bo te combustion 12 11 16 322 G De l arri re l orifice de la conduite de gaz 8 9 16 219 H De la base l acc s de la co...

Page 77: ...l commande de C F 33 Comment puis je passer en mode de s curit enfant 34 Quand dois je changer les piles de ma t l commande 34 Pourquoi mon thermostat dispara t il de ma t l commande 34 Pourquoi l ap...

Page 78: ...air 17 Placer et s curiser l appareil 18 RACCORDEMENT DE LA CONDUITE DE GAZ 19 Conversion de gaz vendu s par ment 19 Installation de la conduite de gaz 19 REV TEMENT ET FINITION 19 D gagements par ra...

Page 79: ...eils au gaz destin s la haute altitude CSA P 4 1 2015 M thodes de test pour mesurer l efficacit annuelle du foyer Cette installation doit tre conforme aux codes locaux ou en l absence de ceux ci au Na...

Page 80: ...de cet appareil ou un autre QUE FAIRE SI VOUS D CELEZ UNE ODEUR DE GAZ N allumez aucun appareil N appuyez sur aucun interrupteur lectrique et n utilisez aucun t l phone dans le b timent Quittez imm d...

Reviews: